45
Table 10 – LEDs
The LEDs on the RTU Open Control Board (see Fig. 57) show the status of certain functions:
If this LED is on...
Status is...
Power
RTU Open has power
Rx
RTU Open is receiving data from the network segment
Tx
RTU Open is transmitting data over the network segment
DO#
The digital output is active
The
Run
and
Error
LEDs indicate control module and network status
If Run LED shows...
And Error LED shows...
Status is...
2 flashes per second
Off
Normal
2 flashes per second
2 flashes,
alternating with
Run
LED
Five minute auto---restart delay after system error
2 flashes per second
3 flashes,
then off
Control module has just been formatted
2 flashes per second
4 flashes,
then pause
Two or more devices on this network have the
same ARC156 network address
2 flashes per second
On
Exec halted after frequent system errors or
control programs halted
5 flashes per second
On
Exec start---up aborted, Boot is running
5 flashes per second
Off
Firmware transfer in progress, Boot is running
7 flashes per second
7 flashes per second, alternating with
Run
LED
Ten second recovery period after brownout
14 flashes per second
14 flashes per second,
alternating with
Run
LED
Brownout
On
On
Failure. Try the following solutions:
S
Turn RTU Open off, then on.
S
Format RTU Open.
S
Download memory to RTU Open.
S
Replace RTU Open.
NOTE
:
Refer to Catalog No. 48--50HCTQ--01T for
complete configuration of RTU Open, operating sequences
and troubleshooting information. Refer to
RTU Open
Controller Integration Guide
(Catalog No. 11--808--428--01)
for details on configuration and troubleshooting of connected
networks. Have a copy of these manuals available at unit
start--up.
Outdoor Air Enthalpy Control
(PNO 33CSENTHSW)
The enthalpy control (33CSENTHSW) is available as a
field--installed accessory to be used with the EconoMi$er2
damper system. The outdoor air enthalpy sensor is part of
the enthalpy control. (The separate field--installed
accessory return air enthalpy sensor (33CSENTSEN) is
required for differential enthalpy control. See Fig. 71.)
Locate the enthalpy control in the economizer next to the
Actuator Motor. Locate two GRA leads in the factory
harness and connect the gray lead labeled “ESL” to the
terminal labeled “LOW”. See Fig. 71. Connect the
enthalpy control power input terminals to economizer
actuator power leads RED (connect to 24V) and BLK
(connect to GND).
7
CTB ECON
(P’LINK: to J4-2) or
(RTU Open: to J2-6)
LOW
GND
24V
Enthalpy
Switch
GRA
BLK
RED
Factory Wiring Harness
PL6-1 (24-V)
PL6-4 (COM)
C11160
Fig. 71 -- Enthalpy Switch (33CSENTHSW) Connections
The outdoor enthalpy changeover setpoint is set at the
enthalpy controller.
Differential Enthalpy Control —
Differential enthalpy control is provided by sensing and
comparing the outside air and return air enthalpy
conditions. Install the outdoor air enthalpy control as
described above. Add and install a return air enthalpy
sensor (see Fig. 72).
48H
C
Содержание 48TC*D
Страница 3: ...3 C10896 Fig 1 Unit Dimensional Drawing 17 Size Unit 48HC...
Страница 4: ...4 C10897 Fig 1 Unit Dimensional Drawing 17 Size Unit cont 48HC...
Страница 5: ...5 C10892 Fig 2 Unit Dimensional Drawing 20 and 24 Size Units 48HC...
Страница 6: ...6 C10893 Fig 2 Unit Dimensional Drawing 20 and 24 Size Units cont 48HC...
Страница 7: ...7 C10900 Fig 3 Unit Dimensional Drawing 28 Size Unit 48HC...
Страница 8: ...8 C10901 Fig 3 Unit Dimensional Drawing 28 Size Unit cont 48HC...
Страница 11: ...11 C10954 Fig 6 Roof Curb Details 17 Size Unit 48HC...
Страница 12: ...12 C10955 Fig 7 Roof Curb Details 20 and 24 Size Units 48HC...
Страница 13: ...13 C10956 Fig 8 Roof Curb Details 28 Size Unit 48HC...
Страница 27: ...27 C11140 Fig 38 PremierLink Wiring Schematic 48HC...
Страница 28: ...28 C11141 Fig 39 PremierLink Wiring Schematic with Humidi MiZerR 48HC...
Страница 37: ...37 C11142 Fig 58 RTU Open System Control Wiring Diagram 48HC...
Страница 38: ...38 C11143 Fig 59 RTU Open System Control Wiring Diagram with Humidi MiZerR 48HC...
Страница 51: ...51 48HC...