Table 1 – Physical Data -- Unit 50VT--A

50VT-A24

50VT-A30

50VT-A36

50VT-A42

50VT-A48

50VT-A60

Unit Size

2

2.5

3

3.5

4

5

Shipping Weight (lb)

(kg)

354

161

346

157

426

193

472

214

460

209

506

230

Compressor Quantity

1

Type

Scroll

Refrigerant

R-410A

Refrigerant Quantity (lb)

Quantity (kg)

11.1

5.0

10.3

4.7

9.9

4.5

11.3

5.1

12.5

5.7

15.2

6.9

Refrigerant Metering Device

Indoor TXV, Outdoor Dual Accuraters

Orifice OD (in)

(mm)

0.032 (2)

0.81 (2)

0.037 (2)

0.94 (2)

0.038 (2)

0.97 (2)

0.040 (2)

1.02 (2)

0.040 (2)

1.02 (2)

0.049 (2)

1.24 (2)

Outdoor Coil

Rows...Fins/in,

face area (sq. ft.)

2...21

13.6

2...21

13.6

2...21

13.6

2...21

17.5

2...21

17.5

2...21

23.3

Outdoor Fan

Nominal Airflow (cfm)

Diameter (in.)

Diameter (mm)

Motor hp (rpm)

2500

24

610

1/10 (810)

2700

24

610

1/5 (810)

3100

26

660

1/5 (810)

3100

26

660

1/5 (810)

3100

26

660

1/5 (810)

3500

26

660

1/4 (810)

Indoor Coil

Rows...Fins/in,

face area (sq. ft.)

3...17

3.7

3...17

3.7

3...17

4.7

3...17

4.7

3...17

5.6

3...17

5.6

Indoor Blower

Nominal Airflow (cfm)

Size (in.)

Size (mm)

Motor hp (rpm)

800

10 x 10

254 x 254

1/2

1000

10 x 10

254 x 254

1/2

1200

11 x 10

279 x 254

3/4

1400

11 x 10

279 x 254

3/4

1600

11 x 10

279 x 254

1

1750

11 x 10

279 x 254

1

High Pressure Switch (psig)

Cutout

Reset (Auto)

650 +/- 15

420 +/- 25

Loss-of-Charge/Low Pressure Switch (psig)

Cutout

Reset (Auto)

20 +/- 5

45 +/- 10

Return Air Filters

disposable (in)

(mm)

20x20x1

508x508x25

20x24x1

508x610x25

24x30x1

610x762x25

24x36x1

610x914x25

*Required filter sizes shown are based on the larger of the AHRI (Air Conditioning Heating and Refrigeration Institute) rated cooling airflow or the heating airflow

velocity of 300 ft/minute for throwaway type or 450 ft/minute for high---capacity type. Air filter pressure drop for non---standard filters must not exceed 0.08 IN.

W.C.

{

If using accessory filter rack refer to the filter rack installation instructions for correct filter size and quantity.

}

For 460 volt units, add 14 lb (6.4 kg) to the weight.

Table 2 – Minimum Airflow for Reliable Electric Heater Operation (CFM)

SIZE

50VT--A24

50VT--A30

50VT--A36

50VT--A42

50VT--A48

50VT--A60

AIRFLOW (CFM)

800

1025

1250

1400

1710

1800

INDOOR
THERMOSTAT

DISCONNECT
PER NEC

FROM
POWER
SOURCE

RETURN
AIR

TOP COVER

POWER ENTRY

CONTROL ENTRY

A09098

Fig. 11 -- Typical Installation

50V

T

--

A

Содержание COMFORT 50VT-A

Страница 1: ...ndensate Drain Pan 26 Outdoor Fan 26 Electrical Controls and Wiring 26 Refrigerant Circuit 26 Indoor Airflow 26 Metering Devices TXV Piston 26 Pressure Switches 27 Loss of Charge Switch 27 High Pressu...

Страница 2: ...tructions shipped with curb See Fig 4 Install insulation cant strips roofing and flashing Ductwork must be attached to curb IMPORTANT The gasketing of the unit to the roof curb is critical for a water...

Страница 3: ...3 A09410 Fig 2 50VT A24 30 Unit Dimensions 50VT A...

Страница 4: ...4 A09411 Fig 3 50VT A36 60 Unit Dimensions 50VT A...

Страница 5: ...mm B small common base IN mm B large base IN mm C IN mm D IN mm E IN mm F IN mm G IN mm H IN mm Small or Large CPRFCURB010A00 11 279 10 254 14 356 16 406 47 8 1214 32 4 822 2 7 69 30 6 778 46 1 1170 C...

Страница 6: ...adapt to various sizes or kinds of loads 2 Instruction in any special operation or precaution 3 Condition of the load as it relates to operation of the lifting kit such as balance temperature etc Foll...

Страница 7: ...commended 4 Seal insulate and weatherproof all external ductwork Seal insulate and cover with a vapor barrier all ductwork passing through conditioned spaces Follow latest Sheet Metal and Air Conditio...

Страница 8: ...be using a minimum of field supplied 3 4 in PVC or field supplied 3 4 in copper pipe at outlet end of the 2 in 51 mm trap See Fig 9 Do not undersize the tube Pitch the drain tube downward at a slope o...

Страница 9: ...o that they do not interfere with operation of unit A gray wire is standard on 3 phase units for connection to an economizer If an accessory electric heater is installed low voltage leads from heater...

Страница 10: ...1000 10 x 10 254 x 254 1 2 1200 11 x 10 279 x 254 3 4 1400 11 x 10 279 x 254 3 4 1600 11 x 10 279 x 254 1 1750 11 x 10 279 x 254 1 High Pressure Switch psig Cutout Reset Auto 650 15 420 25 Loss of Cha...

Страница 11: ...11 A11002 Fig 12 Connection Wiring Schematics 208 230 1 60 50VT A...

Страница 12: ...12 A11001 Fig 12 Cont Ladder Wiring Schematics 208 230 1 60 50VT A...

Страница 13: ...13 A11006 Fig 13 Connection Wiring Schematics 208 230 3 60 50VT A...

Страница 14: ...14 A11005 Fig 13 Cont Ladder Wiring Schematics 208 230 3 60 50VT A...

Страница 15: ...15 A10195 Fig 14 Connection Wiring Diagram 460 3 60 50VT A...

Страница 16: ...16 A10195 Fig 14 Cont Ladder Wiring Diagram 460 3 60 50VT A...

Страница 17: ...P Checking Cooling and Heating Control Operation Start and check the unit for proper control operation as follows 1 Place room thermostat SYSTEM switch or MODE control in OFF position Observe that blo...

Страница 18: ...uctions and adjusted properly ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Disconnect electrical power to the unit and install lockout tag before cha...

Страница 19: ...ressure 3 Select speed tap from Table 4 that will achieve required airflow from Table 2 4 Remove the vinyl cap off of the desired speed tap wire Refer to Table 3 for color coding 5 Connect the desired...

Страница 20: ...he Heating mode Defrost The defrost control is a time temperature control which includes a field selectable time period DIP switch 1 and 2 on the board between defrost cycles of 30 60 90 or 120 minute...

Страница 21: ...ack cfm 2461 2409 2339 2286 2192 2140 2062 1968 1874 50VT A60 Low Blue cfm 1445 1389 1341 1281 1236 1189 1139 1072 1027 Med Low Pink cfm 1678 1635 1602 1558 1513 1474 1438 1404 1349 Medium 1 Red cfm 1...

Страница 22: ...0 10 0 12 0 13 0 15 0 17 0 18 0 20 0 23 Table 9 Electric Heat Pressure Drop Table in W C Small Cabinet 24 36 STATIC STANDARD CFM SCFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 5kw 0 00 0...

Страница 23: ...air filter s at least once each month and replace throwaway type or clean cleanable type at least twice during each cooling season and twice during the heating season or whenever the filter becomes cl...

Страница 24: ...24 A09412 Fig 18 Cooling Charging Table Subcooling 50VT A...

Страница 25: ...OF2 OF1 ON QUIET SHIFT 120 30 60 60 30 90 INTERVAL TIMER OFF P3 DFT O R W 2 Y C T2 C C O DFT T1 Y P1 J1 SPEEDUP Speedup Pins Defrost interval DIP switches Quiet Shift A08020 Fig 19 Defrost Control 50V...

Страница 26: ...trical Controls and Wiring Inspect and check the electrical controls and wiring annually Be sure to turn off the electrical power to the unit Remove access panels see Fig 22 to locate all the electric...

Страница 27: ...gerant System This step covers the refrigerant system of the 50VT A including the compressor oil needed servicing systems on roofs containing synthetic materials the filter drier and refrigerant charg...

Страница 28: ...ch must be removed remove and recover all system charge so that pressure gauges read 0 psig Never open system without breaking vacuum with dry nitrogen Check Defrost Thermostat The defrost thermostat...

Страница 29: ...ils S Vacuum pumps will not remove moisture from oil S Do not use liquid line filter driers with rated working pressures less than 600 psig S Do not leave Puron suction line filter driers in line long...

Страница 30: ...efective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace thermostat Faulty condenser fan motor or capacitor Replace Restriction in refrigerant syst...

Страница 31: ...D IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE COMPRESSOR AMPS INDOOR EVA...

Страница 32: ...S 7310 W Morris St S Indianapolis IN 46231 Edition Date 01 11 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 50VT 0...

Отзывы: