31
S-Bus Sensor Wiring
The labels on the sensors and controller are color coded for ease of
installation. Orange labeled sensors can only be wired to orange
terminals on the controller. Brown labeled sensors can only be
wired to S-bus (brown) terminals. Use Fig. 48 and Table 10 to lo
-
cate the wiring terminals for each S-Bus sensor.
Use Fig. 48 and Table 10 to locate the wiring terminals for each
enthalpy control sensor.
Fig. 48 —
S-Bus Sensor DIP Switches
Table 10 —
HH57AC081 Sensor Wiring Terminations
Use Fig. 48 and Table 11 to set the DIP switches for the desired
use of the sensor.
Table 11 —
HH57AC081 Sensor DIP Switch
NOTE: When an S-Bus sensor is connected to an existing net
-
work, it will take 60 minutes for the network to recognize and
auto-configure itself to use the new sensor.
During the 60-minute setup period, no alarms for sensor failures
(except SAT) will be issued and no economizing function will be
available.
CO
2
Sensor Wiring
When using a CO
2
sensor the black and brown common wires are
internally connected and only one is connected to “IAQ COM” on
the W7220 (see Fig. 47). Use the power from the W7220 to power
the CO
2
sensor OR make sure the ground for the power supplies
are common. See Fig. 49 for CO
2
sensor wiring.
Fig. 49 —
CO
2
Sensor Wiring
Interface Overview
This section describes how to use the EconoMi$er
®
X user inter
-
face for:
• Keypad and menu navigation
• Settings and parameter changes
• Menu structure and selection
User Interface
The user interface consists of a 2-line LCD display and a 4-button
keypad on the front of the economizer controller.
Keypad
Use the four navigation buttons (see Fig. 50) to scroll through the
menus and menu items, select menu items, and to change parame
-
ter and configuration settings.
To use the keypad when working with menus:
• Press the ▲ (Up arrow) button to move to the previous
menu.
• Press the ▼ (Down arrow) button to move to the next
menu.
• Press the
(Enter) button to display the first item in the
currently displayed menu.
• Press the (Menu Up/Exit) button to exit a menu’s item
and return to the list of menus.
Fig. 50 —
W7220 Controller Navigation Buttons
TERMINAL
TYPE
DESCRIPTION
NUMBER
LABEL
1
S-BUS
S-BUS
S-BUS
Communications
(Enthalpy Control
Sensor Bus)
2
S-BUS
S-BUS
S-BUS
Communications
(Enthalpy Control
Sensor Bus)
USE
DIP SWITCH POSITIONS FOR SWITCHES 1, 2, AND 3
1
2
3
DA
OFF
ON
OFF
RA
ON
OFF
OFF
OA
OFF
OFF
OFF
DIP
SWITCH
LABEL
DIP
SWITCHES
(3)
S-BUS
2 PIN SIDE
CONNECTOR
S-BUS
TERMINALS
(1 AND 2)
CO
2
SENSOR
24V
ANALOG
OUT
L1
(HOT)
L2
RED
BLACK
YELLOW
BROWN
ORANGE
GREEN
+
–
POWER SUPPLY. PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
1
1
2 LINE
LCD
MENU UP
(EXIT)
BUTTON
SCROLL
UP/DOWN
BUTTONS
SELECT
(ENTER)
BUTTON
Содержание 50HCQ12
Страница 4: ...4 Fig 2 Unit Dimensional Drawing Size 12 Units ...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing Size 12 Units cont ...
Страница 9: ...9 Fig 6 Roof Curb Details REV 50TM500827 ...
Страница 25: ...25 Fig 42 Typical 50HCQ Control Wiring Diagram ...
Страница 26: ...26 Fig 43 Typical 50HCQ Power Wiring Diagram 208 230 3 60 unit shown ...
Страница 27: ...27 Fig 44 PremierLink Controller Wiring Schematic ...
Страница 28: ...28 Fig 45 RTU Open Controller System Wiring Diagram ...