30RHV
E N G L I S H
Minimum clearances
F
A
B
A
C
D
E
F
D
E
Unit
30RHV
006
008
011
Power supply
V - ph - Hz
230-1-50
230-1-50
230-1-50
400-3-50
Locked rotor amps
LRA
58
82
97
48
Full load amps FLA 16 19 23 10
Delayed fuses (class gL)
A
20
25
30
12
power supply protection
Section of the power
mm
2
3 x 2,5 3 x 4,0 3 x 4,0 5 x 2,5
supply conductors
Delayed fuses (class gL)
A
4
4
4
4
auxiliary circuit protection
Compressor
Capacitor
µ
F/V
40/450
50/450
60/450
–
Fan motor (230-1-50)
Current input
A
0,82
1,1
1,64
1,64
Capacitor
µ
F/V
4/450
3/450
4/450
4/450
Compressor crankcase
heater (230-1-50)
W
25
25
25
25
Current input
A
0.11
0.11
0.11
0.11
Note:
The main supply connecting cable must be H07 RN-F (or
higher) type, synthetic rubber insulation with Neoprene
coating, according to EN 60335-1 codes.
Interlocks with the pumps or other accessories have to be
inserted as shown in the notes on the wiring diagram.
Table III: Electrical data
Mod.
30RHV 006 - 008 - 011
A
mm
100
B
mm
250
C
mm
500
D
mm
100
E
mm
670
F
mm
400