20
5 - USER INTERFACE: MENU STRUCTURE
QCK_TST1 – Quick Test 1 (continued)
No. Name
Status
Default Unit Displayed text*
Description
29 Q_ALARM
off/on
-
-
Alarm Relay Status
Alarm relay status
30 Q_ALERT
off/on
-
-
Alert Relay Switch
Alert relay switch
31 Q_DEXV_A 0 to 100
0
%
DGT EXV Position A
DGT EXV position, circuit A (100% = EXV fully open)
32 Q_DEXV_B 0 to 100
0
%
DGT EXV Position B
DGT EXV position, circuit B (100% = EXV fully open)
33 Q_3W_VLV 0 to 100
-
%
3 way valve position
3-way valve position
*Depends on the selected language (English by default).
IMPORTANT: To enable the Quick Test functionality, the unit
must be stopped (Local off mode).
Trendings
No. Name
Status
Unit
Description
1
GENUNIT_CTRL_PNT
-
%
Control point
2
TEMP_COOL_EWT
-
°C/°F
Cooler entering fluid
3
TEMP_COOL_LWT
-
°C/°F
Cooler leaving fluid
4
TEMP_COND_EWT
-
°C/°F
Condenser entering fluid
5
TEMP_COND_LWT
-
°C/°F
Condenser leaving fluid
6
TEMP_SCT_A
-
°C/°F
Saturated condensing temperature, circuit A
7
TEMP_SST_A
-
°C/°F
Saturated suction temperature, circuit A
8
TEMP_SCT_B
-
°C/°F
Saturated condensing temperature, circuit B
9
TEMP_SST_B
-
°C/°F
Saturated suction temperature, circuit B
10 INPUTS_CURREN_A
-
AMPS
Motor current, circuit A
11 INPUTS_CURREN_B
-
AMPS
Motor current, circuit B
12 EXV_CTRL_EXV_A
-
%
EXV position, circuit A
13 EXV_CTRL_DSH_A
-
^C/^F
Discharge superheat, circuit A
14 EXV_CTRL_ov_exv_a
-
-
EXV override, circuit A
15 EXV_CTRL_EXV_B
-
%
EXV position, circuit B
16 EXV_CTRL_DSH_B
-
^C/^F
Discharge superheat, circuit B
17 EXV_CTRL_ov_exv_b
-
-
EXV override, circuit B
18 EXV_CTRL_eco_sha
-
^C/^F
Economizer superheat, circuit A
19 EXV_CTRL_ov_eco_a
-
-
EXV override, circuit A
20 EXV_CTRL_eco_shb
-
^C/^F
Economizer superheat, circuit B
21 EXV_CTRL_ov_eco_b
-
-
EXV override, circuit B
22
LOADFACT_cap_t_a
-
%
Actual capacity, circuit A
23
LOADFACT_cap_t_b
-
%
Actual capacity, circuit B
24
LOADFACT_smz
-
%
Load/unload factor
25
LOADFACT_over_cap
-
-
Active capacity override
*Depends on the selected language (English by default).
OPT_STA – Software Options
No. Name
Status
Unit Displayed text*
Description
1
opt5
no/yes
-
OPT5: Medium Brine
Not applicable to this unit
2
opt6
no/yes
-
OPT6: Low Brine
Not applicable to this unit
3
opt149
no/yes
-
OPT149: BACnet
Parameter set to “yes” means that BACnet option which requires the
Software Key is activated (see also section 6.19)
4
opt149B
no/yes
-
OPT149B: Modbus
Parameter set to “yes” means that Modbus option which requires the
Software Key is activated (see also section 6.20)
5
opt295
no/yes
-
OPT295: Fast Capacity Recovery
Not applicable to this unit
*Depends on the selected language (English by default).