SPECIAL PROCEDURES FOR 208-V OPERATION
Make sure that the power supply to the unit is switched OFF
and lockout tag installed before making any wiring changes.
Electrical shock can cause serious injury or death.
1. Disconnect the orange transformer-primary lead from the
contactor. See unit wiring label
2. Remove the wire nut from the terminal on the end of the red
transformer-primary lead.
3. Save the wire nut.
4. Connect the red lead to the contactor terminal from which the
orange lead was disconnected.
5. Using the wire nut removed from the red lead, insulate the
loose terminal on the orange lead.
6. Wrap the wire nut with electrical tape so that the metal
terminal cannot be seen.
NOTE:
Indoor blower motor speeds may need to be changed for
208-v operation. Refer to Indoor Airflow and Airflow Adjustment
Section.
Fig. 20—Field-Fabricated Duct Cover
C95019
14 11/16” (372)
13 3/4” (348)
3 3/4” (94)
0
0
10 5/8” (270)
9/32” (7) TYP
19” (482)
22-GAGE SHEET
METAL COVER (SEE ABOVE)
4 ADHESIVE-BACKED SPONGE RUBBER
SEAL STRIPS-1/8”
(3.2)
THICK
31 3/16” (792)
9 11/16” (245)
21 9/16” (547)
11/32” DIA (8 Places/Holes)
11/16” (17) TYP
1 3/4” (43) 0
SEAL ALL FOUR CORNERS
WITH SILICONE SEALER
1//2-IN. THICK, 1-lb
. DENSITY FIBERGLASS INSULATION
WITH ALUMINUM FOIL BACKING; SECURE WITH ADHESIVE
Table 2—Minimum Airflow for Safe Electric Heater
Operation (Cfm)
SIZE
024
030
036
042
048
060
700
875
1225
1225
1400
1750
15