PACKAGED TERMINAL COOLING UNIT

WITH HEAT PUMP OR ELECTRIC HEATING

HVAC Guide Specifications

Size Range:

Cooling:

6,900 to 15,000 Btuh

Heating:

6,000 to 13,400 Btuh

Heat Pump:6,400 to 17,000 Btuh Electric

Carrier Model Numbers:

52ME Performance Series, Cooling with Electric

Heat
52MQ Performance Series, Heat Pump with Electric

Heat

Part 1 — System Description

Packaged Terminal Air Conditioners shall be of the

sizes and capacities as shown on the contract drawing

schedule and in the specifications.
System shall be tested to insure no water infiltration

into the room, when tested at eight inches of rain per

hour with 55 mph wind.

The complete system shall consist of the following:

A.

Packaged Terminal Heat Pump or Heat/Cool

Chassis

: See section 2 -- Chassis Description

B.

Power Cord OR Hardwire Kit

shall provide the

power connection to the unit.

C.

Insulated Polymer Wall Sleeve

shall provide

excellent thermal insulation, be textured to hide

scratches and prevent shine, will have superior

outdoor noise absorption and shall be corrosion

free for the life of the product. The Wall Sleeve

must have dimensions of 42” width x 16“ height x

14--7/8” depth and be shipped with a rear weather

barrier installed.

D.

Wall Sleeve Molding

shall trim the wall sleeve to

the existing wall, to hide wall imperfections and

irregularities due to the sleeve opening.

E.

Outdoor Polymer Louvered Grille

shall resist

corrosion, breakage and match the color specified

on drawing schedule and specifications.

F.

Subbase

will support the wall sleeve when it

extends into the room more than 4 inches.

Subbase

must

come

from

the

factory

pre--assembled, with a built in receptacle (size as

specified

on

drawing

schedule

and

specifications).

Part 2 — Chassis Description

2.1 General:

The chassis shall be a factory--assembled,

single--piece heating and/or cooling unit, that is

simple to install and operate. Just slide the chassis

into a wall sleeve, plug it into an outlet, and operate

after installation. The chassis dimensions shall not

exceed 42” wide and 16“ high with room cabinet in

place. The chassis shall consist of the following

functional sections and components:

A.

Certifications

:

System shall be approved and certified by UL &

UL, Canada. Chassis capacity and efficiency

performance shall be certified in accordance with

ARI standard 310/380. Chassis shall meet

ASHRAE Standard 90.1 for minimum energy

efficiency.

B.

Operating Characteristics:

Chassis shall be capable of starting and running at

115

_

F ambient outdoor temperature per maximum

load criteria of ARI Standard 310/380.

C.

Electrical

:

The accessory power cord or hardwire kit for the

unit will be ordered separately. The power cord

accessory will be 58 inches for 208/230v models

or 15 inches for 265v models. The Hardwire kit

accessory will provide 36 inches of flexible

conduit. The chassis current draw shall be

specified on the chassis nameplate and match

electrical requirements specified on the Contract

drawing schedule and specifications.

The power cord plug configuration shall conform

to NEMA standards and the rating shall support

the current draw of the electric resistance heater.

For 265v installations, UL codes require the use of

an electrical equipped subbase for power cord

usage or hardwire conduit for non--corded

installations.

D.

Safeties

:

Compressor shall have automatic reset, over

temperature and over current protection. The fan

motors shall have an inherent, automatic reset

over temperature protection. The electric heater

shall have two over temperature protectors

.

52M

Содержание 52M Performance Series

Страница 1: ...ation 9 Wall Thermostat Interface 9 Energy Management EM Interface 10 Power Cord for 265V Units 10 Power Cord Protection for 230 208V Units 11 Bi Molded Condenser Shroud 11 Easy Access Chassis 11 Enha...

Страница 2: ...ies 52M whisper quiet model is Carrier s quietest and most energy efficient PTAC unit ever The Performance refrigerant system utilizes the highest efficiency compressors and coil design to achieve max...

Страница 3: ...9 000 10 9 8 400 3 5 239 292 275 285 300 3 2 825 125 52MQ U12 4 11 400 10 8 10 600 3 239 292 220 250 290 4 2 1 050 140 52MQ U15 4 15 000 POWER CORD SELECTION 52M PTACs are not individually equipped wi...

Страница 4: ...eat pump models offer substantial savings over models with conventional electric resistance heaters S Individual units allow tenants to choose the degree of comfort and operating economy S Rapid servi...

Страница 5: ...the space down to the desired temperature during very hot days The result could be warm and humid or warm and dry conditioned space Oversizing If a PTAC unit is oversized cooling capacity is greater...

Страница 6: ...l Arm Allows outdoor air into room through vent filter for improved air quality S Control Door Provides protection for controls and enhances appearance S Improved Condensate Removal Minimizes condensa...

Страница 7: ...ts S No bulky duct system S No seasonal changeover QUIET OPERATION Occupants and neighbors are protected against noise intrusion Indoor sound reduction is achieved through the units two fan motor and...

Страница 8: ...l sleeves are available in a variety of sizes for most standard and deep wall applications All metal wall sleeves come with factory installed insulation designed to minimize heat loss and reduce outdo...

Страница 9: ...or but can easily be adjusted to an 80 degree angle to the floor Air discharge upward Air discharge outward Default A07550 Reversible Polycarbonate Discharge Grille DIGITAL KEYPAD AND ELECTRONIC DISPL...

Страница 10: ...The EM interface is standard and provides a simple to install Energy Management connection The unit has a removable terminal connector to make field wiring easy When 24VAC is supplied to the input th...

Страница 11: ...Plug Head BI MOLDED CONDENSER SHROUD The bi molded condenser shroud provides easy access for service and maintenance of the condenser coil and related components BI MOLDED CONDENSER SHROUD A07677 Bi...

Страница 12: ...d coils keeping coils from direct contact with the basepan and providing additional protection against corrosion A07552 CONDENSATE DRAIN VALVE The temperature activated drain valve opens when the outd...

Страница 13: ...ow for both heating and cooling functions and remains energized as long as the controls are in the heat position When the cooling controls are activated the valve automatically reverses to the cooling...

Страница 14: ...s Payback in Months I 06 08 10 34 26 45 68 57 10 21 16 13 43 08 57 44 71 80 21 16 13 58 20 77 60 97 00 19 14 11 68 34 91 12 113 90 19 14 12 II 06 08 10 57 12 76 16 95 20 13 9 8 71 76 95 68 119 60 13 9...

Страница 15: ...DISPLAY WALL THERMOSTAT AND ENERGY MANAGEMENT INTERFACE CONFIGURATION DIP SWITCHES A06752 PRODUCT CATALOG NUMBER Electrical Data 3 230 208 v 60 Hz 4 265 v 60 Hz Cooling Capacity nominal 07 7 000 Btuh...

Страница 16: ...aximum protection and appearance All Carrier s polymer wall sleeves are made from a molded polymer that is designed for strength and durability This material has excellent corrosion resistance and a f...

Страница 17: ...MOLDING For a superior look and to hide any construction imperfections use Carrier s wall sleeve molding kit to trim the wall sleeve to the wall The molding kit is a perfect solution and can be used w...

Страница 18: ...asily from inside the room These elegant grilles available in many standard colors have baked enamel finishes containing 50 Kynarr resin for a superior finish that will withstand the most extreme cond...

Страница 19: ...t be followed since a louver that is restrictive or allows re circulation will result in a reduction of the unit s capacity and efficiency and will ultimately shorten the compressor life X Y X Y X Y X...

Страница 20: ...aximum clearance is 5 1 2 inches IMPORTANT All standard cord connected 265 v PTAC units will require a field installed electrical subbase accessory per UL and NEC electrical codes All subbase models a...

Страница 21: ...ASE FUSE 30A Thefusekit provides in lineovercurrent protectionat the unit when required by NEC National Electric Code or local codes IMPORTANT The Fuse Kit can only be used with the electrical or hard...

Страница 22: ...dels Part No PTACSTAT NP HP A heat pumps This low voltage easy to use non programmable thermostat provides maximum guest comfort A07135 Non Programmable Thermostat Digital Programmable Thermostat Part...

Страница 23: ...in the wafer area A07748 Drain Kit Power Vent with Power Door Kit Part No 52M PWRVENT DOOR Carrier s power vent kit utilizing a specially designed fan when installed in the unit s fresh air vent will...

Страница 24: ...ntractor Installed wall sleeve must be level from side to side and front to back 208 230 v 42 1067 ACCESSORY WALL SLEEVE HINGED CONTROL ACCESS DOOR DISCHARGE GRILLE REMOVABLE FRONT PANEL 2 03 51 6 3 9...

Страница 25: ...7381 Standard and Extended Metal Insulated Wall Sleeve NOTES All Sleeves 1 Never install fasteners through bottom of sleeve 2 Never use rails to level sleeve MAIN STUD JACK STUD CRIPPLE FLOOR SUB FLOO...

Страница 26: ...y have to be notched to accommodate service cord 2 If more than 4 in of sleeve projects into room an accessory subbase must be used for support 3 For walls 2 in thick or less an accessory subbase must...

Страница 27: ...UM CLEARANCE FOR INDOOR AND OUTDOOR DISCHARGE AIR EQUIPMENT OPERATION HAZARD Failure to follow this caution may result in equipment damage or improper operation Blocking indoor or outdoor discharge ai...

Страница 28: ...VIEW ACCESSORY SUBBASE ELECTRICAL CONNECTIONS NOTES 1 Accessory subbase is required for applications where Wall sleeve extends 4 or more inches into the room Wall thickness is less than 2 inches All 2...

Страница 29: ...ox Wire Terminal for Wall Thermostat Models R W Y O Gh Gl C A07073 Terminal Connector Removal and Replacement THERMOSTAT WIRE ROUTING UNDER SLEEVE BEHIND FRONT PANEL A07074 Terminal Wire Routing NOTE...

Страница 30: ...ORD SELECTION GUIDE 52M PTACs are not individually equipped with a power cord so one must be ordered separately based on the voltage and ampeage of your electrical circuit If the unit is to be plugged...

Страница 31: ...o one must be ordered separately based on the voltage and ampeage of your electrical circuit If the unit is to be plugged into a receptacle then a line cord connection kit needs to be selected If it w...

Страница 32: ...equipped with a power cord so one must be ordered separately based on the voltage and ampeage of your electrical circuit If the unit is to be plugged into a receptacle then a line cord connection kit...

Страница 33: ...he voltage and ampeage of your electrical circuit If the unit is to be plugged into a receptacle then a line cord connection kit needs to be selected If it will be permanently connnected a hardwire co...

Страница 34: ...D SUPPLIED LEGEND NOTES 1 To size transformer use the following equation Quantity of PTAC units x 12 va Transformer Size va Example 110 PTAC Units x 12 va 1320 va Transformer 2 Following are recommend...

Страница 35: ...O C R Y W G O C R Y W G O C R Y W G O C R Y W G O C T STAT MASTER PTAC UNIT 1 UNIT 2 UNIT 3 1 Do not daisy chain R 24 VAC 2 Maximum of 4 PTAC units can be connected to one single wall thermostat 3 Wa...

Страница 36: ...specified on drawing schedule and specifications Part 2 Chassis Description 2 1 General The chassis shall be a factory assembled single piece heating and or cooling unit that is simple to install and...

Страница 37: ...n be easily configured All models shall have a configuration dipswitch easily accessible for the maintenance person optimal comfort settings CONTINUOUS or CYCLE fan mode in HEATING CONTINUOUS or CYCLE...

Страница 38: ...shall have 36 inches of flexible steel conduit and a plug in connector for easy connect disconnect 3 Insulated Polymer Wall Sleeve PN SLEEVE INSUL 1PK shall be made from a molded polymer with factory...

Страница 39: ...force of 10 g s and a random continuous force of 1g during shipping Chassis wall sleeves and grilles shall be shipped in separate cartons Universal handling instructions shall be defined and visible...

Страница 40: ...ctory installed 208 230V 15 amp receptacle Electrical subbase with factory installed 208 230V 20 amp receptacle Electrical subbase with factory installed 208 230V 30 amp receptacle 52C P 17SI SUBBASE...

Страница 41: ...Y ARE EXCLUSIVE AND MAY NOT BE ALTERED ENLARGED OR CHANGED BY ANY DISTRIBUTOR DEALER OR OTHER PERSON WHATSOEVER ALL WORK UNDER THE TERMS OF THIS WARRANTY SHALL BE PERFORMED DURING NORMAL WORKING HOURS...

Страница 42: ...DEALER OR THE CARRIER AUTHORIZED SERVICE CENTER HE RECOMMENDS They have been set up to handle the great majority of all possible service problems The quickest surest and best way to get your air condi...

Отзывы: