42
Relative Humidity Sensor
(Polarized Male Connector)
J4-1 or J4-4 + 24 VDC Supply Voltage
J4-2 or J4-5 (-) 4 to 20 mA Current Loop Output
to RTU-OPEN
4-20 VAC GND 0-5V
mA or or
VDC 0-10V
SPAN
ZERO
C10839
Fig. 66 -- Duct Relative Humidity Sensor Typical Wiring
Humidistat:
The accessory humidistat provides the RTU
Open insight to the relative humidity in the space. The
humidistat reads the RH level in the space and compares it
to its setpoint to operate a dry contact. The humidistat is a
dedicated input on the configurable input 9 and tells the
RTU Open when the RH level is HIGH or LOW. The
normal condition for humidity is LOW. A normally open
humidistat is the factory default control for the
Humidi--MiZer
R
option.
To wire in the field:
S
J5--8 = 24 VAC source for dry contact
S
J5--7 = Signal input
Smoke Detector/Fire Shutdown (FSD) —
On 48HC units equipped with factory--installed Smoke
Detector(s), the smoke detector controller implements the
unit shutdown through its NC contact set connected to the
unit’s CTB input. The FSD function is initiated via the
smoke detector’s Alarm NO contact set. The RTU Open
controller communicates the smoke detector’s tripped status
to the BAS building control. See Figs. 58 and 59, the RTU
Open wiring schematics.
The
Fire
Shutdown
Switch
configuration,
MENU
→
Config
→
Inputs
→
input
5
,
identifies
the
normally open status of this input when there is no fire
alarm.
Connecting Discrete Inputs —
Filter Status:
The filter status accessory is a
field--installed accessory. This accessory detects plugged
filters. When installing this accessory, the unit must be
configured
for
filter
status
by
setting
MENU
→
Config
→
Inputs
→
input 3, 5, 8, or 9
to Filter
Status and normally open (N/O) or normally closed (N/C).
Input 8 or 9 is recommended for easy of installation. Refer
to Fig. 57 and Fig. 58 or 59 for wire terminations at J5.
Fan Status:
The fan status accessory is a field--installed
accessory. This accessory detects when the indoor fan is
blowing air. When installing this accessory, the unit must
be
configured
for
fan
status
by
setting
MENU
→
Config
→
Inputs
→
input 3, 5, 8, or 9
to Fan
Status and normally open (N/O) or normally closed (N/C).
Input 8 or 9 is recommended for easy of installation. Refer
to Fig. 57 and Fig. 58 or 59 for wire terminations at J5.
Remote Occupancy:
The remote occupancy accessory is
a field--installed accessory. This accessory overrides the
unoccupied mode and puts the unit in occupied mode.
When installing this accessory, the unit must be
configured
for
remote
occupancy
by
setting
MENU
→
Config
→
Inputs
→
input 3, 5, 8, or 9
to Remote
Occupancy and normally open (N/O) or normally closed
(N/C).
Also set
MENU
→
Schedules
→
occupancy source
to DI
on/off. Input 8 or 9 is recommended for easy of
installation. Refer to Fig. 57 and Table 9 for wire
terminations at J5.
Power Exhaust (output):
The relay used by the RTU
Open board to control power exhaust is a dry contact
which means it does not have 24vac. This 24vac must be
connected to the relay to allow it to operate the power
exhaust relay in the PE accessory. A 24vac source must be
provided to J11--2 on the RTU Open control board. This
can be provided by the unit’s transformer from various
sources. The “R” terminal on the unit’s low voltage
terminal board (LVTB) is a logical source. Refer to Fig.
57 and Fig. 58 or 59 for wire terminations at J11.
48H
C
Содержание 48TC*D
Страница 3: ...3 C10896 Fig 1 Unit Dimensional Drawing 17 Size Unit 48HC...
Страница 4: ...4 C10897 Fig 1 Unit Dimensional Drawing 17 Size Unit cont 48HC...
Страница 5: ...5 C10892 Fig 2 Unit Dimensional Drawing 20 and 24 Size Units 48HC...
Страница 6: ...6 C10893 Fig 2 Unit Dimensional Drawing 20 and 24 Size Units cont 48HC...
Страница 7: ...7 C10900 Fig 3 Unit Dimensional Drawing 28 Size Unit 48HC...
Страница 8: ...8 C10901 Fig 3 Unit Dimensional Drawing 28 Size Unit cont 48HC...
Страница 11: ...11 C10954 Fig 6 Roof Curb Details 17 Size Unit 48HC...
Страница 12: ...12 C10955 Fig 7 Roof Curb Details 20 and 24 Size Units 48HC...
Страница 13: ...13 C10956 Fig 8 Roof Curb Details 28 Size Unit 48HC...
Страница 27: ...27 C11140 Fig 38 PremierLink Wiring Schematic 48HC...
Страница 28: ...28 C11141 Fig 39 PremierLink Wiring Schematic with Humidi MiZerR 48HC...
Страница 37: ...37 C11142 Fig 58 RTU Open System Control Wiring Diagram 48HC...
Страница 38: ...38 C11143 Fig 59 RTU Open System Control Wiring Diagram with Humidi MiZerR 48HC...
Страница 51: ...51 48HC...