43
INDICATORS
Normal State
The smoke detector operates in the normal state in the
absence of any trouble conditions and when its sensing
chamber is free of smoke. In the normal state, the Power
LED on both the sensor and the controller are on and all
other LEDs are off.
Alarm State
The smoke detector enters the alarm state when the
amount of smoke particulate in the sensor’s sensing
chamber exceeds the alarm threshold value. See Table 8.
Upon entering the alarm state:
S
The sensor’s Alarm LED and the controller’s Alarm
LED turn on.
S
The contacts on the controller’s two auxiliary relays
switch positions.
S
The contacts on the controller’s alarm initiation relay
close.
S
The controller’s remote alarm LED output is activated
(turned on).
S
The controller’s high impedance multiple fan shutdown
control line is pulled to ground Trouble state.
The SuperDuct duct smoke detector enters the trouble
state under the following conditions:
S
A sensor’s cover is removed and 20 minutes pass before
it is properly secured.
S
A sensor’s environmental compensation limit is reached
(100% dirty).
S
A wiring fault between a sensor and the controller is
detected.
An internal sensor fault is detected upon entering the
trouble state:
S
The contacts on the controller’s supervisory relay
switch positions. See Fig. 54.
S
If a sensor trouble, the sensor’s Trouble LED the
controller’s Trouble LED turn on.
S
If 100% dirty, the sensor’s Dirty LED turns on and the
controller’s Trouble LED flashes continuously.
S
If a wiring fault between a sensor and the controller, the
controller’s Trouble LED turns on but not the sensor’s.
ALARM
POWER
TEST/RESET
SWITCH
TROUBLE
C07298
Fig. 54 -- Controller Assembly
NOTE
:
All troubles are latched by the duct smoke
detector. The trouble condition must be cleared and then
the duct smoke detector must be reset in order to restore it
to the normal state.
Resetting Alarm and Trouble Condition Trips:
Manual reset is required to restore smoke detector systems
to Normal operation. For installations using two sensors,
the duct smoke detector does not differentiate which
sensor signals an alarm or trouble condition. Check each
sensor for Alarm or Trouble status (indicated by LED).
Clear the condition that has generated the trip at this
sensor. Then reset the sensor by pressing and holding the
reset button (on the side) for 2 seconds. Verify that the
sensor’s Alarm and Trouble LEDs are now off. At the
controller, clear its Alarm or Trouble state by pressing and
holding the manual reset button (on the front cover) for 2
seconds. Verify that the controller’s Alarm and Trouble
LEDs are now off. Replace all panels.
Troubleshooting
Controller’s Trouble LED is On
1. Check the Trouble LED on each sensor connected to
the controller. If a sensor’s Trouble LED is on, de-
termine the cause and make the necessary repairs.
2. Check the wiring between the sensor and the con-
troller. If wiring is loose or missing, repair or replace
as required.
Table 8 – Detector Indicators
CONTROL OR INDICATOR
DESCRIPTION
Magnetic test/reset switch
Resets the sensor when it is in the alarm or trouble state. Activates or tests the sensor when it is in
the normal state.
Alarm LED
Indicates the sensor is in the alarm state.
Trouble LED
Indicates the sensor is in the trouble state.
Dirty LED
Indicates the amount of environmental compensation used by the sensor
(flashing continuously = 100%)
Power LED
Indicates the sensor is energized.
48TC
Содержание 48TC 04 Series
Страница 27: ...27 COOLING CHARGING CHARTS cont C14064 Fig 33 Cooling Charging Charts 12 5 Ton 48TC...
Страница 28: ...28 COOLING CHARGING CHARTS cont C13217 Fig 34 Charging Chart 48TC Size D14 with Novation Coil 48TC...
Страница 29: ...29 COOLING CHARGING CHARTS cont C13218 Fig 35 Charging Chart 48TC Size D16 48TC...
Страница 30: ...30 COOLING CHARGING CHARTS cont C10666 Fig 36 Charging Chart 48TC Size B04 Humidi MiZer in Reheat 1 48TC...
Страница 31: ...31 COOLING CHARGING CHARTS cont C10667 Fig 37 Charging Chart 48TC Size B05 Humidi MiZer in Reheat 1 48TC...
Страница 32: ...32 COOLING CHARGING CHARTS cont C10668 Fig 38 Charging Chart 48TC Size B06 Humidi MiZer in Reheat 1 48TC...
Страница 33: ...33 COOLING CHARGING CHARTS cont C10669 Fig 39 Charging Chart 48TC Size B07 Humidi MiZer in Reheat 1 48TC...
Страница 40: ...40 C14052 Fig 51 Typical Smoke Detector System Wiring 48TC...
Страница 114: ...114 APPENDIX III WIRING DIAGRAMS C14065 Fig 95 48TC A08 A12 Control Diagram 208 230 3 60 460 3 60 575 3 60 48TC...
Страница 115: ...115 APPENDIX III WIRING DIAGRAMS C13240 Fig 96 48TC D08 D12 Control Diagram 208 230 3 60 460 3 60 575 3 60 48TC...
Страница 116: ...116 APPENDIX III WIRING DIAGRAMS C13241 Fig 97 48TC D14 Control Diagram 208 230 3 60 460 3 60 575 3 60 48TC...
Страница 117: ...117 APPENDIX III WIRING DIAGRAM LIST C12412 Fig 98 48TC D16 Control Diagram 208 230 3 60 460 575 3 60 48TC...
Страница 122: ...122 APPENDIX III WIRING DIAGRAMS C12413 Fig 103 48TC A04 A07 Power Diagram 208 230 1 60 48TC...
Страница 123: ...123 APPENDIX III WIRING DIAGRAMS C12414 Fig 104 48TC A04 A07 Power Diagram 208 230 3 60 460 3 60 48TC...
Страница 124: ...124 APPENDIX III WIRING DIAGRAM LIST C12415 Fig 105 48TC A04 A07 Power Diagram 575 3 60 48TC...
Страница 125: ...125 APPENDIX III WIRING DIAGRAMS C13245 Fig 106 48TC A08 A12 Power Diagram 208 230 3 60 460 3 60 48TC...
Страница 126: ...126 APPENDIX III WIRING DIAGRAM LIST C13246 Fig 107 48TC A08 A12 Power Diagram 575 3 60 48TC...
Страница 127: ...127 APPENDIX III WIRING DIAGRAMS C13484 Fig 108 48TC D08 D12 Power Diagram 208 230 3 60 460 3 60 48TC...
Страница 128: ...128 APPENDIX III WIRING DIAGRAM LIST C13247 Fig 109 48TC D08 D12 Power Diagram 575 3 60 48TC...
Страница 129: ...129 APPENDIX III WIRING DIAGRAMS C13248 Fig 110 48TC D14 Power Diagram 208 230 3 60 460 3 60 48TC...
Страница 130: ...130 APPENDIX III WIRING DIAGRAM LIST C13249 Fig 111 48TC D14 Power Diagram 575 3 60 48TC...
Страница 131: ...131 APPENDIX III WIRING DIAGRAMS C12428 Fig 112 48TC B04 B07 Power Diagram 208 230 1 60 with Humidi MiZert 48TC...
Страница 133: ...133 APPENDIX III WIRING DIAGRAM LIST C12430 Fig 114 48TC B04 B07 Power Diagram 575 3 60 with Humidi MiZert 48TC...
Страница 134: ...134 APPENDIX III WIRING DIAGRAMS C12432 Fig 115 48TC E08 E12 Power Diagram 208 230 3 30 460 3 60 with Humidi MiZert 48TC...
Страница 135: ...135 APPENDIX III WIRING DIAGRAM LIST C12433 Fig 116 48TC E08 E12 Power Diagram 575 3 60 with Humidi MiZert 48TC...
Страница 136: ...136 APPENDIX III WIRING DIAGRAMS C12434 Fig 117 48TC E14 Power Diagram 208 230 3 60 460 3 60 with Humidi MiZert 48TC...
Страница 137: ...137 APPENDIX III WIRING DIAGRAM LIST C12435 Fig 118 48TC E14 Power Diagram 575 3 60 with Humidi MiZert 48TC...
Страница 138: ...138 APPENDIX III WIRING DIAGRAM LIST C12422 Fig 119 48TC D16 Power Diagram 208 230 3 60 460 3 60 48TC...
Страница 139: ...139 APPENDIX III WIRING DIAGRAMS C12423 Fig 120 48TC D16 Power Diagram 575 3 60 48TC...
Страница 140: ...140 APPENDIX III WIRING DIAGRAM LIST C12436 Fig 121 48TC E16 Power Diagram 208 230 3 60 460 3 60 with Humidi MiZert 48TC...
Страница 141: ...141 APPENDIX III WIRING DIAGRAMS C12437 Fig 122 48TC E16 Power Diagram 575 3 60 with Humidi MiZert 48TC...
Страница 142: ...142 APPENDIX III WIRING DIAGRAM LIST C14063 Fig 123 48TC A04 12 D08 14 PremierLink Control Diagram 48TC...
Страница 143: ...143 APPENDIX III WIRING DIAGRAM LIST C13485 Fig 124 48TC 16 PremierLink Control Diagram 48TC...
Страница 145: ...145 APPENDIX III WIRING DIAGRAM LIST C13487 Fig 126 48TC 16 RTU Open Control Diagram 48TC...
Страница 146: ...146 APPENDIX III WIRING DIAGRAM LIST C14124 Fig 127 48TC D08 14 E08 14 W7220 2 Speed IFM 48TC...
Страница 147: ...147 APPENDIX III WIRING DIAGRAM LIST C13489 Fig 128 48TC D16 E16 W7220 2 Speed IFM Control Diagram 48TC...
Страница 148: ...148 APPENDIX III WIRING DIAGRAMS C14062 Fig 129 48TC E 14 Control Diagram 208 230 3 60 460 3 60 575 3 60 48TC...