4
A190303
Fig. 2 -- Clearances to Combustibles
A02055
Fig. 3 -- Return Air Temperature
CODES AND STANDARDS
Follow all national and local codes and standards in addition to
these instructions. The installation must comply with regulations
of the serving gas supplier, local building, heating, plumbing, and
other codes. In absence of local codes, the installation must
comply with the national codes listed below and all authorities
having jurisdiction.
In the United States, follow all codes and standards for the
following:
Safety
S
USA: Current edition of National Fuel Gas Code
(NFGC) NFPA 54/ANSI Z223.1 and the Installation
Standards, Warm Air Heating and Air Conditioning
Systems ANSI/NFPA 90B
General Installation
S
Current edition of the NFGC and the NFPA 90B. For
copies, contact the National Fire Protection Association
Inc., Batterymarch Park, Quincy, MA 02269;
(www.NFPA.org) or for only the NFGC, contact the
American Gas Association, 400 N. Capitol Street,
N.W., Washington, DC 20001 (www.AGA.org).
Combustion and Ventilation Air
S
Current edition of NFGC NFPA54/ANSI Z223.1 Sec-
tion 9.3, Air for Combustion and Ventilation.
Duct Systems
S
Air Conditioning Contractors Association (ACCA)
Manual D, Sheet Metal and Air Conditioning Contract-
ors National Association (SMACNA), or American
Society of Heating, Refrigeration, and Air Condition-
ing Engineers (ASHRAE) 2005 Fundamentals Hand-
book Chapter 35 or 2004 HVAC Systems and Equip-
ment Handbook Chapters 9 and 16.
Acoustical Lining and Fibrous Glass Duct
S
Current edition of SMACNA and NFPA 90B as tested
by UL Standard 181 for Class I Rigid Air Ducts
Gas Piping and Gas Pipe Pressure Testing
S
Current edition of NFGC NFPA54/ANSI Z223.1;
chapters 5, 6, 7, and 8 and National Plumbing Codes.
Electrical Connections
S
Current edition of National Electrical Code (NEC) NF-
PA 70.
Venting
S
Current edition of NFGC NFPA 54 / ANSI Z223.1;
Chapters 12 and 13.
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS PROCEDURE
FURNACE RELIABILITY HAZARD
Improper installation or service of furnace may cause
premature furnace component failure.
Electrostatic discharge can affect electronic components.
Follow the Electrostatic Discharge Precautions Procedure
listed below during furnace installation and servicing to
protect the furnace electronic control. Precautions will
prevent electrostatic discharges from personnel and hand
tools which are held during the procedure. These
precautions will help to avoid exposing the control to
electrostatic discharge by putting the furnace, the control,
and the person at the same electrostatic potential.
CAUTION
!
1. Disconnect all power to the furnace. Multiple disconnects
maybe required. DO NOT TOUCH THE CONTROL OR
ANY WIRE CONNECTED TO THE CONTROL PRIOR
TO
DISCHARGING
YOUR
BODY’S
ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch the clean, unpainted, metal surface of the
furnace chassis which is close to the control. Firmly touch
the clean, unpainted, metal surface of the furnace chassis
which is close to the control. Tools held in a person’s hand
during grounding will be satisfactorily discharged.
3. After touching the chassis, you may proceed to service the
control or connecting wires as long as you do nothing to
recharge your body with static electricity (for example;
DO NOT move or shuffle your feet, do not touch
ungrounded objects, etc.).
4. If you touch ungrounded objects (and recharge your body
with static electricity), firmly touch a clean, unpainted
metal surface of the furnace again before touching control
or wires.
5. Use this procedure for installed and uninstalled
(ungrounded) furnaces.
6. Before removing a new control from its container,
discharge your body’s electrostatic charge to ground to
protect the control from damage. If the control is to be
installed in a furnace, follow items 1 through 4 before
bringing the control or yourself in contact with the
Содержание 58SU0A Series
Страница 22: ...22 A180242 Fig 25 Chimney Inspection Chart ...
Страница 37: ...37 A180211 Fig 38 Wiring Diagram ...