84
timeclock function in place of the jumper between TR and
N. When the timeclock contacts are closed, the
EconoMi$er IV control will be in occupied mode. When
the timeclock contacts are open (removing the 24V signal
from terminal N), the EconoMi$er IV will be in
unoccupied mode.
Demand Control Ventilation (DCV)
When using the EconoMi$er IV for demand controlled
ventilation, there are some equipment selection criteria
which should be considered. When selecting the heat
capacity and cool capacity of the equipment, the
maximum ventilation rate must be evaluated for design
conditions. The maximum damper position must be
calculated to provide the desired fresh air.
Typically the maximum ventilation rate will be about 5 to
10% more than the typical cfm required per person, using
normal outside air design criteria.
A proportional anticipatory strategy should be taken with
the following conditions: a zone with a large area, varied
occupancy, and equipment that cannot exceed the required
ventilation rate at design conditions. Exceeding the
required ventilation rate means the equipment can
condition air at a maximum ventilation rate that is greater
than the required ventilation rate for maximum
occupancy. A proportional-anticipatory strategy will cause
the fresh air supplied to increase as the room CO
2
level
increases even though the CO
2
setpoint has not been
reached. By the time the CO
2
level reaches the setpoint,
the damper will be at maximum ventilation and should
maintain the setpoint.
In order to have the CO
2
sensor control the economizer
damper in this manner, first determine the damper voltage
output for minimum or base ventilation. Base ventilation
is the ventilation required to remove contaminants during
unoccupied periods. The following equation may be used
to determine the percent of outside air entering the
building for a given damper position. For best results there
should be at least a 10 degree difference in outside and
return-air temperatures.
(T
O x
OA
) + (TR
x
RA
) =T
M
100
100
T
O
= Outdoor-Air Temperature
OA = Percent of Outdoor Air
T
R
= Return-Air Temperature
RA = Percent of Return Air
T
M
= Mixed-Air Temperature
Once base ventilation has been determined, set the
minimum damper position potentiometer to the correct
position.
The same equation can be used to determine the occupied
or maximum ventilation rate to the building. For example,
an output of 3.6 volts to the actuator provides a base
ventilation rate of 5% and an output of 6.7 volts provides
the maximum ventilation rate of 20% (or base plus 15 cfm
per person). Use Fig. 93 to determine the maximum
setting of the CO
2
sensor. For example, an 1100 ppm
setpoint relates to a 15 cfm per person design. Use the
1100 ppm curve on Fig. 93 to find the point when the CO
2
sensor output will be 6.7 volts. Line up the point on the
graph with the left side of the chart to determine that the
range configuration for the CO
2
sensor should be 1800
ppm. The EconoMi$er IV controller will output the 6.7
volts from the CO
2
sensor to the actuator when the CO
2
concentration in the space is at 1100 ppm. The DCV
setpoint may be left at 2 volts since the CO
2
sensor
voltage will be ignored by the EconoMi$er IV controller
until it rises above the 3.6 volt setting of the minimum
position potentiometer.
Once the fully occupied damper position has been
determined, set the maximum damper demand control
ventilation potentiometer to this position. Do not set to the
maximum position as this can result in over-ventilation to
the space and potential high humidity levels.
CO
2
Sensor Configuration
The CO
2
sensor has preset standard voltage settings that
can be selected anytime after the sensor is powered up.
Use setting 1 or 2 for Carrier equipment.
1. Press Clear and Mode buttons. Hold at least 5
seconds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
Table 37 – EconoMi$er IV Sensor Usage
APPLICATION
ECONOMI$ER IV WITH OUTDOOR AIR DRY
BULB SENSOR
Accessories Required
Outdoor Air
Dry Bulb
None. The outdoor air dry bulb sensor is
factory installed.
Differential
Dry Bulb
CRTEMPSN002A00*
Single Enthalpy
HH57AC078
Differential
Enthalpy
HH57AC078 and CRENTDIF004A00*
CO
2
for DCV
Control using a
Wall-Mounted
CO
2
Sensor
33ZCSENCO2
CO
2
for DCV
Control using a
Duct-Mounted
CO
2
Sensor
33ZCSENCO2† and
33ZCASPCO2**
O
R CRCBDIOX005A00††
* CRENTDIF004A00 and CRTEMPSN002A00 accessories are
used on many different base units. As such, these kits may
contain parts that will not be needed for installation.
† 33ZCSENCO2 is an accessory CO
2
sensor.
** 33ZCASPCO2 is an accessory aspirator box required for duct-
mounted applications.
†† CRCBDIOX005A00 is an accessory that contains both
33ZCSENCO2 and 33ZCASPCO2 accessories.
3. Use the Up/Down button to select the preset number.
4. Press Enter to lock in the selection.
5. Press Mode to exit and resume normal operation.
The custom settings of the CO
2
sensor can be changed
anytime after the sensor is energized. Follow the steps
below to change the non-standard settings:
1. Press Clear and Mode buttons. Hold at least 5
seconds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to toggle to the NONSTD
menu and press Enter.
48TC
Содержание 48TC 04 Series
Страница 27: ...27 COOLING CHARGING CHARTS cont C14064 Fig 33 Cooling Charging Charts 12 5 Ton 48TC...
Страница 28: ...28 COOLING CHARGING CHARTS cont C13217 Fig 34 Charging Chart 48TC Size D14 with Novation Coil 48TC...
Страница 29: ...29 COOLING CHARGING CHARTS cont C13218 Fig 35 Charging Chart 48TC Size D16 48TC...
Страница 30: ...30 COOLING CHARGING CHARTS cont C10666 Fig 36 Charging Chart 48TC Size B04 Humidi MiZer in Reheat 1 48TC...
Страница 31: ...31 COOLING CHARGING CHARTS cont C10667 Fig 37 Charging Chart 48TC Size B05 Humidi MiZer in Reheat 1 48TC...
Страница 32: ...32 COOLING CHARGING CHARTS cont C10668 Fig 38 Charging Chart 48TC Size B06 Humidi MiZer in Reheat 1 48TC...
Страница 33: ...33 COOLING CHARGING CHARTS cont C10669 Fig 39 Charging Chart 48TC Size B07 Humidi MiZer in Reheat 1 48TC...
Страница 40: ...40 C14052 Fig 51 Typical Smoke Detector System Wiring 48TC...
Страница 114: ...114 APPENDIX III WIRING DIAGRAMS C14065 Fig 95 48TC A08 A12 Control Diagram 208 230 3 60 460 3 60 575 3 60 48TC...
Страница 115: ...115 APPENDIX III WIRING DIAGRAMS C13240 Fig 96 48TC D08 D12 Control Diagram 208 230 3 60 460 3 60 575 3 60 48TC...
Страница 116: ...116 APPENDIX III WIRING DIAGRAMS C13241 Fig 97 48TC D14 Control Diagram 208 230 3 60 460 3 60 575 3 60 48TC...
Страница 117: ...117 APPENDIX III WIRING DIAGRAM LIST C12412 Fig 98 48TC D16 Control Diagram 208 230 3 60 460 575 3 60 48TC...
Страница 122: ...122 APPENDIX III WIRING DIAGRAMS C12413 Fig 103 48TC A04 A07 Power Diagram 208 230 1 60 48TC...
Страница 123: ...123 APPENDIX III WIRING DIAGRAMS C12414 Fig 104 48TC A04 A07 Power Diagram 208 230 3 60 460 3 60 48TC...
Страница 124: ...124 APPENDIX III WIRING DIAGRAM LIST C12415 Fig 105 48TC A04 A07 Power Diagram 575 3 60 48TC...
Страница 125: ...125 APPENDIX III WIRING DIAGRAMS C13245 Fig 106 48TC A08 A12 Power Diagram 208 230 3 60 460 3 60 48TC...
Страница 126: ...126 APPENDIX III WIRING DIAGRAM LIST C13246 Fig 107 48TC A08 A12 Power Diagram 575 3 60 48TC...
Страница 127: ...127 APPENDIX III WIRING DIAGRAMS C13484 Fig 108 48TC D08 D12 Power Diagram 208 230 3 60 460 3 60 48TC...
Страница 128: ...128 APPENDIX III WIRING DIAGRAM LIST C13247 Fig 109 48TC D08 D12 Power Diagram 575 3 60 48TC...
Страница 129: ...129 APPENDIX III WIRING DIAGRAMS C13248 Fig 110 48TC D14 Power Diagram 208 230 3 60 460 3 60 48TC...
Страница 130: ...130 APPENDIX III WIRING DIAGRAM LIST C13249 Fig 111 48TC D14 Power Diagram 575 3 60 48TC...
Страница 131: ...131 APPENDIX III WIRING DIAGRAMS C12428 Fig 112 48TC B04 B07 Power Diagram 208 230 1 60 with Humidi MiZert 48TC...
Страница 133: ...133 APPENDIX III WIRING DIAGRAM LIST C12430 Fig 114 48TC B04 B07 Power Diagram 575 3 60 with Humidi MiZert 48TC...
Страница 134: ...134 APPENDIX III WIRING DIAGRAMS C12432 Fig 115 48TC E08 E12 Power Diagram 208 230 3 30 460 3 60 with Humidi MiZert 48TC...
Страница 135: ...135 APPENDIX III WIRING DIAGRAM LIST C12433 Fig 116 48TC E08 E12 Power Diagram 575 3 60 with Humidi MiZert 48TC...
Страница 136: ...136 APPENDIX III WIRING DIAGRAMS C12434 Fig 117 48TC E14 Power Diagram 208 230 3 60 460 3 60 with Humidi MiZert 48TC...
Страница 137: ...137 APPENDIX III WIRING DIAGRAM LIST C12435 Fig 118 48TC E14 Power Diagram 575 3 60 with Humidi MiZert 48TC...
Страница 138: ...138 APPENDIX III WIRING DIAGRAM LIST C12422 Fig 119 48TC D16 Power Diagram 208 230 3 60 460 3 60 48TC...
Страница 139: ...139 APPENDIX III WIRING DIAGRAMS C12423 Fig 120 48TC D16 Power Diagram 575 3 60 48TC...
Страница 140: ...140 APPENDIX III WIRING DIAGRAM LIST C12436 Fig 121 48TC E16 Power Diagram 208 230 3 60 460 3 60 with Humidi MiZert 48TC...
Страница 141: ...141 APPENDIX III WIRING DIAGRAMS C12437 Fig 122 48TC E16 Power Diagram 575 3 60 with Humidi MiZert 48TC...
Страница 142: ...142 APPENDIX III WIRING DIAGRAM LIST C14063 Fig 123 48TC A04 12 D08 14 PremierLink Control Diagram 48TC...
Страница 143: ...143 APPENDIX III WIRING DIAGRAM LIST C13485 Fig 124 48TC 16 PremierLink Control Diagram 48TC...
Страница 145: ...145 APPENDIX III WIRING DIAGRAM LIST C13487 Fig 126 48TC 16 RTU Open Control Diagram 48TC...
Страница 146: ...146 APPENDIX III WIRING DIAGRAM LIST C14124 Fig 127 48TC D08 14 E08 14 W7220 2 Speed IFM 48TC...
Страница 147: ...147 APPENDIX III WIRING DIAGRAM LIST C13489 Fig 128 48TC D16 E16 W7220 2 Speed IFM Control Diagram 48TC...
Страница 148: ...148 APPENDIX III WIRING DIAGRAMS C14062 Fig 129 48TC E 14 Control Diagram 208 230 3 60 460 3 60 575 3 60 48TC...