background image

20

HIGH

LOW

COM

QC5

QC4

QC3

KZ

KL

07

09

08

0L0

ALO

R13 C8

R11

Q1

Q3

D2

AL2

DCR

QCR

QC1

C

RL

01

G1

G2

Z1

A7

R9

AB A15

C4

C9

C0

QIL

Z2

06

04

U1

C3

R4

RL4

JWZ

C7

D5

D3

R3 R5

R6

R2

JW5

QCB

Y

R

W2 Y

C

W3 W3 W2 W2 C

JW4

P2

JW3

P4

P1

W2

W3

Y2

Y1

Y

DH

G

C

R

SSTZ-8

P3

SDL

24V

A

C/R

3AMP

CDM/C

F1

STD

DEHUM

A09059

Fig. 16 -- Interface Fan Board (IFB)

COMPRESSOR

ACCUMULATOR

OUTDOOR COIL

INDOOR COIL

LCS

LEGEND

HPS – High Pressure Switch

LCS – Loss of Charge Switch

Accurater

 ®

 Metering De vice

Arrow indicates direction of flo

  w

   Position

HP S

TXV in Bypass

Metering 
Position

C03012

Fig. 17 -- Typical Heat Pump Operation, Heating Mode

Step 3 — Defrost Control

Quiet Shift

Quiet Shift is a field--selectable defrost mode, which will eliminate

occasional noise that could be heard at the start of defrost cycle and
restarting of heating cycle. It is selected by placing DIP switch 3

(on defrost board) in ON position.
When Quiet Shift switch is placed in ON position, and a defrost is

initiated, the following sequence of operation will occur. Reversing
valve will energize, outdoor fan will turn off, compressor will turn

off for 30 sec and then turn back on to complete defrost. At the

start of heating after conclusion of defrost reversing valve will
de--energize, compressor will turn off for another 30 sec, and the

outdoor fan will stay off for 40 sec, before starting in the Heating
mode.

Defrost

The defrost control is a time/temperature control which includes a

field--selectable time period (DIP switch 1 and 2 on the board)
between defrost cycles of 30, 60, 90, or 120 minutes (factory set at

60 minutes). To initiate a forced defrost, two options are available

depending on the status of the defrost thermostat.

If defrost thermostat is closed, speed--up pins (J1) must be shorted
by placing a flat head screw driver in between for 5 sec and

releasing, to observe a complete defrost cycle. When the Quiet
Shift switch is selected, compressor will be turned off for two 30

sec intervals during this complete defrost cycle, as explained

previously. When Quiet Shift switch is in factory default OFF
position, a normal and complete defrost cycle will be observed.
If defrost thermostat is in open position, and speedup pins are
shorted (with a flat head screw driver) for 5 sec and released, a

short defrost cycle will be observed (actual length is dependent

upon the selected Quiet Shift position). When Quiet Shift switch is
in ON position, the length of defrost is 1 minute (30 sec

compressor off period followed by 30 sec of defrost with
compressor operation). On return to heating operation, compressor

will again turn off for an additional 30 sec and the outdoor fan for

40 sec. When the Quiet Shift is in OFF position, only a brief 30
sec. cycle will be observed.

NOTE

:

Unit will remain in defrost until defrost thermostat

reopens at approximately 65

_

F (18

_

C) coil temperature at liquid

line or remainder of defrost cycle time.

50V

T

--

A

Содержание COMFORT 50VT-A

Страница 1: ...ndensate Drain Pan 26 Outdoor Fan 26 Electrical Controls and Wiring 26 Refrigerant Circuit 26 Indoor Airflow 26 Metering Devices TXV Piston 26 Pressure Switches 27 Loss of Charge Switch 27 High Pressu...

Страница 2: ...tructions shipped with curb See Fig 4 Install insulation cant strips roofing and flashing Ductwork must be attached to curb IMPORTANT The gasketing of the unit to the roof curb is critical for a water...

Страница 3: ...3 A09410 Fig 2 50VT A24 30 Unit Dimensions 50VT A...

Страница 4: ...4 A09411 Fig 3 50VT A36 60 Unit Dimensions 50VT A...

Страница 5: ...mm B small common base IN mm B large base IN mm C IN mm D IN mm E IN mm F IN mm G IN mm H IN mm Small or Large CPRFCURB010A00 11 279 10 254 14 356 16 406 47 8 1214 32 4 822 2 7 69 30 6 778 46 1 1170 C...

Страница 6: ...adapt to various sizes or kinds of loads 2 Instruction in any special operation or precaution 3 Condition of the load as it relates to operation of the lifting kit such as balance temperature etc Foll...

Страница 7: ...commended 4 Seal insulate and weatherproof all external ductwork Seal insulate and cover with a vapor barrier all ductwork passing through conditioned spaces Follow latest Sheet Metal and Air Conditio...

Страница 8: ...be using a minimum of field supplied 3 4 in PVC or field supplied 3 4 in copper pipe at outlet end of the 2 in 51 mm trap See Fig 9 Do not undersize the tube Pitch the drain tube downward at a slope o...

Страница 9: ...o that they do not interfere with operation of unit A gray wire is standard on 3 phase units for connection to an economizer If an accessory electric heater is installed low voltage leads from heater...

Страница 10: ...1000 10 x 10 254 x 254 1 2 1200 11 x 10 279 x 254 3 4 1400 11 x 10 279 x 254 3 4 1600 11 x 10 279 x 254 1 1750 11 x 10 279 x 254 1 High Pressure Switch psig Cutout Reset Auto 650 15 420 25 Loss of Cha...

Страница 11: ...11 A11002 Fig 12 Connection Wiring Schematics 208 230 1 60 50VT A...

Страница 12: ...12 A11001 Fig 12 Cont Ladder Wiring Schematics 208 230 1 60 50VT A...

Страница 13: ...13 A11006 Fig 13 Connection Wiring Schematics 208 230 3 60 50VT A...

Страница 14: ...14 A11005 Fig 13 Cont Ladder Wiring Schematics 208 230 3 60 50VT A...

Страница 15: ...15 A10195 Fig 14 Connection Wiring Diagram 460 3 60 50VT A...

Страница 16: ...16 A10195 Fig 14 Cont Ladder Wiring Diagram 460 3 60 50VT A...

Страница 17: ...P Checking Cooling and Heating Control Operation Start and check the unit for proper control operation as follows 1 Place room thermostat SYSTEM switch or MODE control in OFF position Observe that blo...

Страница 18: ...uctions and adjusted properly ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Disconnect electrical power to the unit and install lockout tag before cha...

Страница 19: ...ressure 3 Select speed tap from Table 4 that will achieve required airflow from Table 2 4 Remove the vinyl cap off of the desired speed tap wire Refer to Table 3 for color coding 5 Connect the desired...

Страница 20: ...he Heating mode Defrost The defrost control is a time temperature control which includes a field selectable time period DIP switch 1 and 2 on the board between defrost cycles of 30 60 90 or 120 minute...

Страница 21: ...ack cfm 2461 2409 2339 2286 2192 2140 2062 1968 1874 50VT A60 Low Blue cfm 1445 1389 1341 1281 1236 1189 1139 1072 1027 Med Low Pink cfm 1678 1635 1602 1558 1513 1474 1438 1404 1349 Medium 1 Red cfm 1...

Страница 22: ...0 10 0 12 0 13 0 15 0 17 0 18 0 20 0 23 Table 9 Electric Heat Pressure Drop Table in W C Small Cabinet 24 36 STATIC STANDARD CFM SCFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 5kw 0 00 0...

Страница 23: ...air filter s at least once each month and replace throwaway type or clean cleanable type at least twice during each cooling season and twice during the heating season or whenever the filter becomes cl...

Страница 24: ...24 A09412 Fig 18 Cooling Charging Table Subcooling 50VT A...

Страница 25: ...OF2 OF1 ON QUIET SHIFT 120 30 60 60 30 90 INTERVAL TIMER OFF P3 DFT O R W 2 Y C T2 C C O DFT T1 Y P1 J1 SPEEDUP Speedup Pins Defrost interval DIP switches Quiet Shift A08020 Fig 19 Defrost Control 50V...

Страница 26: ...trical Controls and Wiring Inspect and check the electrical controls and wiring annually Be sure to turn off the electrical power to the unit Remove access panels see Fig 22 to locate all the electric...

Страница 27: ...gerant System This step covers the refrigerant system of the 50VT A including the compressor oil needed servicing systems on roofs containing synthetic materials the filter drier and refrigerant charg...

Страница 28: ...ch must be removed remove and recover all system charge so that pressure gauges read 0 psig Never open system without breaking vacuum with dry nitrogen Check Defrost Thermostat The defrost thermostat...

Страница 29: ...ils S Vacuum pumps will not remove moisture from oil S Do not use liquid line filter driers with rated working pressures less than 600 psig S Do not leave Puron suction line filter driers in line long...

Страница 30: ...efective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace thermostat Faulty condenser fan motor or capacitor Replace Restriction in refrigerant syst...

Страница 31: ...D IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE COMPRESSOR AMPS INDOOR EVA...

Страница 32: ...S 7310 W Morris St S Indianapolis IN 46231 Edition Date 01 11 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 50VT 0...

Отзывы: