17
Low--Charge Cooling
Unit charging charts are used to diagnose and correct
incomplete (undercharged) conditions (and overcharged
conditions). The unit charging chart specific to this unit is
attached to the unit’s compressor access panel.
Model 48TC units use two types of charging charts; one
type for Base Cooling systems and a different type for
most units equipped with Humidi--MiZer systems. Check
your unit’s info plate to confirm this unit’s Model Number
and value in Position 6. A Position 6 value of A or D
indicates a unit with a base cooling system; see section
below for information on using these charts. A Position 6
value of B or E indicates a unit with Humidi--MiZer
system; skip to the Humidi--MiZer section below for
information on charging these systems.
SIZE DESIGNATION
NOMINAL TONS
REFERENCE
04
3
05
4
06
5
07
6
08
7.5
09
8.5
12
10
14
12.5
16
15
EXAMPLE:
Model 48TC*A04
Outdoor Temperature
85
_
F (29
_
C)
. . . . . . . . . . . . . . . . . .
Suction Pressure
140 psig (965 kPa)
. . . . . . . . . . . . . . . . .
Suction Temperature should be
60
_
F (16
_
C)
. . . . . . . . . .
Units with Base Cooling Systems (Position 6 =
A or D)
Charging charts for base cooling units (using Acutrol
refrigerant metering devices) are based on charging the
units to the correct superheat for the various operating
conditions. See Tables 2--4 for unit specific charging chart
figures.
NOTE
: Unit size D14 has two charging charts, based on
outdoor coil type installed in this unit. Check the unit
infoplate for the value in Position 11, then select the
appropriate figures in Table 3.
Accurate pressure gauge and temperature sensing meter(s)
are required. Connect the pressure gauge to the service
port on the suction line. Mount one temperature sensing
device on the suction line and insulate it so that outdoor
ambient temperature does not affect the reading. Locate
the second temperature device (thermometer or meter
second channel sensor) in front of the largest face on the
outdoor coil to measure entering air temperature.
Indoor--air flowrate (cfm) must be within the normal
operating range of the unit. If a Motormaster head
pressure control is on the unit, the output must be
jumpered to provide full speed operation on all outdoor
fans.
READING THE CHART (EXAMPLE):
Model 48TC*A04
Outdoor Temperature
85
_
F (29
_
C)
. . . . . . . . . . . . . .
Suction Pressure
140psig (965 kPa
. . . . . . . . . . . . . .
Suction Temperature should be
60
_
F (16
_
C)
. . . . .
Using the Base Cooling Charging Charts
Read the suction pressure gauge; record the pressure.
Read the outdoor ambient temperature and the suction line
temperature. Refer to unit chart to determine what suction
temperature should be and compare to test reading. If the
test suction temperature is higher than the chart value, add
refrigerant. If test suction temperature is lower than chart
value, carefully recover some of the charge. Recheck the
suction pressure as charge is adjusted.
Alternate method: Plot the test suction temperature (using
the X--axis) and test suction pressure (using the Y--axis)
on the unit charging chart. Locate the curve for the
outdoor ambient temperature. If the plotted test condition
point is to the right/below the outdoor ambient
temperature curve, add refrigerant. If the plotted test
condition is to the left/above the outdoor ambient
temperature curve, carefully recover some of the charge.
Recheck the suction pressure as charge is adjusted.
Allow the unit to operate for approximately five minutes,
then recheck conditions against the charging chart. Repeat
the charge adjustment procedure until the plotted test
condition falls on the appropriate outdoor ambient
charging curve.
When charging procedure is completed, remove the
jumper on the Motormaster control if used.
Units with Humidi--Mizer Adaptive Dehumid-
ification System (Model Number Position 6 or
B or E)
Charging charts for Humidi--MiZer units except sizes
E08--E14 are based on charging the units to the correct
liquid temperature for the current discharge pressure
condition. Unit sizes E08--E14 use the Base Cooling unit
charging charts but with a modified procedure. See
instructions below. See Tables 4 (sizes 04--07) and Table
3 (sizes 08--16) for unit specific charging chart figures.
To Use the Cooling Charging Charts, Units
with Humidi--Mizer
NOTE
: 48TC units equipped with Humidi--MiZer option
include a Low Temperature Lockout temperature switch
(LTLO) that will prevent operation in Reheat1 or Reheat2
modes at outdoor temperature below 40
_
F (4.4
_
C). At
outdoor temperature below 40
_
F (4.4
_
C), perform charge
check using only Cooling mode operation and use the
standard cooling charging charts per Tables 2 and 3.
Return to site when the temperature is above 45
_
F
(7.2
_
C) to complete charge checks requiring unit
operation in Reheat1 or Reheat2 modes.
48TC
Содержание 48TC 04 Series
Страница 27: ...27 COOLING CHARGING CHARTS cont C14064 Fig 33 Cooling Charging Charts 12 5 Ton 48TC...
Страница 28: ...28 COOLING CHARGING CHARTS cont C13217 Fig 34 Charging Chart 48TC Size D14 with Novation Coil 48TC...
Страница 29: ...29 COOLING CHARGING CHARTS cont C13218 Fig 35 Charging Chart 48TC Size D16 48TC...
Страница 30: ...30 COOLING CHARGING CHARTS cont C10666 Fig 36 Charging Chart 48TC Size B04 Humidi MiZer in Reheat 1 48TC...
Страница 31: ...31 COOLING CHARGING CHARTS cont C10667 Fig 37 Charging Chart 48TC Size B05 Humidi MiZer in Reheat 1 48TC...
Страница 32: ...32 COOLING CHARGING CHARTS cont C10668 Fig 38 Charging Chart 48TC Size B06 Humidi MiZer in Reheat 1 48TC...
Страница 33: ...33 COOLING CHARGING CHARTS cont C10669 Fig 39 Charging Chart 48TC Size B07 Humidi MiZer in Reheat 1 48TC...
Страница 40: ...40 C14052 Fig 51 Typical Smoke Detector System Wiring 48TC...
Страница 114: ...114 APPENDIX III WIRING DIAGRAMS C14065 Fig 95 48TC A08 A12 Control Diagram 208 230 3 60 460 3 60 575 3 60 48TC...
Страница 115: ...115 APPENDIX III WIRING DIAGRAMS C13240 Fig 96 48TC D08 D12 Control Diagram 208 230 3 60 460 3 60 575 3 60 48TC...
Страница 116: ...116 APPENDIX III WIRING DIAGRAMS C13241 Fig 97 48TC D14 Control Diagram 208 230 3 60 460 3 60 575 3 60 48TC...
Страница 117: ...117 APPENDIX III WIRING DIAGRAM LIST C12412 Fig 98 48TC D16 Control Diagram 208 230 3 60 460 575 3 60 48TC...
Страница 122: ...122 APPENDIX III WIRING DIAGRAMS C12413 Fig 103 48TC A04 A07 Power Diagram 208 230 1 60 48TC...
Страница 123: ...123 APPENDIX III WIRING DIAGRAMS C12414 Fig 104 48TC A04 A07 Power Diagram 208 230 3 60 460 3 60 48TC...
Страница 124: ...124 APPENDIX III WIRING DIAGRAM LIST C12415 Fig 105 48TC A04 A07 Power Diagram 575 3 60 48TC...
Страница 125: ...125 APPENDIX III WIRING DIAGRAMS C13245 Fig 106 48TC A08 A12 Power Diagram 208 230 3 60 460 3 60 48TC...
Страница 126: ...126 APPENDIX III WIRING DIAGRAM LIST C13246 Fig 107 48TC A08 A12 Power Diagram 575 3 60 48TC...
Страница 127: ...127 APPENDIX III WIRING DIAGRAMS C13484 Fig 108 48TC D08 D12 Power Diagram 208 230 3 60 460 3 60 48TC...
Страница 128: ...128 APPENDIX III WIRING DIAGRAM LIST C13247 Fig 109 48TC D08 D12 Power Diagram 575 3 60 48TC...
Страница 129: ...129 APPENDIX III WIRING DIAGRAMS C13248 Fig 110 48TC D14 Power Diagram 208 230 3 60 460 3 60 48TC...
Страница 130: ...130 APPENDIX III WIRING DIAGRAM LIST C13249 Fig 111 48TC D14 Power Diagram 575 3 60 48TC...
Страница 131: ...131 APPENDIX III WIRING DIAGRAMS C12428 Fig 112 48TC B04 B07 Power Diagram 208 230 1 60 with Humidi MiZert 48TC...
Страница 133: ...133 APPENDIX III WIRING DIAGRAM LIST C12430 Fig 114 48TC B04 B07 Power Diagram 575 3 60 with Humidi MiZert 48TC...
Страница 134: ...134 APPENDIX III WIRING DIAGRAMS C12432 Fig 115 48TC E08 E12 Power Diagram 208 230 3 30 460 3 60 with Humidi MiZert 48TC...
Страница 135: ...135 APPENDIX III WIRING DIAGRAM LIST C12433 Fig 116 48TC E08 E12 Power Diagram 575 3 60 with Humidi MiZert 48TC...
Страница 136: ...136 APPENDIX III WIRING DIAGRAMS C12434 Fig 117 48TC E14 Power Diagram 208 230 3 60 460 3 60 with Humidi MiZert 48TC...
Страница 137: ...137 APPENDIX III WIRING DIAGRAM LIST C12435 Fig 118 48TC E14 Power Diagram 575 3 60 with Humidi MiZert 48TC...
Страница 138: ...138 APPENDIX III WIRING DIAGRAM LIST C12422 Fig 119 48TC D16 Power Diagram 208 230 3 60 460 3 60 48TC...
Страница 139: ...139 APPENDIX III WIRING DIAGRAMS C12423 Fig 120 48TC D16 Power Diagram 575 3 60 48TC...
Страница 140: ...140 APPENDIX III WIRING DIAGRAM LIST C12436 Fig 121 48TC E16 Power Diagram 208 230 3 60 460 3 60 with Humidi MiZert 48TC...
Страница 141: ...141 APPENDIX III WIRING DIAGRAMS C12437 Fig 122 48TC E16 Power Diagram 575 3 60 with Humidi MiZert 48TC...
Страница 142: ...142 APPENDIX III WIRING DIAGRAM LIST C14063 Fig 123 48TC A04 12 D08 14 PremierLink Control Diagram 48TC...
Страница 143: ...143 APPENDIX III WIRING DIAGRAM LIST C13485 Fig 124 48TC 16 PremierLink Control Diagram 48TC...
Страница 145: ...145 APPENDIX III WIRING DIAGRAM LIST C13487 Fig 126 48TC 16 RTU Open Control Diagram 48TC...
Страница 146: ...146 APPENDIX III WIRING DIAGRAM LIST C14124 Fig 127 48TC D08 14 E08 14 W7220 2 Speed IFM 48TC...
Страница 147: ...147 APPENDIX III WIRING DIAGRAM LIST C13489 Fig 128 48TC D16 E16 W7220 2 Speed IFM Control Diagram 48TC...
Страница 148: ...148 APPENDIX III WIRING DIAGRAMS C14062 Fig 129 48TC E 14 Control Diagram 208 230 3 60 460 3 60 575 3 60 48TC...