Step 5 — Select and Install Ductwork

The design and installation of the duct system must be in
accordance with the standards of the NFPA for installation of
non--residence type air conditioning and ventilating systems,
NFPA 90A or residence--type, NFPA 90B and/or local codes and
ordinances.
Select and size ductwork, supply--air registers, and return air grilles
according to ASHRAE (American Society of Heating,
Refrigeration, and Air Conditioning Engineers) recommendations.
The unit has duct flanges on the supply-- and return--air openings
on the side of the unit.

PERSONAL INJURY HAZARD

Failure to follow this warning could result in personal

injury or death.

For vertical supply and return units, tools or parts could
drop into ductwork Install a 90 degree turn in the return
ductwork between the unit and the conditioned space. If a
90 degree elbow cannot be installed, then a grille of
sufficient strength and density should be installed to
prevent objects from falling into the conditioned space.
Units with electric heaters require 90 degree elbow in
supply duct.

!

WARNING

When designing and installing ductwork, consider the following:

1. All units should have field--supplied filters or accessory

filter rack installed in the return--air side of the unit.
Recommended sizes for filters are shown in Table 1.

2. Avoid abrupt duct size increases and reductions. Abrupt

change in duct size adversely affects air performance.

IMPORTANT

: Use flexible connectors between ductwork and

unit to prevent transmission of vibration. Use suitable gaskets to
ensure weather tight and airtight seal. When electric heat is
installed, use fireproof canvas (or similar heat resistant material)
connector between ductwork and unit discharge connection. If
flexible duct is used, insert a sheet metal sleeve inside duct. Heat
resistant duct connector (or sheet metal sleeve) must extend 24--in.
(610 mm) from electric heater element.

3. Size ductwork for cooling air quantity (cfm). The minimum

air quantity for proper electric heater operation is listed in
Table 2. Heater limit switches may trip at air quantities
below those recommended.

4. Seal, insulate, and weatherproof all external ductwork. Seal,

insulate and cover with a vapor barrier all ductwork passing

through conditioned spaces. Follow latest Sheet Metal and
Air Conditioning

Contractors

National Association

(SMACNA) and Air Conditioning Contractors Association

(ACCA) minimum installation standards for residential
heating and air conditioning systems.

5. Secure all ducts to building structure. Flash, weatherproof,

and vibration--isolate duct openings in wall or roof

according to good construction practices.

CONFIGURING UNITS FOR DOWNFLOW

(VERTICAL) DISCHARGE

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Before performing service or maintenance operations on the

system, turn off main power to unit and install lockout tag.

There may be more than one disconnect switch.

!

WARNING

1. Open all electrical disconnects and install lockout tag before

starting any service work.

2. Remove horizontal (metal) ductcovers to access vertical

(downflow) discharge duct knockouts in unit basepan. (See
Fig. 6.)

3. To remove downflow return and supply knockout covers,

break front and right side connecting tabs with a

screwdriver and hammer. Push cover down to break rear
and left side tabs.

Horizontal Duct Covers

A09076

Basepan
Downflow
(Vertical)
Supply
Knockout 

Basepan
Downflow 
(Vertical)
Return
Knockout 

A09093

Fig. 6 -- Supply and Return Duct Opening

NOTE

: These panels are held in place with tabs similar to an

electrical knockout. Reinstall horizontal duct covers (Fig. 6)
shipped on unit from factory. Insure openings are air and
watertight.

NOTE

: The design and installation of the duct system must be in

accordance with the standards of the NFPA for installation of
nonresidence--type air conditioning and ventilating systems, NFPA
90A or residence--type, NFPA 90B; and/or local codes and
ordinances.
Adhere to the following criteria when selecting, sizing, and
installing the duct system:

1. Units are shipped for side shot installation.
2. Select and size ductwork, supply--air registers, and

return--air grilles according to American Society of Heating,
Refrigeration and Air Conditioning Engineers (ASHRAE)

recommendations.

3. Use flexible transition between rigid ductwork and unit to

prevent transmission of vibration. The transition may be

50V

T

--

A

Содержание COMFORT 50VT-A

Страница 1: ...ndensate Drain Pan 26 Outdoor Fan 26 Electrical Controls and Wiring 26 Refrigerant Circuit 26 Indoor Airflow 26 Metering Devices TXV Piston 26 Pressure Switches 27 Loss of Charge Switch 27 High Pressu...

Страница 2: ...tructions shipped with curb See Fig 4 Install insulation cant strips roofing and flashing Ductwork must be attached to curb IMPORTANT The gasketing of the unit to the roof curb is critical for a water...

Страница 3: ...3 A09410 Fig 2 50VT A24 30 Unit Dimensions 50VT A...

Страница 4: ...4 A09411 Fig 3 50VT A36 60 Unit Dimensions 50VT A...

Страница 5: ...mm B small common base IN mm B large base IN mm C IN mm D IN mm E IN mm F IN mm G IN mm H IN mm Small or Large CPRFCURB010A00 11 279 10 254 14 356 16 406 47 8 1214 32 4 822 2 7 69 30 6 778 46 1 1170 C...

Страница 6: ...adapt to various sizes or kinds of loads 2 Instruction in any special operation or precaution 3 Condition of the load as it relates to operation of the lifting kit such as balance temperature etc Foll...

Страница 7: ...commended 4 Seal insulate and weatherproof all external ductwork Seal insulate and cover with a vapor barrier all ductwork passing through conditioned spaces Follow latest Sheet Metal and Air Conditio...

Страница 8: ...be using a minimum of field supplied 3 4 in PVC or field supplied 3 4 in copper pipe at outlet end of the 2 in 51 mm trap See Fig 9 Do not undersize the tube Pitch the drain tube downward at a slope o...

Страница 9: ...o that they do not interfere with operation of unit A gray wire is standard on 3 phase units for connection to an economizer If an accessory electric heater is installed low voltage leads from heater...

Страница 10: ...1000 10 x 10 254 x 254 1 2 1200 11 x 10 279 x 254 3 4 1400 11 x 10 279 x 254 3 4 1600 11 x 10 279 x 254 1 1750 11 x 10 279 x 254 1 High Pressure Switch psig Cutout Reset Auto 650 15 420 25 Loss of Cha...

Страница 11: ...11 A11002 Fig 12 Connection Wiring Schematics 208 230 1 60 50VT A...

Страница 12: ...12 A11001 Fig 12 Cont Ladder Wiring Schematics 208 230 1 60 50VT A...

Страница 13: ...13 A11006 Fig 13 Connection Wiring Schematics 208 230 3 60 50VT A...

Страница 14: ...14 A11005 Fig 13 Cont Ladder Wiring Schematics 208 230 3 60 50VT A...

Страница 15: ...15 A10195 Fig 14 Connection Wiring Diagram 460 3 60 50VT A...

Страница 16: ...16 A10195 Fig 14 Cont Ladder Wiring Diagram 460 3 60 50VT A...

Страница 17: ...P Checking Cooling and Heating Control Operation Start and check the unit for proper control operation as follows 1 Place room thermostat SYSTEM switch or MODE control in OFF position Observe that blo...

Страница 18: ...uctions and adjusted properly ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Disconnect electrical power to the unit and install lockout tag before cha...

Страница 19: ...ressure 3 Select speed tap from Table 4 that will achieve required airflow from Table 2 4 Remove the vinyl cap off of the desired speed tap wire Refer to Table 3 for color coding 5 Connect the desired...

Страница 20: ...he Heating mode Defrost The defrost control is a time temperature control which includes a field selectable time period DIP switch 1 and 2 on the board between defrost cycles of 30 60 90 or 120 minute...

Страница 21: ...ack cfm 2461 2409 2339 2286 2192 2140 2062 1968 1874 50VT A60 Low Blue cfm 1445 1389 1341 1281 1236 1189 1139 1072 1027 Med Low Pink cfm 1678 1635 1602 1558 1513 1474 1438 1404 1349 Medium 1 Red cfm 1...

Страница 22: ...0 10 0 12 0 13 0 15 0 17 0 18 0 20 0 23 Table 9 Electric Heat Pressure Drop Table in W C Small Cabinet 24 36 STATIC STANDARD CFM SCFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 5kw 0 00 0...

Страница 23: ...air filter s at least once each month and replace throwaway type or clean cleanable type at least twice during each cooling season and twice during the heating season or whenever the filter becomes cl...

Страница 24: ...24 A09412 Fig 18 Cooling Charging Table Subcooling 50VT A...

Страница 25: ...OF2 OF1 ON QUIET SHIFT 120 30 60 60 30 90 INTERVAL TIMER OFF P3 DFT O R W 2 Y C T2 C C O DFT T1 Y P1 J1 SPEEDUP Speedup Pins Defrost interval DIP switches Quiet Shift A08020 Fig 19 Defrost Control 50V...

Страница 26: ...trical Controls and Wiring Inspect and check the electrical controls and wiring annually Be sure to turn off the electrical power to the unit Remove access panels see Fig 22 to locate all the electric...

Страница 27: ...gerant System This step covers the refrigerant system of the 50VT A including the compressor oil needed servicing systems on roofs containing synthetic materials the filter drier and refrigerant charg...

Страница 28: ...ch must be removed remove and recover all system charge so that pressure gauges read 0 psig Never open system without breaking vacuum with dry nitrogen Check Defrost Thermostat The defrost thermostat...

Страница 29: ...ils S Vacuum pumps will not remove moisture from oil S Do not use liquid line filter driers with rated working pressures less than 600 psig S Do not leave Puron suction line filter driers in line long...

Страница 30: ...efective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace thermostat Faulty condenser fan motor or capacitor Replace Restriction in refrigerant syst...

Страница 31: ...D IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE COMPRESSOR AMPS INDOOR EVA...

Страница 32: ...S 7310 W Morris St S Indianapolis IN 46231 Edition Date 01 11 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 50VT 0...

Отзывы: