background image

11

4.9.12 - CUR_ALRM menu
This menu lists up to ten a active alarms. For each alarm 
the display shows the time and date the alarm was 
generated as well as the alarm description. Each screen 
shows one alarm.

…\ALARMS\CUR_ALM

HH:MM DD-MM-YY: alarm text

Alarm #1

4.9.13 - ALMHIST1 menu
This menu lists up to twenty alarms that have occurred at 
the unit. For each alarm the display shows the time and date 
the alarm was generated as well as the alarm description. 
Each screen shows one alarm.

…\ALARMS\ALMHIST1

HH:MM DD-MM-YY: alarm text 

Alarm #1

4.9.11 - ALARMRST menu

NAME

FORMAT

UNIT

DESCRIPTION

RST_ALM

Yes/No

-

Alarm reset 

ALM

Normal

-

Alarm status

alarm_1c

nnnnn

-

Current alarm 1

alarm_2c

nnnnn

-

Current alarm 2

alarm_3c

nnnnn

-

Current alarm 3

alarm_4c

nnnnn

-

Current alarm 4

alarm_5c

nnnnn

-

Current alarm 5

alarm_1

nnnnn

-

Current JBus alarm 1

alarm_2

nnnnn

-

Current JBus alarm 2

alarm_3

nnnnn

-

Current JBus alarm 3

alarm_4

nnnnn

-

Current JBus alarm 4

alarm_5

nnnnn

-

Current JBus alarm 5

4.9.14 - SCHEDULE menu

NAME

DESCRIPTION

OCC1P01S

Unit on/off time schedule

OCC1P02S

Unit setpoint selection time schedule

4.9.15 - HOLIDAY menu

NAME

DESCRIPTION

HOLDY_01

Holiday period 1

HOLDY_02

Holiday period 2

HOLDY_03

Holiday period 3

HOLDY_04

Holiday period 4

HOLDY_05

Holiday period 5

HOLDY_06

Holiday period 6

HOLDY_07

Holiday period 7

HOLDY_08

Holiday period 8

HOLDY_09

Holiday period 9

HOLDY_10

Holiday period 10

HOLDY_11

Holiday period 11

HOLDY_12

Holiday period 12

HOLDY_13

Holiday period 13

HOLDY_14

Holiday period 14

HOLDY_15

Holiday period 15

HOLDY_16

Holiday period 16

4.9.16 - BRODCAST menu

NAME

FORMAT

DEFAULT

UNIT    

DESCRIPTION

ccnbroad

0/1/2

2

-

Activates the broadcast 

0 = deactivated, 1= broadast during holidays at the network, 2 = 

broadcast during holidays, machine only 

oatbusnm

0 to 239

0

-

Broadcast of the outside temperature  

Bus number of the machine with the outside temperature

oatlocad

0 to 239

0

-

Element number of the machine with the outside temperature

dayl_sel

Disable/Enable

Disable

-

Activation summer time, winter time

Summer time

startmon

1 to 12

3

-

Month

startdow

1 to 7

7

-

Day of the week (1 = Monday)

startwom

1 to 5

5

-

Week of the month

Winter time

stopmon

1 to 12

10

-

Month

stoptdow

1 to 7

7

-

Day of the week (1 = Monday)

stopwom

1 to 5

5

-

Week of the month

Содержание 61AF

Страница 1: ...61AF Pro Dialog Control Operating instructions MAINMENU STATUS Circuit B Total Capacity CAPB_T 0 DEM_LIM 100 SP 4 2 C CTRL_PNT 28 9 C EMSTOP dsable ENTER START STOP PRO DIALOG...

Страница 2: ...2 Default screen characteristics 6 4 3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7 Operating mode...

Страница 3: ...is an electronic control system to regulate units of the following types 61AF These units have only one refrigerant circuit The Pro Dialog control regulates compressor start up to control the water l...

Страница 4: ...y communication via the CCN bus 3 4 The sensors Pressure sensors Two types of electronic sensors are used low pressure suction pressure and pump entering pressure optional high pressure discharge pres...

Страница 5: ...X J12 Series RJ 45 series connection Pin 1 signal Pin 2 ground Pin 3 signal J2A J2B J3 J4 J12 J3 J11 J10 J9B J9A J5 J6 J7A J7B J8 J1 J2 J6 J5 J4 J9 J8 J7 3 6 2 Volt free on off contact If the unit wor...

Страница 6: ...entry screen 0_ Password value 0 basic access Description The password is entered digit by digit The cursor is shown at the current digit that flashes The arrow keys modify the digit value The digit m...

Страница 7: ...for the first selected character Modify value Description of the screen hsp 2 45 C Current value 46 C New value before validation Heating Setpoint 2 Item description The value is validated with the En...

Страница 8: ...emperatures Pressures Setpoint Inputs Outputs Unit status Operating time Language selection Alarm menu Configuration menu Disconnection Reset of the alarms Current alarms Alarm history Time schedule H...

Страница 9: ...N mode and this override value will have priority over the other limit values external or limit control 8 Control point This point can be forced in CCN mode and this override value will have priority...

Страница 10: ...sor A2 st_cp_a2 nnnnn Number of start ups compressor A2 hr_fana1l nnnnn hours Number of low speed operating hours fan A1 hr_fana1h nnnnn hours Number of high speed operating hours fan A1 hr_fana2l nnn...

Страница 11: ...off time schedule OCC1P02S Unit setpoint selection time schedule 4 9 15 HOLIDAY menu NAME DESCRIPTION HOLDY_01 Holiday period 1 HOLDY_02 Holiday period 2 HOLDY_03 Holiday period 3 HOLDY_04 Holiday pe...

Страница 12: ...start up of the first electric heater stage ehs_defr Yes No No Quick electric heat stages for defrost 4 9 20 RESETCFG menu NAME FORMAT DEFAULT UNIT DESCRIPTION oathr_non 10 to 51 7 10 C Outside tempe...

Страница 13: ...ive on the same day the occupied mode takes priority over the unoccupied period Each of the eight periods can be displayed and changed with the aid of a sub sub menu The following table shows how to a...

Страница 14: ...Wednesday Thursday Friday Saturday Sunday Holiday OCCTOD6 0 00 24 00 00 00 Occupied from UNOCTOD6 0 00 24 00 00 00 Occupied until DOW7 0 1 0 Period 7 days of the week MTWTFSSH Monday Tuesday Wednesda...

Страница 15: ...Off Active Unoccupied Remote Off Active Open Remote Remote Off Active Remote Unoccupied Remote Off Active Closed Occupied Disabled No Remote On Active Closed Remote Occupied Disabled No Remote On 5 2...

Страница 16: ...ion of compressor starts which makes leaving water temperature control less precise In addition the high pressure low pressure or defrost unloading functions can also affect the temperature control ac...

Страница 17: ...CCN bus All parameters required for the master slave function must be configured through the Service configura tion menu Master slave operation requires the connection of a tempe rature probe at the c...

Страница 18: ...ctions The local interface and its various menus give access to all unit operating conditions If an operating fault is detected an alarm is activated and an alarm code is stored in the Alarms menu sub...

Страница 19: ...01 Water heat exchanger frost protection Automatic if the same alarm has not tripped during the last 24 hours otherwise manual Water flow rate too low or defective thermistor Unit is shut down 19 P 05...

Страница 20: ...arm No Alarm code Alarm description Reset type Probable cause Action taken by the control Process faults continued 37 FC nn Illegal factory configuration number Manual The unit size has been configure...

Отзывы: