24
Set Thermidistat Control Configuration
Configuration options enable the installer to configure the Thermidistat Control for
a particular installation. Most are not presented to the homeowner and therefore
must be properly set by the installer. (Only those marked with an asterisk * below
are available to the homeowner.) The homeowner configurations are described in
the owner’s manual. A special procedure allows entry into the configuration mode.
Selections can be made while in configuration mode. Description of each selection
and how to use the configuration mode follows.
CONFIGURATION OPTIONS -- SUMMARY
Option 01
— Equipment Type
Option 02
— Clean Filter Timer Adjustment
Option 03* — Fahrenheit/Centigrade Selection
Option 04
— Fan (G) on with W/W1 Selection
Option 05
— Room Air Temperature Sensing (programmable
models only)
Option 06
— Cooling Lockout Below 55
_
F/13
_
C Selection (only
available if outdoor air sensor is present)
Option 07
— Zoning
Option 08
— Auxiliary Heat Lockout Temperature Setting (only
available when heat pump is used and when
outdoor air temperature sensor is present)
Option 09
— Heat Pump Lockout Temperature Balance Point (only available
when outdoor air temperature sensor is present)
Option 10
— Reversing Valve
Содержание A07048
Страница 2: ......
Страница 10: ...8 A13295 Fig 2 Coil Excess Wiring A07685 Fig 3 TP PRH A B Carton Contents ...
Страница 15: ...13 A07225 Fig 5 Press Tabs to Remove Backplate A07226 Fig 6 Take Apart ...
Страница 18: ...16 A07166 Fig 9 Secure Wires to Terminal Strip A07167 Fig 10 Connect Pigtail Wires to Display Module ...
Страница 89: ...87 NOTES ...
Страница 90: ...88 NOTES ...
Страница 91: ......