To configure advanced SYSTEM SETTINGS
You can only adjust the following the SYSTEM SETTINGS screens and parameters on the thermostat itself. You cannot
access them on a mobile device.
You can select
FACTORY DEFAULTS
to restore all default settings to the original values.
Parameter Name/Description
Default
and
Range
HEAT EQUIP TYPE
— The equipment heating type. If you select
GAS HEAT
and the
COMPRESSOR TYPE
for
HP
, then the defined
DUAL FUEL
thermostat operation is used
for heating.
D:
R:
GAS HEAT
GAS HEAT/ELECTRIC
HEATING EQUIP STAGES
— The number of gas heating stages or E- heating stages in the
equipment.
D:
R:
1
1 to 2
COMPRESSOR TYPE
— The type of the unit's compressors(s).
NOTE
Select
HP
for the
HEAT EQUIP TYPE
to define the auxiliary heat type.
D:
R:
A/C
NONE, A/C, HP
COMPRESSOR STAGES
— The numbers of compressors.
NOTES
•
If
COMPRESSOR TYPE
is set to
HP
, the number of stages also defines the number of
HP heating stages.
•
If set to
3
, the sixth relay output is used for the third-stage compressor and the
thermostat cannot be configured for:
○
Humidifier
○
Humid-MiZer™ dehumidification
○
HP reversing valve operation.
D:
R:
2
NONE, 1 to 3
AUTO ALLOWED
— Enables and disables the thermostat to automatically switch from
heating to cooling to maintain the temperature between the setpoints.
D:
R:
YES
YES/NO
PROG OR NON-PROG
— Allows the thermostat to operate as a non-programmable
(simplified) thermostat or a programmable thermostat with 2 or 4 time periods per day.
D:
R:
PROG
PROG / NON-PROG
MAX HOLD TIME
— The thermostat setpoints cannot be overridden by the user. When the
SCHEDULE PAUSED
button is pressed on the
SETPOINTS
screen (
SCHEDULE IS
RUNNING
), and the user changes the setpoint, the
MAXIMUM TEMPORARY HOLD TIMER
is started with the value selected here and displayed in the clock location.
D:
R:
2 hours
OFF
1-6 hours
FAHRENHEIT OR CELSIUS
— The temperature scale.
D:
R:
°F