background image

GB - 13

30RHV

E N G L I S H

Diagnostics

The electronic control on the machine continuously monitors its
operation. In the event of a malfunction, it activates a relay whose
contact generates a coded alarm signal. Some alarm conditions are
automatically reset, others require the intervention of the operator to
search for the fault, remove its cause and switch the unit back on.

Manual resetting of alarm conditions
Manual resetting of alarm conditions is performed using the
remote ON/OFF button by simply switching OFF and then ON again
or opening and closing S1 switch (see electrical connections).

WARNING:
manual resetting causes the definitive loss of the alarm code;
therefore, before a manual reset, check the code according to the
instruction reported and remove its cause.

N.B.
Temporary power supply failure to a unit in an alarm condition does
not reset the unit.

Alarm

Description

Control

Alarm reset

Probable cause

code

action

method

1

Compressor fault

Compressor stopped Manual

Compressor overheated

2

Leaving water temperature

Unit stopped

Automatic

Sensor out of range, probe wire interruption

probe fault

or sensor fault

3

Entering water temperature

Unit stopped

Automatic

Sensor out of range, probe wire interruption

probe fault

or sensor fault

4

Defrost probe fault

Unit stopped

Automatic

Sensor out of range, probe wire interruption
or sensor fault

5

Air temperature probe fault

Unit stopped

Automatic

Sensor out of range, probe wire interruption
or sensor fault

6

High pressure transducer fault

Unit stopped

Automatic

Transducer out of range, incorrect transducer voltage
transducer wire interrupted or transducer fault

11

Low pressure transducer fault

Unit stopped

Automatic

Transducer out of range, incorrect transducer voltage
transducer wire interrupted or transducer fault

13

Low refrigerant pressure

Unit stopped

Automatic/

Lack of refrigerant in the circuit, blocked

in the circuit

Manual

refrigerant filter or low pressure transducer fault

14

High refrigerant pressure

Unit stopped

Manual

Fan fault, coil obstructed, high outdoor

in the circuit

air temperature

15

High pressure safety switch /

The safety pressure switch has not been reset after

reverse compressor rotation

Unit stopped

Manual

the last alarm, incorrect compressor connection

16

Plate exchanger

Unit stopped

Automatic/

Low water flow rate entering or leaving

anti-freeze protection

Manual

water probe fault

Repeated attainment of low

Low pressure transducer fault,

21

suction temperature in cooling

Unit stopped

Automatic

refrigerant filter blocked

(more than six times)

or lack of refrigerant in the circuit

22

Repeated attainment of high

High pressure transducer fault

pressure condition in cooling

Unit stopped

Automatic

high air temperature,

(more than six times)

high entering water temperature

23

Repeated attainment of high

Unit stopped

Automatic

Low water flow rate entering or leaving

discharge temperature in heating

water probe fault

24

Repeated attainment of low

Unit stopped

Automatic

Low pressure transducer fault, refrigerant filter

suction temperature in heating

blocked or lack of refrigerant in the circuit

25

Low entering water

Unit stopped

Automatic

Entering water temperature too low,

temperature in heating

entering or leaving water probe fault

26

Outdoor interblock fault

Unit stopped

Manual

Flowswitch tripped or fault, air in the water circuit

31

CCN emergency shut-down

Unit stopped

Automatic

Network control

32

Loss of communication with the The unit operates

Automatic

CCN bus wiring defect or

Flotronic or Chiller System Manager

in local mode

fault in the system

33

Maintenance service request

Unit stopped

Manual

The following list describes the possible cause for each alarm code:

Содержание AQUASNAP JUNIOR 30RHV

Страница 1: ...AQUASNAP JUNIOR 30RHV INSTALLATION MANUAL L L O Y D S R E G I S TER QUALIT Y A S S U R A N C E IS O 900 1...

Страница 2: ...e with R 410A R 410A refrigerant cylinders are pink in colour R 410A refrigerant cylinders have a dip tube which allows liquid to flow out of the cylinder in upright position The R 410A units must be...

Страница 3: ...E D B C F A E E D B C F A G H G H Mod 30RHV 006 008 Mod 30RHV011 Mod 30RHV 006 008 011 A mm 800 800 800 B mm 803 803 1264 C mm 300 300 300 D mm 508 508 508 E mm 146 146 146 F mm 330 330 330 G mm 97 9...

Страница 4: ...rotection Compressor Capacitor F V 40 450 50 450 60 450 Fan motor 230 1 50 Current input A 0 82 1 1 1 64 1 64 Capacitor F V 4 450 3 450 4 450 4 450 Compressor crankcase heater 230 1 50 W 25 25 25 25 C...

Страница 5: ...ble V Refer to the following example for the buffes tank open closed Refrigerant circuit high pressure switch kPa 4206 2996 Freeze up protection C 2 7 Compressor first start delay sec 60 Compressor st...

Страница 6: ...and explain all chiller functions to the owner Leave this manual with the owner for consultation during future periodic maintenance The chiller and its components must be periodically inspected to ch...

Страница 7: ...ruction of the unit air outlet and intake or any obstacle that is too close see minimum clearances required Installation on grassy ground or soft surfaces in these cases a solid foundation must be inc...

Страница 8: ...ust be located at the highest point of the circuit Pressure drop Pressure drop kPa Water flow rate l h Pressure drop kPa Water flow rate l h Pressure drop kPa Water flow rate l h Legend DP KPa 12 C DP...

Страница 9: ...iary circuit supply is directly taken from one phase and neutral and it is proteced by fuse F If the electrical supply cables L1 R L2 S L3 T are connected in an incorrect sequence the power supply is...

Страница 10: ...pply N Neutral power supply S1 ON OFF switch S2 HEAT COOL switch NOTE The contact rating must be greater than 20 mA 24 V ac G L N 0 24 5 6 1 2 3 4 S1 S2 Unit electrical panel Terminal blocks Electroni...

Страница 11: ...HEAT COOL switch NOTE The contact rating must be greater than 20 mA 24 V ac G L1 L2 L3 N 0 24 5 6 1 2 3 4 S1 S2 Unit electrical panel Terminal blocks Electronic board connectors Power supply 400V 3ph...

Страница 12: ...r outlet 11 Reversing valve Refrigerant R 410A Gas Liquid Gas Liquid The unit includes a brazed plate water refrigerant heat exchanger The heat exchanger operates as an evaporator in the summer cycle...

Страница 13: ...control setpoint This parameter is regulated by the control and factory set to an entering water temperature of 12 C The second set point default value is 14 C and it can be selected via the Service...

Страница 14: ...ducer wire interrupted or transducer fault 13 Low refrigerant pressure Unit stopped Automatic Lack of refrigerant in the circuit blocked in the circuit Manual refrigerant filter or low pressure transd...

Страница 15: ...stopped check cause and repair Wrong electrical connections on defrost circuit check electrical connections and repair Discharge pressure too high Coil dirty or obstructed clean or remove obstructions...

Страница 16: ...H28 1005 Via R Sanzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice October 2005 Supersedes January 2005 Printed in...

Отзывы: