\\MAINMENU\TEMP

Current path in the menu structure

EWT        

40°C 

List of items

LWT         

46°C

Cursor position

OAT        

4°C

CHWSTEMP      

46°C

SCT_A

49°C

Leaving Water Temperature

Description of the item framed by 

the selection cursor

The Up and Down arrow keys position the cursor on the 
current menu item. The Enter key activates the parameter 
modification (if possible). Any non-pertinent modification 
attempt is blocked by a refusal screen.

4.6 - Parameter modification

A configuration parameter can be modified by positioning 
the cursor and then pressing the Enter key.

\\MAINMENU\SETPOINT

Current path in the menu structure

hps1        

45°C

List of items

hps2         

45°C

Cursor position

hramp_sp        

0.6°C

lim_sp1      

100%

hramp_sp

27.4°C

Heating Setpoint 2

Description of the item framed by 

the selection cursor

The following screen allows modification of a parameter.

Modify value

Screen description

hsp 1

45

°C

Current value

_

°C

Cursor position

Heating Setpoint 2    

Item description

The Up and Down arrow keys permit the selection of the 
first digit. Pressing the Up key successively scrolls up to 
the following symbols:
0, 1, 2, 3, 4, 5, 6, 7, 8, 9, ., -.
The Down key follows the reverse order of the Up key in 
scrolling down the digit list above. Each digit is validated 
with the Enter key.
The - sign is only accessible for the first selected character.

Modify value

Description of the screen

hsp 2

45

°C

Current value

46

°C

New value before validation

Heating Setpoint 2    

Item description

The value is validated with the Enter key.  At any time the 
return key cancels the current modification.

ATTENTION: If the user exits from the current data screen, 
the value is saved. A saving confirmation is displayed. 
The Enter key validates the parameter modification(s). 
The Return to the Previous Screen key cancels the current 
modification(s).

\\MAINMENUSETPOINT

Current path in the menu structure

Save changes?    

Confirmation that the modification is 

saved

4.7 - Operating mode screen

The unit is in Local Off mode, pressing the on/off (0/1) key 
once activates the display of the operating mode screen.

Select Machine Mode

Description of the screen

Local On

List of the machine operating 

modes

Local Schedule

Cursor

CCN
Remote

The Up and Down keys position the cursor on the selected 
operating mode. Four modes are immediately displayed on 
the screen. To access operating modes that are not visible, 
please use the Up and Down keys.

When the operating mode has been selected, the new 
operating mode can be validated with the Enter key.

Command accepted

Operating mode validation screen

When the unit is in an operating mode and the On/off key 
is pressed, the unit will stop. A confirmation screen protects 
the unit against inadvertent shutdowns.

PRESS ENTER

Machine shutdown confirmation 

screen

TO CONFIRM STOP

Содержание 61AF

Страница 1: ...61AF Pro Dialog Control Operating instructions MAINMENU STATUS Circuit B Total Capacity CAPB_T 0 DEM_LIM 100 SP 4 2 C CTRL_PNT 28 9 C EMSTOP dsable ENTER START STOP PRO DIALOG...

Страница 2: ...2 Default screen characteristics 6 4 3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7 Operating mode...

Страница 3: ...is an electronic control system to regulate units of the following types 61AF These units have only one refrigerant circuit The Pro Dialog control regulates compressor start up to control the water l...

Страница 4: ...y communication via the CCN bus 3 4 The sensors Pressure sensors Two types of electronic sensors are used low pressure suction pressure and pump entering pressure optional high pressure discharge pres...

Страница 5: ...X J12 Series RJ 45 series connection Pin 1 signal Pin 2 ground Pin 3 signal J2A J2B J3 J4 J12 J3 J11 J10 J9B J9A J5 J6 J7A J7B J8 J1 J2 J6 J5 J4 J9 J8 J7 3 6 2 Volt free on off contact If the unit wor...

Страница 6: ...entry screen 0_ Password value 0 basic access Description The password is entered digit by digit The cursor is shown at the current digit that flashes The arrow keys modify the digit value The digit m...

Страница 7: ...for the first selected character Modify value Description of the screen hsp 2 45 C Current value 46 C New value before validation Heating Setpoint 2 Item description The value is validated with the En...

Страница 8: ...emperatures Pressures Setpoint Inputs Outputs Unit status Operating time Language selection Alarm menu Configuration menu Disconnection Reset of the alarms Current alarms Alarm history Time schedule H...

Страница 9: ...N mode and this override value will have priority over the other limit values external or limit control 8 Control point This point can be forced in CCN mode and this override value will have priority...

Страница 10: ...sor A2 st_cp_a2 nnnnn Number of start ups compressor A2 hr_fana1l nnnnn hours Number of low speed operating hours fan A1 hr_fana1h nnnnn hours Number of high speed operating hours fan A1 hr_fana2l nnn...

Страница 11: ...off time schedule OCC1P02S Unit setpoint selection time schedule 4 9 15 HOLIDAY menu NAME DESCRIPTION HOLDY_01 Holiday period 1 HOLDY_02 Holiday period 2 HOLDY_03 Holiday period 3 HOLDY_04 Holiday pe...

Страница 12: ...start up of the first electric heater stage ehs_defr Yes No No Quick electric heat stages for defrost 4 9 20 RESETCFG menu NAME FORMAT DEFAULT UNIT DESCRIPTION oathr_non 10 to 51 7 10 C Outside tempe...

Страница 13: ...ive on the same day the occupied mode takes priority over the unoccupied period Each of the eight periods can be displayed and changed with the aid of a sub sub menu The following table shows how to a...

Страница 14: ...Wednesday Thursday Friday Saturday Sunday Holiday OCCTOD6 0 00 24 00 00 00 Occupied from UNOCTOD6 0 00 24 00 00 00 Occupied until DOW7 0 1 0 Period 7 days of the week MTWTFSSH Monday Tuesday Wednesda...

Страница 15: ...Off Active Unoccupied Remote Off Active Open Remote Remote Off Active Remote Unoccupied Remote Off Active Closed Occupied Disabled No Remote On Active Closed Remote Occupied Disabled No Remote On 5 2...

Страница 16: ...ion of compressor starts which makes leaving water temperature control less precise In addition the high pressure low pressure or defrost unloading functions can also affect the temperature control ac...

Страница 17: ...CCN bus All parameters required for the master slave function must be configured through the Service configura tion menu Master slave operation requires the connection of a tempe rature probe at the c...

Страница 18: ...ctions The local interface and its various menus give access to all unit operating conditions If an operating fault is detected an alarm is activated and an alarm code is stored in the Alarms menu sub...

Страница 19: ...01 Water heat exchanger frost protection Automatic if the same alarm has not tripped during the last 24 hours otherwise manual Water flow rate too low or defective thermistor Unit is shut down 19 P 05...

Страница 20: ...arm No Alarm code Alarm description Reset type Probable cause Action taken by the control Process faults continued 37 FC nn Illegal factory configuration number Manual The unit size has been configure...