![Carrier 48TC 04 Series Скачать руководство пользователя страница 50](http://html1.mh-extra.com/html/carrier/48tc-04-series/48tc-04-series_service-and-maintenance-instructions_2563286050.webp)
50
125,000/90,000 BTUH INPUT
180,000/120,000 BTUH INPUT
240,000/180,000 BTUH INPUT
250,000/200,000 BTUH INPUT
C08447
Fig. 66 -- Spark Adjustment (08--14)
5. If factory orifice has been removed, check that each
orifice is tight at its threads into the manifold pipe
and that orifice projection does not exceed maximum
valve. See Fig. 62.
6. Reinstall burners on rack in the same locations as
factory--installed. (The outside crossover flame re-
gions of the outermost burners are pinched off to pre-
vent excessive gas flow from the side of the burner
assembly. If the pinched crossovers are installed
between two burners, the flame will not ignite prop-
erly.)
7. Reinstall burner rack as described in Removal and
Replacement of Gas Train section, above.
Gas Valve —
All three--phase models (except Low NOx)
are equipped with 2--stage gas valves. Single--phase
models and all Low NOx models are equipped with
single--stage gas valves. See Fig. 68 for locations of
adjustment screws and features on the gas valves.
To adjust gas valve pressure settings:
IMPORTANT
: Leak check all gas connections including
the main service connection, gas valve, gas spuds, and
manifold pipe plug. All leaks must be repaired before
firing unit.
Check Unit Operation and Make Necessary Adjust-
ments
NOTE
: Gas supply pressure at gas valve inlet must be
within specified ranges for fuel type and unit size. See
Table 17 and Table 19.
1. Remove manifold pressure tap plug from manifold
and connect pressure gauge or manometer. See Fig.
63.
2. Turn on electrical supply.
3. Turn on unit main gas valve.
4. Set room thermostat to call for heat. If unit has two--
stage gas valve, verify high--stage heat operation be-
fore attempting to adjust manifold pressure.
5. When main burners ignite, check all fittings, mani-
fold, and orifices for leaks.
6. Adjust high--stage pressure to specified setting by
turning the plastic adjustment screw clockwise to in-
crease pressure, counter--clockwise to decrease pres-
sure.
7.
For Two--Stage Gas Valves
set room thermostat to
call for low--stage heat. Adjust low--stage pressure to
specified setting.
8. Replace regulator cover screw(s) when finished.
9. With burner access panel removed, observe unit
heating operation in both high stage and low stage
operation if so equipped. Observe burner flames to
see if they are blue in appearance, and that the flames
are approximately the same for each burner.
10. Turn off unit, remove pressure manometer and re-
place the 1/8 in. pipe fitting on the gas manifold. See
Fig. 63.
Limit Switch
Remove blower access panel. Limit switch is located on
the fan deck. See Fig. 56.
Burner Ignition
Unit is equipped with a direct spark ignition 100% lockout
system. Integrated Gas Unit Controller (IGC) is located in
the control box. See Fig. 64. The IGC contains a
self--diagnostic LED (light--emitting diode). A single LED
(see Fig. 69) on the IGC provides a visual display of
operational or sequential problems when the power supply
is uninterrupted.
When a break in power occurs, the IGC will be reset
(resulting in a loss of fault history) and the indoor
(evaporator) fan ON/OFF times will be reset. The LED
error code can be observed through the viewport. During
servicing refer to the label on the control box cover or
Table 14 for an explanation of LED error code
descriptions.
If lockout occurs, unit can be reset by interrupting power
supply to unit for at least 5 seconds.
48TC
Содержание 48TC 04 Series
Страница 27: ...27 COOLING CHARGING CHARTS cont C14064 Fig 33 Cooling Charging Charts 12 5 Ton 48TC...
Страница 28: ...28 COOLING CHARGING CHARTS cont C13217 Fig 34 Charging Chart 48TC Size D14 with Novation Coil 48TC...
Страница 29: ...29 COOLING CHARGING CHARTS cont C13218 Fig 35 Charging Chart 48TC Size D16 48TC...
Страница 30: ...30 COOLING CHARGING CHARTS cont C10666 Fig 36 Charging Chart 48TC Size B04 Humidi MiZer in Reheat 1 48TC...
Страница 31: ...31 COOLING CHARGING CHARTS cont C10667 Fig 37 Charging Chart 48TC Size B05 Humidi MiZer in Reheat 1 48TC...
Страница 32: ...32 COOLING CHARGING CHARTS cont C10668 Fig 38 Charging Chart 48TC Size B06 Humidi MiZer in Reheat 1 48TC...
Страница 33: ...33 COOLING CHARGING CHARTS cont C10669 Fig 39 Charging Chart 48TC Size B07 Humidi MiZer in Reheat 1 48TC...
Страница 40: ...40 C14052 Fig 51 Typical Smoke Detector System Wiring 48TC...
Страница 114: ...114 APPENDIX III WIRING DIAGRAMS C14065 Fig 95 48TC A08 A12 Control Diagram 208 230 3 60 460 3 60 575 3 60 48TC...
Страница 115: ...115 APPENDIX III WIRING DIAGRAMS C13240 Fig 96 48TC D08 D12 Control Diagram 208 230 3 60 460 3 60 575 3 60 48TC...
Страница 116: ...116 APPENDIX III WIRING DIAGRAMS C13241 Fig 97 48TC D14 Control Diagram 208 230 3 60 460 3 60 575 3 60 48TC...
Страница 117: ...117 APPENDIX III WIRING DIAGRAM LIST C12412 Fig 98 48TC D16 Control Diagram 208 230 3 60 460 575 3 60 48TC...
Страница 122: ...122 APPENDIX III WIRING DIAGRAMS C12413 Fig 103 48TC A04 A07 Power Diagram 208 230 1 60 48TC...
Страница 123: ...123 APPENDIX III WIRING DIAGRAMS C12414 Fig 104 48TC A04 A07 Power Diagram 208 230 3 60 460 3 60 48TC...
Страница 124: ...124 APPENDIX III WIRING DIAGRAM LIST C12415 Fig 105 48TC A04 A07 Power Diagram 575 3 60 48TC...
Страница 125: ...125 APPENDIX III WIRING DIAGRAMS C13245 Fig 106 48TC A08 A12 Power Diagram 208 230 3 60 460 3 60 48TC...
Страница 126: ...126 APPENDIX III WIRING DIAGRAM LIST C13246 Fig 107 48TC A08 A12 Power Diagram 575 3 60 48TC...
Страница 127: ...127 APPENDIX III WIRING DIAGRAMS C13484 Fig 108 48TC D08 D12 Power Diagram 208 230 3 60 460 3 60 48TC...
Страница 128: ...128 APPENDIX III WIRING DIAGRAM LIST C13247 Fig 109 48TC D08 D12 Power Diagram 575 3 60 48TC...
Страница 129: ...129 APPENDIX III WIRING DIAGRAMS C13248 Fig 110 48TC D14 Power Diagram 208 230 3 60 460 3 60 48TC...
Страница 130: ...130 APPENDIX III WIRING DIAGRAM LIST C13249 Fig 111 48TC D14 Power Diagram 575 3 60 48TC...
Страница 131: ...131 APPENDIX III WIRING DIAGRAMS C12428 Fig 112 48TC B04 B07 Power Diagram 208 230 1 60 with Humidi MiZert 48TC...
Страница 133: ...133 APPENDIX III WIRING DIAGRAM LIST C12430 Fig 114 48TC B04 B07 Power Diagram 575 3 60 with Humidi MiZert 48TC...
Страница 134: ...134 APPENDIX III WIRING DIAGRAMS C12432 Fig 115 48TC E08 E12 Power Diagram 208 230 3 30 460 3 60 with Humidi MiZert 48TC...
Страница 135: ...135 APPENDIX III WIRING DIAGRAM LIST C12433 Fig 116 48TC E08 E12 Power Diagram 575 3 60 with Humidi MiZert 48TC...
Страница 136: ...136 APPENDIX III WIRING DIAGRAMS C12434 Fig 117 48TC E14 Power Diagram 208 230 3 60 460 3 60 with Humidi MiZert 48TC...
Страница 137: ...137 APPENDIX III WIRING DIAGRAM LIST C12435 Fig 118 48TC E14 Power Diagram 575 3 60 with Humidi MiZert 48TC...
Страница 138: ...138 APPENDIX III WIRING DIAGRAM LIST C12422 Fig 119 48TC D16 Power Diagram 208 230 3 60 460 3 60 48TC...
Страница 139: ...139 APPENDIX III WIRING DIAGRAMS C12423 Fig 120 48TC D16 Power Diagram 575 3 60 48TC...
Страница 140: ...140 APPENDIX III WIRING DIAGRAM LIST C12436 Fig 121 48TC E16 Power Diagram 208 230 3 60 460 3 60 with Humidi MiZert 48TC...
Страница 141: ...141 APPENDIX III WIRING DIAGRAMS C12437 Fig 122 48TC E16 Power Diagram 575 3 60 with Humidi MiZert 48TC...
Страница 142: ...142 APPENDIX III WIRING DIAGRAM LIST C14063 Fig 123 48TC A04 12 D08 14 PremierLink Control Diagram 48TC...
Страница 143: ...143 APPENDIX III WIRING DIAGRAM LIST C13485 Fig 124 48TC 16 PremierLink Control Diagram 48TC...
Страница 145: ...145 APPENDIX III WIRING DIAGRAM LIST C13487 Fig 126 48TC 16 RTU Open Control Diagram 48TC...
Страница 146: ...146 APPENDIX III WIRING DIAGRAM LIST C14124 Fig 127 48TC D08 14 E08 14 W7220 2 Speed IFM 48TC...
Страница 147: ...147 APPENDIX III WIRING DIAGRAM LIST C13489 Fig 128 48TC D16 E16 W7220 2 Speed IFM Control Diagram 48TC...
Страница 148: ...148 APPENDIX III WIRING DIAGRAMS C14062 Fig 129 48TC E 14 Control Diagram 208 230 3 60 460 3 60 575 3 60 48TC...