Carrier COMFORT 50VT-A Скачать руководство пользователя страница 2

2

Recognize safety information. This is the safety--alert symbol

.

When you see this symbol on the unit and in instructions or manu-
als, be alert to the potential for personal injury. Understand these

signal words: DANGER, WARNING, and CAUTION. These
words are used with the safety--alert symbol. DANGER identifies

the most serious hazards which

will

result in severe personal injury

or death. WARNING signifies hazards which

could

result in per-

sonal injury or death. CAUTION is used to identify unsafe practic-

es which

may

result in minor personal injury or product and prop-

erty damage. NOTE is used to highlight suggestions which

will

result in enhanced installation, reliability, or operation.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Before installing or servicing system, always turn off main

power to system and install lockout tag. There may be

more than one disconnect switch. Turn off accessory heater

power switch if applicable.

!

WARNING

CUT HAZARD

Failure to follow this caution may result in personal injury.
When removing access panels (see Fig. 21) or performing

maintenance functions inside your unit, be aware of sharp

sheet metal parts and screws. Although special care is taken

to reduce sharp edges to a minimum, be extremely careful

when handling parts or reaching into the unit.

!

CAUTION

INTRODUCTION

The 50VT--A heat pump is fully self--contained and designed for

outdoor installation. (See Fig. 1) Standard units are shipped in a
horizontal--discharge configuration for installation on a ground

level slab. Standard units can be converted to downflow (vertical)

discharge configurations for rooftop applications.

RECEIVING AND INSTALLATION

Step 1 — Check Equipment

Identify Unit

The unit model number and serial number are stamped on the unit

identification plate. Check this information against shipping
papers.

Inspect Shipment

Inspect for shipping damage before removing packaging material.

If unit appears to be damaged or is torn loose from its anchorage,
have it examined by transportation inspectors before removal.

Forward claim papers directly to transportation company.

Manufacturer is not responsible for any damage incurred in transit.
Check all items against shipping list. Immediately notify the

nearest equipment distributor if any item is missing. To prevent
loss or damage, leave all parts in original packages until

installation.
If the unit is to be mounted on a curb in a downflow application,
review Step 5 to determine which method is to be used to remove

the downflow panels before rigging and lifting into place. The
panel removal process may require the unit to be on the ground.

Step 2 — Provide Unit Support

Roof Curb

Install accessory roof curb in accordance with instructions shipped

with curb (See Fig. 4). Install insulation, cant strips, roofing, and
flashing. Ductwork must be attached to curb.

IMPORTANT

: The gasketing of the unit to the roof curb is critical

for a watertight seal. Install gasketing material supplied with the
roof curb. Improperly applied gasketing also can result in air leaks
and poor unit performance.
Curb should be level to within 1/4 in. (6 mm) (See Fig. 7). This is

necessary for unit drain to function properly. Refer to accessory
roof curb installation instructions for additional information as

required.

Installation on older “G” series roof curbs.

Two accessory kits are available to aid in installing a new “G”
series unit on an old “G” roof curb.

1. Accessory kit number CPADCURB001A00, (small chassis)

and accessory kit number CPADCURB002A00, (large

chassis) includes roof curb adapter and gaskets for the
perimeter seal and duct openings. No additional

modifications to the curb are required when using this kit.

2. An alternative to the adapter curb is to modify the existing

curb by removing the outer horizontal flange and use

accessory kit number CPGSKTKIT001A00 which includes
spacer blocks (for easy alignment to existing curb) and

gaskets for the perimeter seal and duct openings. This kit is
used when existing curb is modified by removing outer
horizontal flange.

UNIT/STRUCTURAL DAMAGE HAZARD

Failure to follow this caution may result in property

damage.
Ensure there is sufficient clearance for saw blade when

cutting the outer horizontal flange of the roof curb so there

is no damage to the roof or flashing.

!

CAUTION

Slab Mount

Place the unit on a solid, level concrete pad that is a minimum of 4
in. (102 mm) thick with 2 in. (51 mm) above grade (See Fig. 8).

The slab should extend approximately 2 in. (51 mm) beyond the

casing on all 4 sides of the unit. Do not secure the unit to the slab
except when required by local codes.

Step 3 — Provide Clearances

The required minimum service clearances are shown in Fig. 2 and
3. Adequate ventilation and outdoor air must be provided. The

outdoor fan draws air through the outdoor coil and discharges it
through the top fan grille. Be sure that the fan discharge does not

recirculate to the outdoor coil. Do not locate the unit in either a

corner or under an overhead obstruction. The minimum clearance
under a partial overhang (such as a normal house overhang) is 48

in. (1219 mm) above the unit top. The maximum horizontal
extension of a partial overhang must not exceed 48 in. (1219 mm).

IMPORTANT

: Do not restrict outdoor airflow. An air restriction

at either the outdoor--air inlet or the fan discharge may be
detrimental to compressor life.
Do not place the unit where water, ice, or snow from an overhang

or roof will damage or flood the unit. Do not install the unit on
carpeting or other combustible materials. Slab--mounted units

should be at least 4 in. (102 mm) above the highest expected water
and runoff levels. Do not use unit if it has been under water.

50V

T

--

A

Содержание COMFORT 50VT-A

Страница 1: ...ndensate Drain Pan 26 Outdoor Fan 26 Electrical Controls and Wiring 26 Refrigerant Circuit 26 Indoor Airflow 26 Metering Devices TXV Piston 26 Pressure Switches 27 Loss of Charge Switch 27 High Pressu...

Страница 2: ...tructions shipped with curb See Fig 4 Install insulation cant strips roofing and flashing Ductwork must be attached to curb IMPORTANT The gasketing of the unit to the roof curb is critical for a water...

Страница 3: ...3 A09410 Fig 2 50VT A24 30 Unit Dimensions 50VT A...

Страница 4: ...4 A09411 Fig 3 50VT A36 60 Unit Dimensions 50VT A...

Страница 5: ...mm B small common base IN mm B large base IN mm C IN mm D IN mm E IN mm F IN mm G IN mm H IN mm Small or Large CPRFCURB010A00 11 279 10 254 14 356 16 406 47 8 1214 32 4 822 2 7 69 30 6 778 46 1 1170 C...

Страница 6: ...adapt to various sizes or kinds of loads 2 Instruction in any special operation or precaution 3 Condition of the load as it relates to operation of the lifting kit such as balance temperature etc Foll...

Страница 7: ...commended 4 Seal insulate and weatherproof all external ductwork Seal insulate and cover with a vapor barrier all ductwork passing through conditioned spaces Follow latest Sheet Metal and Air Conditio...

Страница 8: ...be using a minimum of field supplied 3 4 in PVC or field supplied 3 4 in copper pipe at outlet end of the 2 in 51 mm trap See Fig 9 Do not undersize the tube Pitch the drain tube downward at a slope o...

Страница 9: ...o that they do not interfere with operation of unit A gray wire is standard on 3 phase units for connection to an economizer If an accessory electric heater is installed low voltage leads from heater...

Страница 10: ...1000 10 x 10 254 x 254 1 2 1200 11 x 10 279 x 254 3 4 1400 11 x 10 279 x 254 3 4 1600 11 x 10 279 x 254 1 1750 11 x 10 279 x 254 1 High Pressure Switch psig Cutout Reset Auto 650 15 420 25 Loss of Cha...

Страница 11: ...11 A11002 Fig 12 Connection Wiring Schematics 208 230 1 60 50VT A...

Страница 12: ...12 A11001 Fig 12 Cont Ladder Wiring Schematics 208 230 1 60 50VT A...

Страница 13: ...13 A11006 Fig 13 Connection Wiring Schematics 208 230 3 60 50VT A...

Страница 14: ...14 A11005 Fig 13 Cont Ladder Wiring Schematics 208 230 3 60 50VT A...

Страница 15: ...15 A10195 Fig 14 Connection Wiring Diagram 460 3 60 50VT A...

Страница 16: ...16 A10195 Fig 14 Cont Ladder Wiring Diagram 460 3 60 50VT A...

Страница 17: ...P Checking Cooling and Heating Control Operation Start and check the unit for proper control operation as follows 1 Place room thermostat SYSTEM switch or MODE control in OFF position Observe that blo...

Страница 18: ...uctions and adjusted properly ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Disconnect electrical power to the unit and install lockout tag before cha...

Страница 19: ...ressure 3 Select speed tap from Table 4 that will achieve required airflow from Table 2 4 Remove the vinyl cap off of the desired speed tap wire Refer to Table 3 for color coding 5 Connect the desired...

Страница 20: ...he Heating mode Defrost The defrost control is a time temperature control which includes a field selectable time period DIP switch 1 and 2 on the board between defrost cycles of 30 60 90 or 120 minute...

Страница 21: ...ack cfm 2461 2409 2339 2286 2192 2140 2062 1968 1874 50VT A60 Low Blue cfm 1445 1389 1341 1281 1236 1189 1139 1072 1027 Med Low Pink cfm 1678 1635 1602 1558 1513 1474 1438 1404 1349 Medium 1 Red cfm 1...

Страница 22: ...0 10 0 12 0 13 0 15 0 17 0 18 0 20 0 23 Table 9 Electric Heat Pressure Drop Table in W C Small Cabinet 24 36 STATIC STANDARD CFM SCFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 5kw 0 00 0...

Страница 23: ...air filter s at least once each month and replace throwaway type or clean cleanable type at least twice during each cooling season and twice during the heating season or whenever the filter becomes cl...

Страница 24: ...24 A09412 Fig 18 Cooling Charging Table Subcooling 50VT A...

Страница 25: ...OF2 OF1 ON QUIET SHIFT 120 30 60 60 30 90 INTERVAL TIMER OFF P3 DFT O R W 2 Y C T2 C C O DFT T1 Y P1 J1 SPEEDUP Speedup Pins Defrost interval DIP switches Quiet Shift A08020 Fig 19 Defrost Control 50V...

Страница 26: ...trical Controls and Wiring Inspect and check the electrical controls and wiring annually Be sure to turn off the electrical power to the unit Remove access panels see Fig 22 to locate all the electric...

Страница 27: ...gerant System This step covers the refrigerant system of the 50VT A including the compressor oil needed servicing systems on roofs containing synthetic materials the filter drier and refrigerant charg...

Страница 28: ...ch must be removed remove and recover all system charge so that pressure gauges read 0 psig Never open system without breaking vacuum with dry nitrogen Check Defrost Thermostat The defrost thermostat...

Страница 29: ...ils S Vacuum pumps will not remove moisture from oil S Do not use liquid line filter driers with rated working pressures less than 600 psig S Do not leave Puron suction line filter driers in line long...

Страница 30: ...efective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace thermostat Faulty condenser fan motor or capacitor Replace Restriction in refrigerant syst...

Страница 31: ...D IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE COMPRESSOR AMPS INDOOR EVA...

Страница 32: ...S 7310 W Morris St S Indianapolis IN 46231 Edition Date 01 11 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 50VT 0...