Carrier 50GJ006 Скачать руководство пользователя страница 27

When the second stage of cooling is satisfied, the com-

pressor and outdoor (condenser) fan motor will be de-
energized. The damper position will be determined by the
supply-air temperature.

When the first stage of cooling is satisfied, the damper

will move to fully closed position.

COOLING, 50GJ006 UNITS WITH PARABLADE ECONO-
MIZER — When the outdoor-air is above the enthalpy con-
trol setting, and the room thermostat calls for cooling, the
compressor contactor is energized to start the compressor and
the outdoor (condenser) fan motor. The indoor (evaporator)
fan motor is energized and the economizer damper moves to
the minimum position. After the room thermostat is satisfied
the damper will spring return to the fully closed position.

When the outdoor-air is below the enthalpy control set-

ting and the thermostat calls for cooling, the economizer out-
door air damper is opened proportionally to maintain between
50 and 56 F at the mixed air sensor. If outside air alone can-
not satisfy the cooling requirements, economizer cooling is
integrated with mechanical cooling. When the room thermo-
stat is satisfied, the damper will spring return to the fully
closed position.

COOLING, 50GJ008,012 UNITS WITH PARABLADE
ECONOMIZER — When the outdoor air is above the en-
thalpy control setting, and the room thermostat calls for cool-
ing, the compressor contactor no. 1 is energized to start
compressor no. 1 and the outdoor (condenser) fan motor. The
indoor (evaporator) fan motor is energized and the econo-
mizer damper moves to the minimum position. Upon further
call for cooling, compressor contactor no. 2 is energized, start-
ing compressor no. 2. After the room thermostat is satisfied
the damper will spring return to the fully closed position.

When the outdoor air is below the enthalpy control setting

and the thermostat calls for cooling, the economizer outdoor
air damper is opened proportionally to maintain between
50 and 56 F at the mixed air sensor. If outside air alone can-
not satisfy the cooling requirements, economizer cooling is
integrated with mechanical cooling and the second compres-
sor is locked out. When the room thermostat is satisfied, the
damper will spring return to the fully closed position.

HEATING, 50GJ006 UNITS WITH ECONOMIZER (If Ac-
cessory Heater is Installed) — Upon a call for heat through
W1, the IFC energizes to start the evaporator fan and the
economizer damper blade opens to the minimum position. If
the accessory two-position damper is used, the outdoor-air
damper opens to the minimum position whenever the evapo-
rator fan runs. If unit is equipped with 2 stages of heat, when
additional heat is needed a call is made through W2.

As space temperature approaches the heating temperature

set point, heating stages cycle off. Economizer or two-
position damper returns to fully closed position.

HEATING, 50GJ008,012 UNITS WITH ECONOMIZER (If
Accessory Heater is Installed) — When the room thermostat
calls for heat through terminal W1, the evaporator-fan con-
tactor and heater contactor no. 1 are energized. On units
equipped for 2 stages of heat, when additional heat is needed,
heater contactor no. 2 is energized through W2. The evaporator-
fan motor is energized, and the economizer damper moves
to the minimum position. If the two-position damper is used,
the outdoor-air damper opens to the minimum position when-
ever the evaporator fan opens. When the thermostat is sat-
isfied, the damper moves to the fully closed position.

SERVICE

When servicing unit, shut off all electrical power to unit
to avoid shock hazard or injury from rotating parts.

Cleaning —

Inspect unit interior at the beginning of each

heating and cooling season or as operating conditions
require.

EVAPORATOR COIL
1. Turn unit power off. Remove evaporator coil access panel.
2. If economizer or accessory two-position damper is in-

stalled, remove economizer/two-position damper by dis-
connecting economizer plug and removing mounting screws
(see Fig. 14 or 15). Refer to Accessory Economizer or
Two-Position Damper Installation Instructions for more
details.

3. Slide filters out of unit.
4. Clean coil using a commercial coil cleaner or dishwasher

detergent in a pressurized spray canister. Wash both sides
of coil and flush with clean water. For best results, back-
flush toward return-air section to remove foreign mate-
rial.

5. Flush condensate pan after completion.
6. Reinstall economizer and filters.
7. Reconnect wiring.
8. Replace access panels.
CONDENSER COILS — Inspect coils monthly. Clean con-
denser coils annually, and as required by location and outdoor-
air conditions.
Clean 2-row coils as follows:
1. Turn off unit power.
2. Remove top panel screws on condenser end of unit.
3. Remove condenser coil corner post. See Fig. 30 and 31.

To hold top panel open, place coil corner post between
top panel and center post. See Fig. 32 and 33.

4. Remove device holding coil sections together at return

end of condenser coil. Carefully separate the outer coil
section 3 to 4 in. from the inner coil section. See Fig. 34
and 35.

5. Use a water hose or other suitable equipment to flush down

between the 2 coil sections to remove dirt and debris. Clean
the outer surfaces with a stiff brush in the normal manner.

6. Secure the sections together. Reposition the coil sections,

and remove the coil corner post from between the top
panel and center post. Install the coil corner post and coil
center post, and replace all screws.

CONDENSATE DRAIN — Check and clean each year at
start of cooling season. In winter, keep drain dry or protect
against freeze-up.

FILTERS — Clean or replace at start of each heating and
cooling season, or more often if operating conditions require
it. Replacement filters must be same dimensions as original
filters.

OUTDOOR-AIR INLET SCREEN(S) — Clean screen(s) with
steam or hot water and a mild detergent. Do not use dis-
posable filters in place of screens.

27

Содержание 50GJ006

Страница 1: ...e air To minimize the possibility of moisture con tamination to the refrigerant system a special 100 molecu lar sieve filter drier is used Refrigerant R 407C must always be charged liquid Charg ing ga...

Страница 2: ...E BOTTOM UNIT SIZE A ROOF CURB ACCESSORY 50GJ006 18 29 356 CRRFCURB001A00 28 09 610 CRRFCURB002A00 NOTES 1 Roof curb accessory is shipped unassembled 2 Insulated panels 3 Dimensions in are in millimet...

Страница 3: ...BOTTOM 11 49 NPT 1 29 NPT CRBTMPWR00A200 THRU THE BOTTOM UNIT SIZE A ROOF CURB ACCESSORY 50GJ008 012 18 29 356 CRRFCURB003A00 28 09 610 CRRFCURB004A00 NOTES 1 Roof curb accessory is shipped unassembl...

Страница 4: ...external trap can be com pleted after the unit is in place All units must have an external trap for condensate drain age Install a trap at least 4 in deep and protect against freeze up See Fig 4 If d...

Страница 5: ...n top skid when rigging to prevent rigging straps from damaging unit 3 Unit weights do not include economizer See Table 1 for econo mizer weights All panels must be in place when rigging 50GJ OPERATIN...

Страница 6: ...pm 2100 2100 2100 Motor Pulley Pitch Diameter A B in 2 4 3 4 3 4 4 4 4 0 5 0 Nominal Motor Shaft Diameter in 7 8 7 8 7 8 Fan Pulley Pitch Diameter in 4 0 7 0 8 0 Belt Qty Type Length in 1 A 40 1 A 51...

Страница 7: ...on horizontal discharge units with electric heat 1 in clearance to duct work for 1 ft b Condenser coil for proper airflow 36 in one side 12 in the other The side getting the greater clearance is optio...

Страница 8: ...iction may prevail a Bottom to combustible surfaces when not using curb 0 in on horizontal discharge units with electric heat 1 in clearance to ductwork for 1 ft b Condenser coil for proper airflow 36...

Страница 9: ...8 230 3 60 50GJ008 012 460 3 60 LEGEND C Contactor COMP S Compressors IFC Indoor Evaporator Fan Contactor NEC National Electrical Code OFC Outdoor Condenser Fan Contactor Terminal Block Field Wiring F...

Страница 10: ...ithin 10 Use the formula shown in Tables 2A and 2B Note 2 on page 11 to determine the percentage of voltage imbalance Operation on improper line voltage or excessive phase imbalance con stitutes abuse...

Страница 11: ...4 8 16 5 27 8 33 0 41 7 50 0 19 8 33 4 39 7 50 2 60 1 31 4 33 6 50 5 58 4 71 4 68 9 35 35 60 60 80 90 33 33 46 54 66 77 172 575 3 60 518 632 7 9 50 0 0 7 4 8 17 0 34 0 51 0 17 1 34 1 51 2 24 9 28 9 50...

Страница 12: ...Refer to Fig 6A and 6B for drilling holes in basepan HEAT ANTICIPATOR SETTINGS For 50GJ006 units set first stage heat anticipator setting at 0 8 and set second stage heat anticipator setting at 0 3 Fo...

Страница 13: ...horizontal discharge block off plate over the opening on the access panel Block off plate MUST be installed before installing hood assembly See Fig 16 7 Insert economizer plug into economizer harness...

Страница 14: ...LIEF DAMPER ECONOMIZER MOUNTING SCREWS ECONOMIZER MOTOR Fig 14 Varislide Economizer Installed in Unit ECONOMIZER MOTOR ECONOMIZER CONTROL BOARD WIRING HARNESS Fig 15 Horizontal Varislide Economizer In...

Страница 15: ...ide Economizer Minimum Position Damper Setting MINIMUM POSITIO N OPEN 3 1 T P P1 T1 4 2 5 S S O D C TR B REV B 1 9 8 8 1 8 A H U M I D I T Y 90 70 60 30 10 D C B A 60 65 70 75 55 50 85 80 DAMPER DAMPE...

Страница 16: ...ogic module T and T1 should be disconnected during adjustment b The 2 potentiometers with slots for adjustment are located on the face of the economizer logic module Turn the lower potentiometer fully...

Страница 17: ...d in Unit CONTROL CURVE CONTROL POINT APPROX DEG AT 50 RH A 73 23 B 70 21 C 67 19 D 63 17 Fig 23 Enthalpy Settings for PARABLADE Economizer Fig 24 Panels Reinstalled on Unit Fig 25 Outdoor Air Hood In...

Страница 18: ...flange toward fixed flange to increase speed or away from fixed flange to decrease speed Increasing fan speed increases load on motor Do not exceed maxi mum speed specified in Table 1 5 Set movable fl...

Страница 19: ...260 1 57 1330 1 78 2400 1107 1 24 1145 1 32 1222 1 52 1296 1 73 1365 1 94 2500 1150 1 39 1186 1 48 1262 1 68 1331 1 89 1400 2 12 2600 1193 1 56 1228 1 65 1301 1 86 1367 2 07 1435 2 31 2700 1237 1 74 1...

Страница 20: ...VE MOTOR cont External Static Pressure in wg 1 4 1 6 1 8 2 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 2250 884 1 97 937 2 33 947 2 66 1022 3 10 2300 885 2 00 939 2 36 979 2 69 1025 3 12 2400 892 2 08 944 2 40...

Страница 21: ...988 1 91 995 1 95 3100 892 1 78 947 2 00 995 2 05 1008 2 07 3200 899 1 85 951 2 06 1000 2 17 1021 2 20 3300 907 1 93 959 2 10 1004 2 33 1036 2 36 3400 915 2 01 966 2 17 1009 2 46 1043 2 47 3500 924 2...

Страница 22: ...1359 1 60 1800 1178 1 14 1249 1 32 1316 1 52 1382 1 72 1900 1201 1 23 1274 1 43 1338 1 62 1402 1 83 2000 1226 1 33 1297 1 53 1363 1 73 1424 1 94 2100 1252 1 45 1320 1 64 1388 1 85 1448 2 07 2200 1280...

Страница 23: ...888 2 24 903 2 55 911 2 85 2400 824 1 72 872 2 01 909 2 32 931 2 64 935 2 96 2500 832 1 79 882 2 09 925 2 40 955 2 72 972 3 06 2550 836 1 83 887 2 13 931 2 45 964 2 77 986 3 11 2660 839 1 87 891 2 17...

Страница 24: ...3400 853 1 71 899 1 93 951 2 17 995 2 17 1008 2 32 3500 862 1 78 907 2 01 959 2 24 1000 2 33 1021 2 47 3600 871 1 86 915 2 09 965 2 32 1005 2 46 1036 2 59 3700 879 1 95 927 2 17 973 2 38 1013 2 57 10...

Страница 25: ...ed in accordance with these installation instructions and applicable codes Operating Parameters The maximum outdoor entering air temperature is 115 F The minimum entering outdoor air temperature is 45...

Страница 26: ...y air tempera ture is above 57 F the damper continues to open until it reaches the fully open position or until the supply air temperature drops below 52 F When the supply air temperature falls betwee...

Страница 27: ...HEATING 50GJ008 012 UNITS WITH ECONOMIZER If Accessory Heater is Installed When the room thermostat calls for heat through terminal W1 the evaporator fan con tactor and heater contactor no 1 are energ...

Страница 28: ...er Coil 50GJ006 Fig 31 Cleaning Condenser Coil 50GJ008 012 Fig 32 Propping Up Top Panel 50GJ006 Fig 33 Propping Up Top Panel 50GJ008 012 Fig 34 Separating Coil Sections 50GJ006 Fig 35 Separating Coil...

Страница 29: ...ns Accurate pressure gage and tem perature sens ing device are required Units charged with R 407C must use dedicated hoses and pressure gages Connect the pres sure gage to the service port on the suct...

Страница 30: ...Fig 37 Cooling Charging Chart 50GJ006 Fig 38 Cooling Charging Charts 50GJ008 30...

Страница 31: ...Fig 39 Cooling Charging Charts 50GJ012 31...

Страница 32: ...ant system Locate restriction and remove Compressor operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermostat set too low Reset ther...

Страница 33: ...and EC settings and the economizer control board wiring are correct check to ensure that the 24 vac terminal of the SAT has 24 vac white wire If OAT EC and control board are functioning and wired pro...

Страница 34: ...ot close No power to economizer 1 Disconnect power at TR and TR1 Disconnect jumper across P and P1 2 Connect jumper across TR and 1 3 Connect jumper across T1 and T 4 If connected remove enthalpy sens...

Страница 35: ......

Страница 36: ...TAGE L1 L2 L2 L3 L3 L1 CIRCUIT 1 COMPRESSOR AMPS L1 L2 L3 CIRCUIT 2 COMPRESSOR AMPS L1 L2 L3 INDOOR EVAPORATOR FAN AMPS L1 L2 L3 TEMPERATURES OUTDOOR AIR TEMPERATURE DB RETURN AIR TEMPERATURE DB WB CO...

Отзывы: