
23
C
W2
G
W1
R
Y1
Typical
Thermostat
Corrections
O/B/Y2
(see Note)
Note: Typical multi-function marking. Follow manufacturer’s configuration
instructions to select Y2.
Field Wiring
Central
Terminal
Board
W1
Y2
Y1
R
W2
G
C
X
W1
Y2
Y1
R
W2
G
C
X
T–STAT
See
Caution
UNIT DAMAGE HAZARD
Failure to follow this caution may cause a short circuit.
CAUTION
!
Carefully check the connection of control coductor
for indoor fan control at terminal G. Connecting the
indoor fan lead to terminal C will cause a short circuit
condition which can cause component damage inside
the unit or at thermostat.
C10731
Fig. 30 -- Typical Low--Voltage Control Connections
NOTE
: If utilizing the through the base connections,
route the low voltage wire through the wire ties to the
central terminal board.
Rubber
Grommet
Corner
Post
Wire
Ties
Thru the Base
Connection
C10734
Fig. 31 -- Field Control Wiring Raceway
Heat Anticipator Settings —
Set heat anticipator settings at 0.14 amp for the first stage
and 0.14 amp for second--stage heating.
Transformer Connection for 208--v Power Supply —
All units except 208/230-v units are factory wired for the
voltage shown on the nameplate.
If the 208/230-v unit is
to be connected to a 208-v power supply, the control
transformer must be rewired by moving the black wire
with the
1
/
4
-in. female spade connector from the 230--v
connection and moving it to the 208-v
1
/
4
-in. male
terminal on the primary side of the transformer.
Refer to
unit label diagram for additional information.
48H
C
Содержание 48TC*D
Страница 3: ...3 C10896 Fig 1 Unit Dimensional Drawing 17 Size Unit 48HC...
Страница 4: ...4 C10897 Fig 1 Unit Dimensional Drawing 17 Size Unit cont 48HC...
Страница 5: ...5 C10892 Fig 2 Unit Dimensional Drawing 20 and 24 Size Units 48HC...
Страница 6: ...6 C10893 Fig 2 Unit Dimensional Drawing 20 and 24 Size Units cont 48HC...
Страница 7: ...7 C10900 Fig 3 Unit Dimensional Drawing 28 Size Unit 48HC...
Страница 8: ...8 C10901 Fig 3 Unit Dimensional Drawing 28 Size Unit cont 48HC...
Страница 11: ...11 C10954 Fig 6 Roof Curb Details 17 Size Unit 48HC...
Страница 12: ...12 C10955 Fig 7 Roof Curb Details 20 and 24 Size Units 48HC...
Страница 13: ...13 C10956 Fig 8 Roof Curb Details 28 Size Unit 48HC...
Страница 27: ...27 C11140 Fig 38 PremierLink Wiring Schematic 48HC...
Страница 28: ...28 C11141 Fig 39 PremierLink Wiring Schematic with Humidi MiZerR 48HC...
Страница 37: ...37 C11142 Fig 58 RTU Open System Control Wiring Diagram 48HC...
Страница 38: ...38 C11143 Fig 59 RTU Open System Control Wiring Diagram with Humidi MiZerR 48HC...
Страница 51: ...51 48HC...