SETPOINT – Setpoint Table (continued)
No. Name
Status
Default Unit Displayed text*
Description
6
hsp2
35.0 to 85.0
95.0 to 185.0
70.0
158.0
°C
°F
Heating Setpoint 2
Heating setpoint 2 (used during unoccupied periods)
7
hramp_sp
0.1 to 11.1
0.2 to 20.0
0.6
1.0
^C
^F
Heating Ramp Loading
Heating ramp loading setpoint (rate at which the water
temperature may change within one minute in Heating)
8
cauto_sp
3.9 to 50.0
39.0 to 122.0
23.9
75.0
°C
°F
Cool Changeover Setpt
Not applicable to this unit
9
hauto_sp
0 to 46.1
32.0 to 115.0
17.8
64.0
°C
°F
Heat Changeover Setpt
Not applicable to this unit
10 w_sct_sp
26.7 to 60.0
80.0 to 140.0
35.0
95.0
°C
°F
Water Val Condensing Stp Water valve condensing setpoint
11 lim_sp1
0 to 100
100
%
Switch Limit Setpoint 1
Switch limit setpoint 1 (demand limit)
12 lim_sp2
0 to 100
100
%
Switch Limit Setpoint 2
Switch limit setpoint 2 (demand limit)
13 lim_sp3
0 to 100
100
%
Switch Limit Setpoint 3
Switch limit setpoint 3 (demand limit)
*Depends on the selected language (English by default).
QCK_TST1 – Quick Test 1
No. Name
Status
Default Unit Displayed text*
Description
1
QCK_TEST
off/on
off
-
Quick Test Enable
This parameter is used to enable the Quick Test functionality
(Quick test Enable = yes)
With Quick Test enabled: Forcing a specific parameter given in this
table allows the user to verify if the component behaves correctly
2
3
Q_EXVA
0 to 100
0
%
Circuit A EXV Position
EXV position, circuit A (100% = EXV fully open)
4
Q_EXVB
0 to 100
0
%
Circuit B EXV Position
EXV position, circuit B (100% = EXV fully open)
5
Q_EXVC
0 to 100
0
%
Circuit C EXV Position
Not applicable to this unit
6
Q_ECO_A 0 to 100
0
%
Circuit A Eco EXV Pos
Economizer EXV position, circuit A
(100% = Economizer EXV fully open)
7
Q_ECO_B 0 to 100
0
%
Circuit B Eco EXV Pos
Economizer EXV position, circuit B
(100% = Economizer EXV fully open)
8
Q_ECO_C 0 to 100
0
%
Circuit C Eco EXV Pos
Not applicable to this unit
9
Q_OILS_A
off/on
-
-
Circuit A Oil Solenoid
Oil solenoid valve, circuit A
10 Q_SLI_1A
off/on
-
-
Circuit A Slide Valve 1
Slide valve 1, circuit A
11 Q_SLI_2A
off/on
-
-
Circuit A Slide Valve 2
Slide valve 2, circuit A
12 Q_OILS_B
off/on
-
-
Circuit B Oil Solenoid
Oil solenoid valve, circuit B
13 Q_SLI_1B
off/on
-
-
Circuit B Slide Valve 1
Slide valve 1, circuit B
14 Q_SLI_2B
off/on
-
-
Circuit B Slide Valve 2
Slide valve 2, circuit B
15 Q_OILS_C
off/on
-
-
Circuit C Oil Solenoid
Not applicable to this unit
16 Q_SLI_1C
off/on
-
-
Circuit C Slide Valve 1
Not applicable to this unit
17 Q_SLI_2C
off/on
-
-
Circuit C Slide Valve 2
Not applicable to this unit
18 Q_PMP1
0 to 2
-
-
Cooler Pump 1
Cooler pump 1 test:
1 = Pump shall run for a short period of time
2 = Pump shall run all the time (set the value to “0” to stop the
pump test)
19 Q_PMP2
0 to 2
-
-
Cooler Pump 2
Cooler pump 2 test:
1 = Pump shall run for a short period of time
2 = Pump shall run all the time (set the value to “0” to stop the
pump test)
20 Q_HPMP1 0 to 2
-
-
Condenser Pump 1
Condenser pump test:
1 = Pump shall run for a short period of time
2 = Pump shall run all the time (set the value to “0” to stop the
pump test)
21
Q_ELBOXF off/on
-
-
Electrical Box Fan
Electrical box fan
22 Q_READY
off/on
-
-
Chiller Ready Output
Chiller ready output
23 Q_RUN
off/on
-
-
Chiller Running Output
Chiller running output
24 Q_CATO
0 to 100
0
%
Chiller Capacity in0-10V
Chiller capacity in 0-10V
25 Q_RUN_A
off/on
-
-
Cir A Running Output
Running output, circuit A
26 Q_RUN_B
off/on
-
-
Cir B Running Output
Running output, circuit B
27 Q_RUN_C
off/on
-
-
Cir C Running Output
Not applicable to this unit
28 Q_SHUT
off/on
-
-
Shutdown Relay Status
Shutdown relay status
5 - USER INTERFACE: MENU STRUCTURE