![Carrier 50HCQ12 Скачать руководство пользователя страница 8](http://html.mh-extra.com/html/carrier/50hcq12/50hcq12_installation-instructions-manual_2563303008.webp)
8
Step 1 —
Plan for Unit Location
Select a location for the unit and its support system (curb or other)
that provides for the minimum clearances required for safety (in
-
cluding clearance to combustible surfaces), unit performance and
service access below, around and above unit as specified in unit
drawings. See Fig. 3.
NOTE: Consider also the effect of adjacent units.
Unit may be installed directly on wood flooring or on Class A, B,
or C roof-covering material when roof curb is used.
Do not install unit in an indoor location. Do not locate air inlets
near exhaust vents or other sources of contaminated air.
Although unit is weatherproof, avoid locations that permit water
from higher level runoff and overhangs to fall onto unit.
Select a unit mounting system that provides adequate height to al
-
low installation of condensate trap per requirements. Refer to Step
9 — Install External Condensate Trap and Line on page 14 for re
-
quired trap dimensions.
ROOF MOUNT
Check building codes for weight distribution requirements. Unit
operating weight is shown in Table 5.
Table 5 —
Operating Weights
Step 2 —
Plan for Sequence of Unit Installation
The support method used for this unit will dictate different se
-
quences for the steps of unit installation. For example, on curb-
mounted units, some accessories must be installed on the unit be
-
fore the unit is placed on the curb. Review the following for rec
-
ommended sequences for installation steps:
CURB-MOUNTED INSTALLATION
1. Install curb.
2. Install field-fabricated ductwork inside curb.
3. Install accessory thru-base service connection package
(affects curb and unit) (refer to accessory installation
instructions for details).
4. Prepare bottom condensate drain connection to suit
planned condensate line routing (refer to Step 10 — Install
External Condensate Trap and Line on page 14 for
details).
5. Rig and place unit.
6. Install outdoor air hood.
7. Install condensate line trap and piping.
8. Make electrical connections.
9. Install other accessories.
PAD-MOUNTED INSTALLATION
1. Prepare pad and unit supports.
2. Check and tighten the bottom condensate drain connection
plug.
3. Rig and place unit.
4. Convert unit to side duct connection arrangement.
5. Install field-fabricated ductwork at unit duct openings.
6. Install outdoor air hood.
7. Install condensate line trap and piping.
8. Make electrical connections.
9. Install other accessories.
FRAME-MOUNTED INSTALLATION
Frame-mounted applications generally follow the sequence for a
curb installation. Adapt the sequence as required to suit specific
installation plan.
Step 3 —
Inspect Unit
Inspect unit for transportation damage. File any claim with trans
-
portation agency.
Confirm before installation of unit that voltage, amperage and cir
-
cuit protection requirements listed on unit data plate agree with
power supply provided.
On units with hinged panel option, check to be sure all latches are
snug and in closed position.
Locate the carton containing the outside air hood parts. Do
not remove carton until unit has been rigged and located in final
position.
Step 4 —
Provide Unit Support
ROOF CURB MOUNT
Accessory roof curb details and dimensions are shown in Fig. 6.
Assemble and install accessory roof curb in accordance with in
-
structions shipped with the curb.
Curb should be level. This is necessary for unit drain to function
properly. Unit leveling tolerances are shown in Fig. 7. Refer to
Accessory Roof Curb Installation Instructions for additional infor
-
mation as required.
Install insulation, cant strips, roofing felt, and counter flashing as
shown.
Ductwork must be attached to curb and not to the unit. The
accessory thru-the-base power connection package must be in
-
stalled before the unit is set on the roof curb.
If electric and control wiring is to be routed through the basepan,
attach the accessory thru-the-base service connections to the base
-
pan in accordance with the accessory installation instructions.
NOTE: The gasketing of the unit to the roof curb is critical for a
watertight seal. Install gasket supplied with the roof curb as shown
in Fig. 6. Improperly applied gasket can also result in air leaks and
poor unit performance.
SLAB MOUNT (HORIZONTAL UNITS ONLY)
Provide a level concrete slab that extends a minimum of 6 in.
(150 mm) beyond unit cabinet. Install a gravel apron in front of
condenser coil air inlet to prevent grass and foliage from obstruct
-
ing airflow.
NOTE: Horizontal units may be installed on a roof curb if
required.
ALTERNATE UNIT SUPPORT (IN LIEU OF CURB OR
SLAB MOUNT)
A non-combustible sleeper rail can be used in the unit curb sup
-
port area. If sleeper rails cannot be used, support the long sides of
the unit with a minimum of 3 equally spaced 4-in. x 4
-
in. (102 mm
x 102 mm) pads on each side.
50HCQ12D
COMPONENT
UNIT LB (KG)
Base Unit
1390 (632)
Economizer
Vertical
100 (45)
Horizontal
115 (52)
Powered Outlet
32 (15)
Curb
14 in. (356 mm)
180 (82)
24 in. (610 mm)
235 (107)
Содержание 50HCQ12
Страница 4: ...4 Fig 2 Unit Dimensional Drawing Size 12 Units ...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing Size 12 Units cont ...
Страница 9: ...9 Fig 6 Roof Curb Details REV 50TM500827 ...
Страница 25: ...25 Fig 42 Typical 50HCQ Control Wiring Diagram ...
Страница 26: ...26 Fig 43 Typical 50HCQ Power Wiring Diagram 208 230 3 60 unit shown ...
Страница 27: ...27 Fig 44 PremierLink Controller Wiring Schematic ...
Страница 28: ...28 Fig 45 RTU Open Controller System Wiring Diagram ...