hank you for choosing our refrigerating unit. This model is equipped with a highly evolved electronic control panel that dispenses with a series
of conventional components such as timers, thermostats and thermometers while offering the facility for straightforward personalisation of the

control program to suit your needs. The panel also provides a self-diagnostic function showing the nature of any functional anomalies so that
they can be solved fast. This operation and programming manual has been published to assist you, please read it carefully.

1) OPERATION

The distinguishing feature of this unit is that it is formed of two separate parts: the condensing unit with remote electronic control panel, for instal-

lation outside the coldroom , and the evaporator for installation inside the room. This design solution eliminates problems related to space
restrictions outside the cell. The two units can be installed at a distance from each other. The air is drawn through the evaporator by means of
the motor driven fan and exhausted through the grids on the sides. In the evaporator, the air drawn in by the motor driven fan units is cooled
by the heat exchanger and expelled from the front of the unit. The temperature is monitored by room sensor. Once the set-point is reached the
refrigeration plant is stopped. Defrosting is automatic by means of electrical heaters in the evaporator; this cycle terminates in correspondence
with the "defrost end" temperature set on the control unit and detected by a sensor. The defrost water is collected in a tray located beneath
the evaporator from where it is drained to outside the rooml.

2) INSTALLATION

For correct installation, proceed thus:

1)

Position the condenser unit on floor level outside the coldroom.

2)

Secure the evaporator unit to the coldroom ceiling (pict. 1) as follows:

2A) Open the fan holder bottom 

‘A’

by

loosing screws 

‘B’

(pict. 2-3).

2B) Drill the fixing holes on the 

coldroom ceiling observing the
recommended distance from the
wall (pict.  4).

2C) Secure the evaporator using the

supplied components (pict. 5):

1 - Threaded bar
2 - Washer
3 - Nut

2D) Hook up the evaporator to the electrical supply utilising the terminal board located inside

the junction box. Close the junction box and clamp the cable so that it is clear of the fan
blades.

2E) Re-close the air-cooler cover and then make the refrigeration connections (pict. 6).

REMOTE CONTROL PANEL INSTALLATION

Unscrew the lateral fixings to remove the remote control panel cover plate (pict.  7).

Fix the base plate in the desired position using the pre-drilled

holes and making sure it is level (pict.  8).

Replace the cover plate by performing the operation indicated at

pict. 7  in reverse.

Adjust the cable connection between the control panel and the

unit, making sure it does not interfere with existing cable 
connections.

To assure optimal operation of the refrigerating unit:

A) Restrict the number of times the coldroom is opened.
B) Make sure that the unit has an efficient air intake and expels a generous amount of turbulent air.
C) Position the unit on horizontal planes..
D) Avoid to place the condensing unit in closed ambient or not ventilated.

4

A

B

100-150

1

3

2

1

2

pict. 3

pict. 2

pict. 4

pict. 5

pict. 6

Condensing unit

Evaporator

pict. 1

pict. 7

pict. 8

E

N

G

L

I

S

H

Содержание BDB121NO170F

Страница 1: ...USE AND MAINTENANCE BEDIENUNGSANLEITUNG INSTRUCTIONS D USAGE ET ENTRETIEN USO E MANUTENZIONE DB O DB O ...

Страница 2: ...F 30 0 1162 5 8 0 5 230 1 50 0 7 4 3 7 9 R404A 600 4 43 13 12 6 BDB121NO170F 30 20 761 1 0 7 230 1 50 0 8 4 8 7 6 R404A 600 4 43 13 12 6 BDB121TO170F 30 20 965 1 2 0 9 230 1 50 0 8 5 0 7 5 R404A 600 4 46 13 12 6 MDB123TO170F 30 0 1332 3 4 0 6 230 1 50 0 8 5 0 8 4 R404A 600 4 43 13 12 6 BDB123TO170F 30 20 1096 1 7 1 3 230 1 50 0 9 5 5 11 3 R404A 600 4 50 13 12 6 MDB221TO170F 30 0 2243 1 2 0 9 400 3...

Страница 3: ... SHEET SERVICEBLATT FICHE DE SERVICE FOGLIO SERVIZIO DATE DATUM OPERATION MASSNAHME SERVICE FIRM SERVICEFIRMA SIGNATURE UNTERSCHRIFT DATE DATA OPERATION OPERAZIONE ETS DE SERVICE DITTA ASSISTENZA SIGNATURE FIRMA ...

Страница 4: ...water is collected in a tray located beneath the evaporator from where it is drained to outside the rooml 2 INSTALLATION For correct installation proceed thus 1 Position the condenser unit on floor level outside the coldroom 2 Secure the evaporator unit to the coldroom ceiling pict 1 as follows 2A Open the fan holder bottom A by loosing screws B pict 2 3 2B Drill the fixing holes on the coldroom c...

Страница 5: ...ire earth to the earth terminal 60 GND Tighten the cable gland Remeber that the voltage in output to the card is 230 V 1Amp MAX It is necessary to protect the door heater with a fuse by costumer MICRO DOOR CONNECTION Remove the plug F pict 2 and insert a cable gland PG 11 Insert the cable deriving from the micro door and connect the bands to the terminals 19 and 20 of the electronic control panel ...

Страница 6: ...eady for program ming It is necessary therefore to set the required room temperature bearing in mind the limits of the range which the unit is able to operate Press the SET 6 key the yellow LED will light The last set temperature will be displayed on the display screen 5 which showes the set value Press the set key 6 the yellow led will light for one second and the display 5 will start flashing a ...

Страница 7: ...s terminals E3 and E4 Pict 2 5 A wire comes out from nr 30 on the card it is welded in the card an connented to terminal 4 Disconnect it and let it free 6 Enter the thermostat bulb inside room 7 Adjust the stat at the required temperature and switch the unit on 8 When the set temperature is reached compressor evaporator and condenser fans will stop 9 During emergency period defrost cycle is cut ou...

Страница 8: ...n G Ga as s V Vo ollt ta ag ge e A Am mp pe er re e n nº º A Am mp pe er re e m mm m2 2 M MO OD DE EL LL LO O G Ga am mm ma a V Ve er rs siio on ne e T Te en ns siio on ne e 20 POWER CURRENT FUSE We advise the use of such a fuse circuit breaker fitted in the line otherwise a suitable fused isolator can be used LEISTUNGSSICHERUNG Man raet die Verwendung solcher Schmelzsicherung auf der Linie eingeb...

Страница 9: ... associato al parametro 2C Modify the value pressing 8 and 9 until you reach the required one Um den wert zu änderu 8 und 9 bis zum gew wert drücken Modifier la valeur en pressant ensamble 8 et 9 jusqu on rejoint la valeur désiderée Modificare il valore agendo con i tasti 8 e 9 fino al raggiungimento di quello voluto 2D Press the key 6 to confirm temporarily the new value and return to the display...

Страница 10: ...BRINAMENTO all accensione dello strumento 1 si 0 no d5 DEFROST DELAY AFTER RESET OR EXTERNAL TRIGGER VERZÖGERUNG ABTAUEN VON EINSCHALTEN INSTRUMENT DURCH MULTIFUNCTION EIN GANG RETARD DEGIVRAGE APRES ALLUMAGE DE L INSTRUMENT PAR ENTREE MULTIFONCTIONS RITARDO SBRINAMENTO dall accensione stru mento da ingr multifunction d6 DISPLAY LOCK DURING DEFROST 1 yes 0 no SPERRUNG ANZEIGE WÄHREND ABTAUEN 1 ja ...

Страница 11: ...20 20 20 20 F F2 2 flag 0 1 0 0 0 0 F F3 3 flag 0 1 1 1 1 1 F Fd d min 0 15 1 1 1 1 H H0 0 0 15 0 0 0 0 H H1 1 flag 0 1 0 0 0 0 P PO O flag 0 15 10 10 10 10 P P1 1 min 0 199 60 60 60 60 T3 T4 T1 T2 C CO OD DE E C CO OD DE E C CO OD DE E C CO OD DIIC CE E MANUFACTURED STANDARDS HERSTELLERSTANDARD STANDARDS CONSTRUCTEUR STANDARD COSTRUTTORE Unit of measure Operating Field Arbitsbereich Electric defr...

Страница 12: ...6 31 41 9 8 15 24 1 67 33 9 11 17 72 41 50 75 62 70 30 35 27 69 68 18 16 77 40 13 32 55 2 11 67 64 14 52 65 29 38 74 46 61 60 9 8 47 19 44 7 28 73 5 4 45 6 49 20 54 53 21 12 25 23 22 39 36 34 43 80 78 79 1 DB121 123 18 05 99 Arfini Tav n Modello Data Disegnatore ...

Страница 13: ...R191 1 1 1 1 1 1 39 HANDLE HANDGRIFF POIGNÉE MANIGLIA 3MNG009 1 1 1 1 1 1 40 LEFT HAND SIDE LINKE SEITENWAND FLANC GAUCHE FIANCO SINISTRO 2225072 1 1 1 1 1 1 41 REINFORCEMENT VERSTÄRKUNG RENFORCEMENT RINFORZO 2009093 2 2 2 2 2 2 42 SIGHT GLASS SCHAUGLAS VOYANT LIQUIDE INDICATORE 3INU019 1 1 1 1 1 1 43 TERMINAL KLEMME BORNE MORSETTO 3MRS004 1 1 1 1 1 1 44 NUT MUTTER ECROU DADO 3DDO043 2 2 2 2 2 2 4...

Страница 14: ...30 18 35 32 31 55 38 15 24 51 52 1 65 41 67 40 72 26 63 68 77 9 3 70 58 33 69 64 67 27 48 76 8 16 9 50 56 19 9 17 37 11 46 4 8 9 6 60 7 28 47 44 78 73 61 49 54 74 20 53 45 5 23 25 21 22 39 43 36 34 81 79 80 2 DB 221 18 05 99 Arfini Tav n Modello Data Disegnatore ...

Страница 15: ...LLONGE PROLUNGA 3PRL009 1 1 1 37 TERMINAL KLEMME BORNE MORSETTO 3MOR010 8 8 8 38 CONTACTOR FERNSCHALTER TELERUPTEUR TELERUTTORE 3TLR191 1 1 1 39 HANDLE HANDGRIFF POIGNÉE MANIGLIA 3MNG009 1 1 1 40 LEFT HAND SIDE LINKE SEITENWAND FLANC GAUCHE FIANCO SINISTRO 2225072 1 1 1 41 REINFORCEMENT VERSTÄRKUNG RENFORCEMENT RINFORZO 2009093 2 2 2 42 SIGHT GLASS SCHAUGLAS VOYANT LIQUIDE INDICATORE 3INU006 1 1 1...

Страница 16: ...6 13 14 76 65 67 46 29 20 45 10 38 14 3 63 31 15 52 68 77 40 33 47 22 21 19 2 32 73 4 72 9 49 33 25 69 41 9 8 16 26 28 42 23 27 61 9 11 37 17 11 24 1 51 41 30 35 59 67 58 57 75 43 36 34 78 80 79 56 50 3 DB 135 18 05 99 Arfini Tav n Modello Data Disegnatore ...

Страница 17: ...OR FERNSCHALTER TELERUPTEUR TELERUTTORE 3TLR191 1 1 1 1 39 HANDLE HANDGRIFF POIGNÉE MANIGLIA 3MNG009 1 1 1 1 40 LEFT HAND SIDE LINKE SEITENWAND FLANC GAUCHE FIANCO SINISTRO 2135203 1 1 1 1 41 REINFORCEMENT VERSTÄRKUNG RENFORCEMENT RINFORZO 2009093 2 2 2 2 42 SIGHT GLASS SCHAUGLAS VOYANT LIQUIDE INDICATORE 3INU006 1 1 1 1 43 TERMINAL KLEMME BORNE MORSETTO 3MRS004 1 1 1 1 44 NUT MUTTER ECROU DADO 3D...

Страница 18: ... SOLENOIDE SOLENOIDE 10 EXPANSION VALVE EXPANSIONVENTIL DETENDEUR THERMOSTATIQUE TERMOSTATICA 11 EVAPORATOR MOTOR DRIVEN FAN VERDAMPFER MOTORVENTILATOR MOTOVENTILATEUR EVAPORATEUR MOTOVENTIL EVAPORATORE 12 EVAPORATOR VERDAMPFER EVAPORATEUR EVAPORATORE 13 DEFROST HEATER ABTAUHEIZUNG RESISTANCE DEGIVRAGE RESISTENZA SBRINAMENTO 14 DEFROST DRAIN LINE ABTAUWASSERABFLUSS ECOULEMENT EAU DEGIVRAGE SCARICO...

Страница 19: ...N NO OT TE E N NO OT TE ES S 31 ...

Страница 20: ...0MAN043 C del 04 2001 ...

Отзывы: