Secure screws and paint protectors solidly against unit base to
hold lifting brackets in position. Never use lifting brackets
when the temperature is below -10 F (-23 C). Never exceed
200 lbs per bracket of lifting force. Never use lifting brackets
for lifting other models of air conditioning units. Lifting point
should be directly over the unit center of gravity. Failure to
follow this warning could result in personal injury or death.
1. Position brackets as close to the corners of unit as possible. Be
sure brackets are well outside of center of gravity (See Fig.
2-5, and 7).
2. Position paint protectors and foam strips between screws and
painted surface of unit. Tighten screws until they make contact
with the paint protectors.
3. Secure device or hook of sufficient strength to hole in bracket
as shown in detail ’’C’’ of Fig. 7.
4. If wood top is available, use it for a spreader bar to prevent
straps from damaging unit. If wood top is not available, use
spreader bars of sufficient length.
UNITS WITH OPTIONAL BASE RAILS - Keep unit upright and
do not drop. Use spreader bars or top crate when rigging unit.
Rollers may be used to move unit across roof. Level unit for proper
condensate disposal. See Fig. 7 for additional information. Lifting
Fig. 3— 50HX024-030 Unit Dimensions (with base rails)
UNIT
ELECTRICAL CHARACTERISTICS
UNIT WEIGHT
CORNER WT
LB/KG
CENTER OF GRAVITY
IN/MM
lb.
kg
A
B
C
D
X
Y
Z
50HX024
208/230-1-60
277
126
62/28
74/34
80/36
61/28
20.2/515
21.3/541
13.8/351
50HX030
208/230-1-60
308
140
61/28
92/42
79/36
76/35
20.2/514
21.5/547
13.8/351