Fig. 51 —
Single Enthalpy Curve Boundaries
Table 22 —
Single Enthalpy and Dual Enthalpy High Limit Curves
Enthalpy Settings
When the OA temperature, enthalpy and dew point are below the
respective setpoints, the Outdoor Air can be used for economiz
-
ing. Figure 51 shows the new single enthalpy boundaries in the
W7220. There are 5 boundaries (setpoints ES1 through ES5),
which are defined by dry bulb temperature, enthalpy and dew
point.
Refer to Table 22 for ENTH CURVE setpoint values.
The W7220 calculates the enthalpy and dew point using the OA
temperature and humidity input from the OA enthalpy sensor.
When the OA temperature, OA humidity and OA dew point are
all below the selected boundary, the economizer sets the econo
-
mizing mode to YES, economizing is available.
When all of the OA conditions are above the selected boundary,
the conditions are not good to economize and the mode is set to
NO.
Figure 51 shows the 5 current boundaries. There is also a high lim
-
it boundary for differential enthalpy. The high limit boundary is
ES1 when there are no stages of mechanical cooling energized and
HL (high limit) when a compressor stage is energized.
Two-Speed Fan Operation
The W7220 controller has the capability to work with a system us
-
ing a 2-speed supply fan. The W7220 does not control the supply
directly but uses the following input status to determine the speed
of the supply fan and controls the OA damper to the required
position.
The W (heating mode) is not controlled by the W7220 but it re
-
quires the status to know where to position the OA damper for
minimum position for the fan speed.
The 2-speed fan delay is available when the system is pro
-
grammed for 2-speed fan (in the System Setup menu item). The 2-
speed fan delay is defaulted to 5 minutes and can be changed in
the Advanced Setup menu item. When the unit has a call for Y1 In
and in the free cooling mode and there is a call for Y2 In, the 2-
speed fan delay starts and the OA damper will modulate 100%
open, the supply fan should be set to high speed by the unit
controller.
After the delay one of two actions will happen:
• The Y2 In call will be satisfied with the damper 100%
open and fan on high speed and the call will turn off
OR
• If the call for additional cooling in the space has not been
satisfied then the first stage of mechanical cooling will be
enabled through Y1 Out or Y2 Out.
Checkout
Inspect all wiring connections at the economizer module’s termi
-
nals, and verify compliance with the installation wiring diagrams.
For checkout, review the Status of each configured parameter and
perform the Checkout tests.
For information about menu navigation and use of the keypad see
Interface Overview on page 31.
ENTHALPY
CURVE
TEMP. DRY
BULB (F)
TEMP.
DEWPOINT (F)
ENTHALPY
(btu/lb/da)
POINT P1
POINT P2
TEMP. (F)
HUMIDITY
(%RH)
TEMP. (F)
HUMIDITY
(%RH)
ES1
80
60
28.0
80
36.8
66.3
80.1
ES2
75
57
26.0
75
39.6
63.3
80.0
ES3
70
54
24.0
70
42.3
59.7
81.4
ES4
65
51
22.0
65
44.8
55.7
84.2
ES5
60
48
20.0
60
46.9
51.3
88.5
HL
86
66
32.4
86
38.9
72.4
80.3
ECONOMIZING
AVAILABLE
NOT AVAILABLE
ENTHALPY
RA
HUM (%RH)
RA
TEMP
TEMPERATURE
ABSOLUTE HUMIDITY
ES5
ES4
ES3
ES2
ES1
HL
P1
(T,RH)
P2 (T,RH)
SINGLE ENTHALPY
DUAL ENTHALPY
HIGH LIMIT
STATE
FAN SPEED
OCC
Low
Y1
Low
Y2
High
W
High
Содержание 50HCQ12
Страница 4: ...4 Fig 2 Unit Dimensional Drawing Size 12 Units ...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing Size 12 Units cont ...
Страница 9: ...9 Fig 6 Roof Curb Details REV 50TM500827 ...
Страница 25: ...25 Fig 42 Typical 50HCQ Control Wiring Diagram ...
Страница 26: ...26 Fig 43 Typical 50HCQ Power Wiring Diagram 208 230 3 60 unit shown ...
Страница 27: ...27 Fig 44 PremierLink Controller Wiring Schematic ...
Страница 28: ...28 Fig 45 RTU Open Controller System Wiring Diagram ...