Table 9 — Fan Performance — 50GJ006 Horizontal Discharge Units
BELT DRIVE MOTOR
Airflow
(Cfm)
External Static Pressure (in. wg)
0.1
0.2
0.4
0.6
0.8
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1500
665
0.31
729
0.35
843
0.47
940
0.60
1026
0.74
1600
703
0.36
763
0.40
872
0.53
965
0.66
1049
0.81
1700
741
0.40
801
0.47
902
0.60
993
0.75
1077
0.89
1800
765
0.45
821
0.51
923
0.65
1019
0.81
1099
0.96
1900
802
0.45
854
0.58
953
0.73
1046
0.90
1126
1.06
2000
840
0.60
888
0.66
984
0.82
1073
0.99
1154
1.16
2100
878
0.69
923
0.75
1015
0.91
1101
1.08
1182
1.27
2200
916
0.78
958
0.85
1046
1.01
1129
1.19
1209
1.39
2300
954
0.89
993
0.96
1079
1.13
1160
1.31
1237
1.51
2400
993
1.00
1029
1.07
1112
1.25
1190
1.43
1264
1.63
2500
1031
1.13
1066
1.20
1145
1.39
1220
1.57
1292
1.77
2600
1070
1.26
1103
1.34
1179
1.52
1251
1.71
1322
1.92
2700
1109
1.41
1140
1.48
1212
1.67
1283
1.87
1352
2.09
BELT DRIVE MOTOR (cont)
Airflow
(Cfm)
External Static Pressure (in. wg)
1.0
1.2
1.4
1.6
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1500
1108
0.89
1187
1.06
1202
1.18
1079
1.10
1600
1130
0.97
1206
1.14
1275
1.32
1281
1.44
1700
1152
1.05
1226
1.23
1298
1.41
1359
1.60
1800
1178
1.14
1249
1.32
1316
1.52
1382
1.72
1900
1201
1.23
1274
1.43
1338
1.62
1402
1.83
2000
1226
1.33
1297
1.53
1363
1.73
1424
1.94
2100
1252
1.45
1320
1.64
1388
1.85
1448
2.07
2200
1280
1.58
1345
1.77
1410
1.97
1473
2.20
2300
1309
1.71
1372
1.91
1434
2.11
1496
2.34
2400
1336
1.85
1400
2.06
1459
2.26
1519
2.48
2500
1363
2.00
1428
2.22
1486
2.43
1543
2.65
2600
1390
2.15
1456
2.38
1514
2.61
1569
2.83
2700
1418
2.31
1483
2.56
1543
2.80
—
—
LEGEND
Bhp — Brake Horsepower Input to Fan
NOTES:
1. Boldface indicates a field-supplied drive is required. (See
Note 6.)
2.
Indicates field-supplied motor and drive are required.
3. Maximum continuous bhp is 1.80. Extensive motor and electrical
testing on these units ensures that the full range of the motor can
be utilized with confidence. Using your fan motors up to the
ratings shown will not result in nuisance tripping or premature mo-
tor failure. Unit warranty will not be affected. For additional infor-
mation on motor performance, refer to Table 4 on page 19.
4. Values include losses for filters, unit casing, and wet coils.
5. Use of a field-supplied motor may affect wire sizing. Contact
Carrier representative to verify.
6. Standard motor drive range: 1020 to 1460 rpm. All other rpms re-
quire field-supplied drive.
7. Interpolation is permissible. Do not extrapolate.