6 - APPLICATION DATA
6.1 - Operating limits
6.1.1 - 61XWHLZE / 61XWH-ZE units
61XWHZ-E
Minimum
Maximum
Evaporator
Entering temperature at start-up
-
Up to 35,0°C
Leaving temperature during operation
3,3°C
(1)
Up to 25,0°C
Condenser
Entering temperature at start-up
13,0°C
(2)
-
Leaving temperature during operation
35,0°C
(2)
Up to 85,0°C
(3)
(1) Use of antifreeze protection is required if the leaving temperature is below 3.3°C
(61XWHLZE range).
(2) For lower condenser temperatures a water flow control valve must be used at
the condenser (two or three-way valve). Please refer to option 152 to ensure
the correct condensing temperature.
(3) Limited to 75°C for model 17
6.1.2 - 61XWHHZE units
Only models 3, 5, 7, 10, 15
61XWHHZE
Minimum
Maximum
Evaporator
Entering temperature at start-up
-
Up to 60,0°C
Leaving temperature during operation
20,0°C
Up to 55,0°C
Condenser
Entering temperature at start-up
13,0°C
(1)
-
Leaving temperature during operation
35,0°C
(1)
Up to 85°C
(1) For lower condenser temperatures a water flow control valve must be used at
the condenser (two or three-way valve). Please refer to option 152 to ensure
the correct condensing temperature.
Note: Ambient temperatures: Du
ring storage and transport
(including by container) the minimum and maximum
permissible temperatures are -20°C and 70°C.
6.2 -
Minimum chilled water flow
The minimum chilled water flow is shown in the table in chapter 7.6.
If the system flow is less than the minimum unit flow rate, the
evaporator flow can be recirculated, as shown in the diagram.
For minimum chiller flow rate
1
2
Legend
1 Evaporator
2 Recirculation
6.3 -
Maximum chilled water flow
The maximum chilled water flow is limited by the permitted
pressure drop in the evaporator. It is provided in the table in chapter
7.6.
Bypass the evaporator as shown in the diagram to obtain a lower
evaporator flow rate.
For maximum chiller flow rate
Legend
1 Evaporator
2 Recirculation
1
2
6.4 -
Condenser water flow rate
The minimum and maximum condenser water flow rates are shown
in the table in chapter 7.6.
6.5 -
Standard and optional number of water
passes
The unit is equipped of two passes on evaporator and on
condenser.
61XWH
Model
3
5
7
10
14
15
17
Evaporator
Standard unit
2
2
2
2
2
2
2
Unit with option 100A
3
3
3
3
3
3
3
Unit with option 100C
1
1
1
1
1
1
1
Condenser
Standard unit
2
2
2
2
2
2
2
Unit with option 102A
3
3
3
3
3
3
3
Unit with option 102C
1
1
1
1
1
1
1
6.6 -
Evaporator and condenser water flow rates
Units 61XWH
Model
3
5
7
10
14
15
17
Evaporator water flow rate, l/s
Minimum
4
6
8
11
13
13
13
Maximum
39
57
76
84
116
116
116
Condenser water flow rate, l/s
Minimum
4
6
8
12
18
14
14
Maximum
29
55
74
119
130 134 134
Notes :
-
Minimum evaporator flow rate based on a water velocity
of 0,3 m/s.
-
Minimum condenser flow rate based on a water velocity
of 0,3 m/s.
-
Maximum flow rate based on a pressure drop of 120 kPa.
-
These values are given for standard units. For options
100A, 100C, 102A and 102C, please refer to the unit
selection program.