59
12 - FACTORY OPTIONS AND ACCESSORIES
Gas connection
Use the gas line connections only with EC certi
fi
ed components.
The PCH module is supplied complete with a dual gas valve, gas
stabiliser and
fi
lter. All components are
fi
tted inside the burner
housing.
To complete the installation, as required by current standards, an
anti-vibration joint and a gas valve must be
fi
tted.
Note: A EN216 certi
fi
ed gas
fi
lter with
fi
ltration level lower or equal
to 50 micron must be used, with no pressure stabiliser, a wide
range gas
fi
lter must be used since the
fi
lter supplied as standard,
upstream of the gas valve, has a limited area.
If the burner is not going to be used over a prolonged
period the gas supply valve must be closed.
Important:
For a correct maintenance, connect the PCH module
by means of a seal and swivel gasket. Avoid using threaded
connected directly on the gas connection.
During the installation, tighten the external gas supply pipe but
without exceeding the tightening torque of 150 Nm.
Important:
It is strictly prohibited to supply gas to the circuit with
pressure higher than 60 mbar. Such pressures could cause the
valve to break.
If pressure are higher than 60 mbar, a pressure reducer must be
installed at least 10 m away and no pressure stabiliser must be
fi
tted between the pressure reducer and the heater, but leaving
the gas
fi
lter.
Key:
1. Main burner gas solenoid valve
2. Pilot burner gas solenoid valve
3. Pressure stabiliser:
4. Safety gas solenoid valve
5. Gas
fi
lter (small section)
6. Anti-vibration joint
7. Gas
fi
lter (large section)
8. Gas valve
Gas
type
Gas settings
PCH020
PCH034
PCH045
PCH065
PCH080
PCH105
min. max. min. max. min. max. min. max. min. max. min. max.
G20
Cat. E-H
Air supply pressure
mbar
20 [min 17-max 25]
Ø pilot nozzle
mm
0,7
Gas consumption (15°C-1013mbar) m3/h
0,51
2,01
0,80 3,69
0,90
4,44
1,31
6,88
1,74
8,68
2,22 10,58
Carbon dioxide - CO
2
content
%
8,8
9,1
8,7
9,1
8,7
9,1
8,7
9,1
8,7
9,1
8,5
9,1
Fumes temperature
ºC
39
113
31
94
30
94
31
86
26,5
70
28
80
Fume mass
fl
ow rate (max.)
kg/h
31
57
72
107
135
165
Gas butter
fl
y valve
mm
5,8
7,4
7,5
11,0
12,2
15,8
G25
Cat.
L-LL
Air supply pressure
mbar
25 [min 17-max 30] (20 for Germany)
Ø pilot nozzle
mm
0,7 (0,75 for Germany)
Gas consumption (15°C-1013mbar) m3/h
0,59
2,34
0,93
4,29
1,05
5,17
1,53
8,00
2,02
10,1
2,21
12,30
Carbon dioxide - CO
2
content
%
8,8
9,0
8,6
9,0
8,8
8,9
8,8
9,2
8,6
8,9
8,8
9,0
Fumes temperature
ºC
39
113
31
94
30
94
31
86
26
70
28
80
Fume mass
fl
ow rate (max.)
kg/h
--
Gas butter
fl
y valve
mm
7,4
8,9
8,9
Not necessary Not necessary Not necessary
G30
Cat.
3B-P
Air supply pressure
mbar
30 [min 25-max 35] - 50 [min 42,5-max 57,5]
Ø pilot nozzle
mm
0,51
Gas consumption (15°C-1013mbar) m3/h
0,40
1,58
0,63 2,90
0,71
3,49
1,03
5,39
1,49
6,80
1,70
8,30
Carbon dioxide - CO
2
content
%
10,8
11,4
10,8 11,5 10,8
10,9 10,7
11,3
10,1
10,3
10,4
10,6
Fumes temperature
ºC
39
113
31
94
30
94
31
86
26,5
70
28
80
Fume mass
fl
ow rate (max.)
kg/h
--
Gas butter
fl
y valve
mm
3,7
5,0
5,2
6,5
7,0
9,3
G31
Cat. 3P
Air supply pressure
mbar
30 [min 25-max 35] - 37 [min 25-max 45] - 50 [min 42,5-max 57,5]
Ø pilot nozzle
mm
0,51
Gas consumption (15°C-1013mbar) m3/h
0,39
1,55
0,62 2,85
0,70 3,43
1,01
5,31
1,34
6,70
1,47
8,18
Carbon dioxide - CO
2
content
%
9,3
9.,8
9,2
9,7
9,3
9,4
9,4
9,6
9,3
9,6
9,5
9,8
Fumes temperature
ºC
39
113
31
94
30
94
31
86
26,5
70
28
80
Fume mass
fl
ow rate (max.)
kg/h
24
45
58
84
107
130
Gas butter
fl
y valve
mm
3,7
5,0
5,2
6,5
7,0
9,3
1
2
3
4
5
6
7
8
Included in the burner module
To be carried out
by the installer
Gas supply:
Ø 3/4’’
Gas settings data for GAS G25.3 - Cat. K (Netherlands), G25.1 - Cat. S (Hungary), G2.350 - Cat. Ls (Poland) and G27 - Cat. Lw [ex GZ41.5] (Poland)
can be found in the manufacturer’s installation and maintenance manual (APENGROUP), supplied with the unit.