31
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF position and
install a lockout tag.
There may be more than one
disconnect switch. Lock out and tag switch with a suitable
warning label. Verify proper operation after servicing.
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in improper
furnace operation or failure of furnace.
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous
operation.
CAUTION
!
INTRODUCTION
GENERAL
These instructions are written as if the furnace is installed in an
upflow application. An upflow furnace application is where the
blower is located below the combustion and controls section of
the furnace, and conditioned air is discharged upward. Since this
furnace can be installed in any of the 4 positions shown in Fig. 4,
you must revise your orientation to component location
accordingly.
ELECTRICAL CONTROLS AND WIRING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
There may be more than one electrical supply to the
furnace. Check accessories and cooling unit for additional
electrical supplies that must be shut off during furnace
servicing. Lock out and tag switch with a suitable warning
label.
!
WARNING
The electrical ground and polarity for 115--v wiring must be
properly maintained. Refer to Fig. 24 for field wiring information
and to Fig. 38 for furnace wiring information.
NOTE
: If the polarity is not correct, the STATUS LED on the
control will flash rapidly RED and prevent the furnace from
heating. The control system also requires an earth ground for
proper operation of the control and flame--sensing electrode.
The 24--v circuit contains an automotive--type, 3--amp. fuse
located on the control. (See Fig. 38) Any shorts of the 24--v
wiring during installation, service, or maintenance will cause this
fuse to blow. If fuse replacement is required, use ONLY a 3--amp.
fuse. The control LED will display a three flash AMBER code
when fuse needs to be replaced.
Proper instrumentation is required to service electrical controls.
The control in this furnace is equipped with a multi--colored
Status Code LED (Light--Emitting Diode) to aid in installation,
servicing, and troubleshooting. The furnace control LED is either
ON continuously, rapid flashing, or displaying a flash code in one
of three colors (Red, Green, or Amber).
For an explanation of status codes, refer to service label located
on blower access door or Fig. 35 and the Service guide at the end
of this manual.
See Fig. 35 for a summary of fault codes and a brief explanation
of fault codes.
The stored status code will not be erased from the control
memory, if 115-- or 24--v power is interrupted.
1. To retrieve status code, proceed with the following:
NOTE
: NO thermostat signal may be present at control, and all
blower--OFF delays must be completed.
a. Remove outer access door.
b. Remove inner blower door.
c. Close blower door interlock switch.
d. Depress and hold SW1 button once (for less than 5
seconds).
2. When above items have been completed, the LED flashes
the fault code history (up to 5 fault codes from newest to
oldest). Record the status code(s) for further troubleshoot-
ing.
3. Check LED status. If no previous faults in the history,
control will rapidly flash the LED GREEN.
A180212
Fig. 35 -- Service Label
Содержание 58SU0A Series
Страница 22: ...22 A180242 Fig 25 Chimney Inspection Chart ...
Страница 37: ...37 A180211 Fig 38 Wiring Diagram ...