4.9.24 - OCC1PSX menu
The control provides two timer programs:
The first timer program (No. 1) provides a means to auto-
matically switch the unit from an occupied mode to an 
unoccupied mode: the unit is started during occupied periods. 

The second timer program (No. 2) provides a means to 
automatically switch the active setpoint from an occupied 
setpoint to an unoccupied setpoint, if the Auto mode has 
been selected.

Setpoint 1 is used during occupied periods, setpoint 2 
during unoccupied periods.

Each schedule consists of eight time periods set by the 
operator. These time periods can be flagged to be in effect or 
not in effect on each day of the week plus a holiday period. 
The day begins at 00.00 hours and ends at 23.59 hours.

Program is in unoccupied mode unless a schedule time period 
is in effect. If two periods overlap and are both active on 
the same day, the occupied mode takes priority over the 
unoccupied period.

Each of the eight periods can be displayed and changed 
with the aid of a sub-sub-menu. The following table shows 
how to access the period configuration. Method is the same 
for the time schedule 1 or the time schedule 2.

Time schedule type:

23

22

21

P6

P3

20

P3

19

P3

18

P3

P2

P2

17

P4

P4

P3

P2

P2

16

P4

P4

P3

P2

P2

15

P4

P4

P3

P2

P2

14

P4

P4

P3

P2

P2

13

P4

P4

P3

P2

P2

12

P5

P4

P4

P3

P2

P2

11

P5

P4

P4

P3

P2

P2

10

P5

P4

P4

P3

P2

P2

9

P5

P4

P4

P3

P2

P2

8

P5

P4

P4

P3

P2

P2

7

6

5

4

3

P1

2

P1

1

P1

0

HOL

SUN

SAT

FRI

THU

WES

TUE

MON

Time

MON: 

Monday

TUE: 

Tuesday

WED: 

Wednesday

THU: 

Thursday

FRI: 

Friday

SAT: 

Saturday

SUN: 

Sunday

HOL: 

Holiday

Occupied

Unoccupied

Starts at

Stops at

Active on

P1: period 1,

0h00,

3h00,

Monday

P2: period 2,

7h00,

18h00,

 Tuesday

P3: period 3,

7h00,

21h00,

Wednesday

P4: period 4,

7h00,

17h00,

Th Friday

P5: period 5,

7h00,

12h00,

Saturday

P6: period 6,

20h00,

21h00,

Holidays

P7: period 7,

Not used in this example

P8: period 8,

Not used in this example

Содержание 61AF

Страница 1: ...61AF Pro Dialog Control Operating instructions MAINMENU STATUS Circuit B Total Capacity CAPB_T 0 DEM_LIM 100 SP 4 2 C CTRL_PNT 28 9 C EMSTOP dsable ENTER START STOP PRO DIALOG...

Страница 2: ...2 Default screen characteristics 6 4 3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7 Operating mode...

Страница 3: ...is an electronic control system to regulate units of the following types 61AF These units have only one refrigerant circuit The Pro Dialog control regulates compressor start up to control the water l...

Страница 4: ...y communication via the CCN bus 3 4 The sensors Pressure sensors Two types of electronic sensors are used low pressure suction pressure and pump entering pressure optional high pressure discharge pres...

Страница 5: ...X J12 Series RJ 45 series connection Pin 1 signal Pin 2 ground Pin 3 signal J2A J2B J3 J4 J12 J3 J11 J10 J9B J9A J5 J6 J7A J7B J8 J1 J2 J6 J5 J4 J9 J8 J7 3 6 2 Volt free on off contact If the unit wor...

Страница 6: ...entry screen 0_ Password value 0 basic access Description The password is entered digit by digit The cursor is shown at the current digit that flashes The arrow keys modify the digit value The digit m...

Страница 7: ...for the first selected character Modify value Description of the screen hsp 2 45 C Current value 46 C New value before validation Heating Setpoint 2 Item description The value is validated with the En...

Страница 8: ...emperatures Pressures Setpoint Inputs Outputs Unit status Operating time Language selection Alarm menu Configuration menu Disconnection Reset of the alarms Current alarms Alarm history Time schedule H...

Страница 9: ...N mode and this override value will have priority over the other limit values external or limit control 8 Control point This point can be forced in CCN mode and this override value will have priority...

Страница 10: ...sor A2 st_cp_a2 nnnnn Number of start ups compressor A2 hr_fana1l nnnnn hours Number of low speed operating hours fan A1 hr_fana1h nnnnn hours Number of high speed operating hours fan A1 hr_fana2l nnn...

Страница 11: ...off time schedule OCC1P02S Unit setpoint selection time schedule 4 9 15 HOLIDAY menu NAME DESCRIPTION HOLDY_01 Holiday period 1 HOLDY_02 Holiday period 2 HOLDY_03 Holiday period 3 HOLDY_04 Holiday pe...

Страница 12: ...start up of the first electric heater stage ehs_defr Yes No No Quick electric heat stages for defrost 4 9 20 RESETCFG menu NAME FORMAT DEFAULT UNIT DESCRIPTION oathr_non 10 to 51 7 10 C Outside tempe...

Страница 13: ...ive on the same day the occupied mode takes priority over the unoccupied period Each of the eight periods can be displayed and changed with the aid of a sub sub menu The following table shows how to a...

Страница 14: ...Wednesday Thursday Friday Saturday Sunday Holiday OCCTOD6 0 00 24 00 00 00 Occupied from UNOCTOD6 0 00 24 00 00 00 Occupied until DOW7 0 1 0 Period 7 days of the week MTWTFSSH Monday Tuesday Wednesda...

Страница 15: ...Off Active Unoccupied Remote Off Active Open Remote Remote Off Active Remote Unoccupied Remote Off Active Closed Occupied Disabled No Remote On Active Closed Remote Occupied Disabled No Remote On 5 2...

Страница 16: ...ion of compressor starts which makes leaving water temperature control less precise In addition the high pressure low pressure or defrost unloading functions can also affect the temperature control ac...

Страница 17: ...CCN bus All parameters required for the master slave function must be configured through the Service configura tion menu Master slave operation requires the connection of a tempe rature probe at the c...

Страница 18: ...ctions The local interface and its various menus give access to all unit operating conditions If an operating fault is detected an alarm is activated and an alarm code is stored in the Alarms menu sub...

Страница 19: ...01 Water heat exchanger frost protection Automatic if the same alarm has not tripped during the last 24 hours otherwise manual Water flow rate too low or defective thermistor Unit is shut down 19 P 05...

Страница 20: ...arm No Alarm code Alarm description Reset type Probable cause Action taken by the control Process faults continued 37 FC nn Illegal factory configuration number Manual The unit size has been configure...

Отзывы: