50
Economizer
2 Position Damper
Unit Without Economizer or
2 Position Damper
C10645
Fig. 76 -- EconoMi$er
t
IV Wiring
Step 13 — Adjust Factory--Installed Options
EconoMi$er IV Occupancy Switch —
Refer to Fig. 76 for general EconoMi$er IV wiring.
External occupancy control is managed through a
connection on the Central Terminal Board.
If external occupancy control is desired, connect a time
clock or remotely controlled switch (closed for Occupied,
open for Unoccupied sequence) at terminals marked
OCCUPANCY on CTB. Remove or cut jumper JMP 2 to
complete the installation.
Step 14 — Install Accessories
Available accessories include:
Roof Curb
Thru--base connection kit (must be installed before unit
is set on curb)
LP conversion kit
Manual outside air damper
High Altitude Gas kits
Low Ambient Controls
Thermostat / Sensors
Two--Position motorized outside air damper
EconoMi$er2 (without control/for external signal and
integrated barometric relief)
EconoMi$er IV (with control and integrated barometric
relief)
Power Exhaust
Differential dry--bulb sensor (EconoMi$er IV)
Outdoor enthalpy sensor
Differential enthalpy sensor
CO
2
sensor
DDC interface (PremierLink)
Louvered hail guard
Phase monitor control
Winter Start kit
Refer to separate installation instructions for information
on installing these accessories.
Pre--Start and Start--Up
This completes the mechanical installation of the unit.
Refer to the unit’s Service and Maintenance manual for
detailed Pre--Start and Start--up instructions.
48H
C
Содержание 48TC*D
Страница 3: ...3 C10896 Fig 1 Unit Dimensional Drawing 17 Size Unit 48HC...
Страница 4: ...4 C10897 Fig 1 Unit Dimensional Drawing 17 Size Unit cont 48HC...
Страница 5: ...5 C10892 Fig 2 Unit Dimensional Drawing 20 and 24 Size Units 48HC...
Страница 6: ...6 C10893 Fig 2 Unit Dimensional Drawing 20 and 24 Size Units cont 48HC...
Страница 7: ...7 C10900 Fig 3 Unit Dimensional Drawing 28 Size Unit 48HC...
Страница 8: ...8 C10901 Fig 3 Unit Dimensional Drawing 28 Size Unit cont 48HC...
Страница 11: ...11 C10954 Fig 6 Roof Curb Details 17 Size Unit 48HC...
Страница 12: ...12 C10955 Fig 7 Roof Curb Details 20 and 24 Size Units 48HC...
Страница 13: ...13 C10956 Fig 8 Roof Curb Details 28 Size Unit 48HC...
Страница 27: ...27 C11140 Fig 38 PremierLink Wiring Schematic 48HC...
Страница 28: ...28 C11141 Fig 39 PremierLink Wiring Schematic with Humidi MiZerR 48HC...
Страница 37: ...37 C11142 Fig 58 RTU Open System Control Wiring Diagram 48HC...
Страница 38: ...38 C11143 Fig 59 RTU Open System Control Wiring Diagram with Humidi MiZerR 48HC...
Страница 51: ...51 48HC...