Table 4 — Evaporator-Fan Motor Data
UNIT
50GJ
MAXIMUM
CONTINUOUS
BHP*
MAXIMUM
OPERATING
WATTS*
UNIT
VOLTAGE
MAXIMUM
AMP
DRAW
006
1.80
2162
208/230
6.4
460
2.9
575
2.9
008
2.90
2615
208/230
7.9
460
3.6
575
3.6
012
4.20
3775
208/230
11.7
460
5.3
575
5.3
LEGEND
BHP — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be used with
confidence. Using the fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure.
Unit warranty will not be affected.
Table 5 — Fan Rpm at Motor Pulley Settings*
UNIT
50GJ
MOTOR PULLEY TURNS OPEN
0
1
⁄
2
1
1
1
⁄
2
2
2
1
⁄
2
3
3
1
⁄
2
4
4
1
⁄
2
5
5
1
⁄
2
6
006
1460
1425
1385
1350
1315
1275
1240
1205
1165
1130
1095
1055
1020
008
1085
1060
1035
1010
985
960
935
910
890
865
840
—
—
012
1080
1060
1035
1015
990
970
950
925
905
880
860
—
—
*Approximate fan rpm shown.
Table 6 — Fan Performance − 50GJ006 Vertical Discharge Units
BELT DRIVE MOTOR
Airflow
(Cfm)
External Static Pressure (in. wg)
0.1
0.2
0.4
0.6
0.8
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1500
711
0.33
769
0.39
878
0.51
971
0.64
1052
0.78
1600
751
0.39
806
0.45
906
0.58
1004
0.73
1087
0.88
1700
791
0.46
846
0.53
941
0.66
1030
0.80
1112
0.96
1800
852
0.55
905
0.62
1002
0.78
1084
0.93
1163
1.10
1900
894
0.64
945
0.72
1037
0.88
1119
1.04
1194
1.21
2000
936
0.74
984
0.82
1072
0.98
1154
1.16
1226
1.33
2100
978
0.85
1024
0.93
1108
1.10
1190
1.29
1259
1.47
2200
1021
0.97
1064
1.05
1145
1.22
1225
1.43
1294
1.62
2300
1064
1.10
1104
1.18
1183
1.36
1260
1.57
1330
1.78
2400
1107
1.24
1145
1.32
1222
1.52
1296
1.73
1365
1.94
2500
1150
1.39
1186
1.48
1262
1.68
1331
1.89
1400
2.12
2600
1193
1.56
1228
1.65
1301
1.86
1367
2.07
1435
2.31
2700
1237
1.74
1269
1.83
1341
2.05
1404
2.26
1471
2.51
BELT DRIVE MOTOR (cont)
Airflow
(Cfm)
External Static Pressure (in. wg)
1.0
1.2
1.4
1.6
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1500
1134
0.95
1213
1.11
1276
1.38
1331
1.49
1600
1159
1.02
1231
1.20
1311
1.39
1395
1.59
1700
1184
1.12
1258
1.30
1322
1.49
1403
1.69
1800
1235
1.29
1303
1.48
1371
1.69
1433
1.90
1900
1266
1.40
1330
1.59
1396
1.81
1460
2.03
2000
1297
1.53
1362
1.73
1422
1.94
1485
2.16
2100
1327
1.66
1393
1.87
1452
2.08
1510
2.31
2200
1359
1.81
1423
2.02
1483
2.24
1538
2.46
2300
1392
1.97
1454
2.18
1515
2.41
1569
2.64
2400
1426
2.15
1485
2.36
1544
2.59
1601
2.84
2500
1461
2.34
1518
2.55
1575
2.78
—
—
2600
1497
2.54
1552
2.76
—
—
—
—
2700
1532
2.75
—
—
—
—
—
—
LEGEND
Bhp — Brake Horsepower Input to Fan
NOTES:
1. Boldface indicates a field-supplied drive is required. (See
Note 6.)
2.
Indicates field-supplied motor and drive are required.
3. Maximum continuous bhp is 1.80. Extensive motor and electrical
testing on these units ensures that the full range of the motor can
be utilized with confidence. Using your fan motors up to the
ratings shown will not result in nuisance tripping or premature mo-
tor failure. Unit warranty will not be affected. For additional infor-
mation on motor performance, refer to Table 4 on page 19.
4. Values include losses for filters, unit casing, and wet coils.
5. Use of a field-supplied motor may affect wire sizing. Contact
Carrier representative to verify.
6. Standard motor drive range: 1020 to 1460 rpm. All other rpms re-
quire field-supplied drive.
7. Interpolation is permissible. Do not extrapolate.
19
Содержание 50GJ006
Страница 30: ...Fig 37 Cooling Charging Chart 50GJ006 Fig 38 Cooling Charging Charts 50GJ008 30...
Страница 31: ...Fig 39 Cooling Charging Charts 50GJ012 31...