T-318
3
−
32
Table 3-6 Controller Alarm Indications (Sheet 3 of 6)
Alarm Code
Cause
Components
Troubleshooting
Corrective Actions
AL29
AutoFresh
Failure
Alarm 29 is triggered
if CO2 or O2 level is
outside of the limit
range and the vent
position is at 100% for
longer than 90
minutes.
Alarm LED will be
activated and user
intervention is re-
quired.
Refer to eAutoFresh
manual.
The alarm is triggered off
when atmospheric con-
ditions are within limit
settings.
AL50
Air Vent
Position
Sensor (VPS)
VPS Sensor out of
range.
Vent Position
Sensor (VPS)
Make sure VPS is secure. Manually tighten panel.
If the alarm persists,
replace the sensor or the
assembly.
Replace VPS.
AL51
EEPROM
Failure
Controller Memory
Failure
Controller
Pressing the ENTER key
when “CLEAr” is displayed
will result in an attempt to
clear the alarm.
If action is successful (all
alarms are inactive),
AL51 will be reset.
Power cycle the unit. If the
alarm persists, it indicates
defective controller
memory.
Replace defective
controller, refer to
Controller Service
AL52
EEPROM
Alarm List Full
Alarm list queue is full. Active Alarms
Repair any alarms in the
queue that are active.
Indicated by “AA”.
Clear alarms, refer to
CONTROLLER
AL53
Battery Pack
Failure
Battery voltage low
Battery
If this alarm occurs on start
up, allow a unit fitted with
rechargeable batteries to
operate for up to 24 hours
to charge rechargeable
batteries sufficiently. Once
fully charged, the alarm will
deactivate.
To clear the alarm press
ENTER and ALT simul-
taneously at the startup
of Cd19 (Battery Check).
If alarm persists, replace
the battery pack, refer to
Section 6.23.5 Battery
Replacement.
AL54
Primary
Supply Sensor
(STS)
Invalid Supply
Temperature Sensor
(STS) reading.
Supply
Temperature
Sensor (STS)
Perform Pre
−
trip P5:
If P5 passes, no further
action is required.
If P5 fails, replace the
defective sensor as
determined by P5, refer
to TEMPERATURE
SENSOR Service
AL56
Primary
Return Sensor
(RTS)
Invalid Return
Temperature Sensor
(RTS) reading.
Return
Temperature
Sensor (RTS)
Perform Pre
−
trip P5:
If P5 passes, no further
action is required.
If P5 fails, replace the
defective sensor as
determined by P5, refer
to TEMPERATURE
SENSOR Service
Содержание 69NT40-541-300
Страница 2: ......
Страница 4: ......
Страница 20: ......
Страница 32: ......
Страница 128: ......
Страница 131: ...7 3 T 318 Based on Drawing 62 66058 Figure 7 2 SCHEMATIC DIAGRAM Units with 3 Phase Evaporator Motors...
Страница 133: ...7 5 T 318 6 Heater FCCH FCCH Figure 7 4 SCHEMATIC DIAGRAM Units with Normal Evaporator Fan Capability...
Страница 134: ...7 6 T 318 FCCH FCCH Figure 7 5 SCHEMATIC DIAGRAM Units with Single Evaporator Fan Capability...
Страница 136: ...7 8 T 318 To ST10 To TRX2 To QC1 To QC1 To QC1 To MC6 CONTROLLER Figure 7 7 SCHEMATIC DIAGRAM Emergency Bypass...
Страница 138: ...7 10 T 318 Based on Drawing 62 66058 Figure 7 9 UNIT WIRING DIAGRAM Units with 3 Phase Evaporator Motors Sheet 1 of 2...
Страница 139: ...7 11 T 318 Based on Drawing 62 66058 Figure 7 10 UNIT WIRING DIAGRAM Units with 3 Phase Evaporator Motors Sheet 2 of 2...
Страница 144: ......
Страница 150: ......
Страница 151: ......