background image

GB - 14

30RHV

Troubleshooting and guide for the owner

Troubleshooting

Unit compressor and fan will not start:
• Unit not energized; check the mains power connections.
• Mains switch OFF; check and put in the ON position.
• Main switch fuses have blown; replace.
• Wait for 2 minutes; compressor cycling protection is on.
• Pressure switch open; check and eliminate cause.
• Mains voltage too low.
• Electrical connections loose or wrong; check and repair.

Compressor will not start, but unit fan is running:
• Electrical connections of compressor loose or wrong; check and

repair.

• Compressor burnt out, seized or protection device open; check

for the cause and replace compressor if necessary.

• Run capacitor faulty (single-phase models); replace.

Compressor starts, but stops due to its overtemperature
protection (other than stops caused by the normal operation
of the thermostat):
• Wrong refrigerant charge (excessive or low) or air or other non-

condensable gases in the circuit; drain refrigerant (see note 1),
evacuate and recharge.

• Mains voltage wrong (too high or too low).
• Condenser coil obstructed; remove obstructions.
• Fan off; check cause and repair.
• Run capacitor faulty; check and replace.
• Indoor unit thermostat faulty; replace.
• Refrigerant circuit clogged; check and remove obstructions.
• Reversing valve faulty in heat pump models; replace.
• Expansion device clogged or covered with ice; drain refrigerant

(see note 1), evacuate and recharge.

Compressor runs continuously:
• Unit selected too small for actual air conditioning needs.
• Water temperature selection too low (if in cooling) or too high (if

in heating, for heat pump models); check temperature selection.

• Refrigerant charge low; check and add refrigerant.
• Outdoor unit fan faulty; replace.
• Air or other non-condensable gases in the circuit; drain

refrigerant (see note 1), evacuate and recharge.

• Obstruction in the air intake or dirty indoor unit filters; remove

obstruction or clean filter.

Frequent ice build-up on coil (during heating with heat pump
units):
• Fan stopped; check cause and repair.
• Wrong electrical connections on defrost circuit; check electrical

connections and repair.

Discharge pressure too high:
• Coil dirty or obstructed; clean or remove obstructions.
• Water flow rate is insufficient or the pump is faulty (during

heating); replace.

• Refrigerant charge too high; drain some refrigerant (see note 1).
• Air or other non-condensable gases in the circuit; drain

refrigerant (see note 1), evacuate and recharge.

Discharge pressure too low:
• Refrigerant charge too low; add refrigerant.
• Coil dirty or obstructed; clean or remove obstructions.
• Water filter dirty; clean filter.

Suction pressure too high:
• Internal high pressure relief valve open; check for cause and

repair.

• Refrigerant charge too high; drain some refrigerant (see note 1).
• Reversing valve (on heat pump models) faulty or internal leak;

replace.

Suction pressure too low:
• Refrigerant charge too low; add refrigerant.
• Evaporator coil (indoor or outdoor in case of heat pump models)

covered with ice; see the following points.

• Air circulation on the evaporator unit not sufficient; check for the

cause and repair.

• Expansion device or suction line clogged: check and repair.

• Fan does not stop during defrost periods (when heating with heat

pump models); check electrical connections.

• Defective defrost probe (heating with heat pump models);

replace.

• Contact between tube and defrost probe (heating with heat pump

models) faulty; check and repair.

Fan cycling due to its overtemperature protection:
• Fan capacitor faulty; replace.
• Electrical connections loose; check connections.
• Fan bearing seized; check and repair.
• Expansion device clogged or covered with ice; drain refrigerant

(see note 1), evacuate and recharge.

Note 1:
Do not release refrigerant to the atmosphere; use
refrigerant recovery equipment.

Guide for the owner

When installation and tests are completed explain the Operation
and Maintenance Manual to the owner, with particular attention to
the main operating modes of the air conditioner, such as:

• Turning the unit on and off.

• Control functions.

In the event of a fault or malfunctioning, check the error code
shown on the remote control or at the LED on the board in the
chiller control panel.

Содержание AQUASNAP JUNIOR 30RHV

Страница 1: ...AQUASNAP JUNIOR 30RHV INSTALLATION MANUAL L L O Y D S R E G I S TER QUALIT Y A S S U R A N C E IS O 900 1...

Страница 2: ...e with R 410A R 410A refrigerant cylinders are pink in colour R 410A refrigerant cylinders have a dip tube which allows liquid to flow out of the cylinder in upright position The R 410A units must be...

Страница 3: ...E D B C F A E E D B C F A G H G H Mod 30RHV 006 008 Mod 30RHV011 Mod 30RHV 006 008 011 A mm 800 800 800 B mm 803 803 1264 C mm 300 300 300 D mm 508 508 508 E mm 146 146 146 F mm 330 330 330 G mm 97 9...

Страница 4: ...rotection Compressor Capacitor F V 40 450 50 450 60 450 Fan motor 230 1 50 Current input A 0 82 1 1 1 64 1 64 Capacitor F V 4 450 3 450 4 450 4 450 Compressor crankcase heater 230 1 50 W 25 25 25 25 C...

Страница 5: ...ble V Refer to the following example for the buffes tank open closed Refrigerant circuit high pressure switch kPa 4206 2996 Freeze up protection C 2 7 Compressor first start delay sec 60 Compressor st...

Страница 6: ...and explain all chiller functions to the owner Leave this manual with the owner for consultation during future periodic maintenance The chiller and its components must be periodically inspected to ch...

Страница 7: ...ruction of the unit air outlet and intake or any obstacle that is too close see minimum clearances required Installation on grassy ground or soft surfaces in these cases a solid foundation must be inc...

Страница 8: ...ust be located at the highest point of the circuit Pressure drop Pressure drop kPa Water flow rate l h Pressure drop kPa Water flow rate l h Pressure drop kPa Water flow rate l h Legend DP KPa 12 C DP...

Страница 9: ...iary circuit supply is directly taken from one phase and neutral and it is proteced by fuse F If the electrical supply cables L1 R L2 S L3 T are connected in an incorrect sequence the power supply is...

Страница 10: ...pply N Neutral power supply S1 ON OFF switch S2 HEAT COOL switch NOTE The contact rating must be greater than 20 mA 24 V ac G L N 0 24 5 6 1 2 3 4 S1 S2 Unit electrical panel Terminal blocks Electroni...

Страница 11: ...HEAT COOL switch NOTE The contact rating must be greater than 20 mA 24 V ac G L1 L2 L3 N 0 24 5 6 1 2 3 4 S1 S2 Unit electrical panel Terminal blocks Electronic board connectors Power supply 400V 3ph...

Страница 12: ...r outlet 11 Reversing valve Refrigerant R 410A Gas Liquid Gas Liquid The unit includes a brazed plate water refrigerant heat exchanger The heat exchanger operates as an evaporator in the summer cycle...

Страница 13: ...control setpoint This parameter is regulated by the control and factory set to an entering water temperature of 12 C The second set point default value is 14 C and it can be selected via the Service...

Страница 14: ...ducer wire interrupted or transducer fault 13 Low refrigerant pressure Unit stopped Automatic Lack of refrigerant in the circuit blocked in the circuit Manual refrigerant filter or low pressure transd...

Страница 15: ...stopped check cause and repair Wrong electrical connections on defrost circuit check electrical connections and repair Discharge pressure too high Coil dirty or obstructed clean or remove obstructions...

Страница 16: ...H28 1005 Via R Sanzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice October 2005 Supersedes January 2005 Printed in...

Отзывы: