background image

Packaged rooftop units 

with integrated gas burner

17

-  When starting the compressors, check the subcooling and overheating 

and thus verify if the refrigerant load is appropriate 

to the operating conditions. To adjust the 

refrigerant load, a schrader valve is available on 

the liquid line.

-  Verify the absence of any leaks of the refrigerant.

-  Check the unit operation and verify the safety elements.

-  All the 48EN/EH models are 

equipped with scroll type 

compressors and have a phase 

control relay. Verify that they 

turn in the correct direction and, 

if not, reverse the power wires.

10. S

TARTING

 

THE

 

UNIT

R 410A

Operational checks

Check the unit operation by verifying the electronic control and the 

safety elements.

It is also recommendable to create a report, taking note of the date, 

which includes the following information: the nominal voltage, current 

absorbed by the compressors, fans and other electrical components, 

signifi cant temperatures in the cooling circuit (see table below) and 

other aspects considered interesting such as alarms detected by the 

electronic control of the unit. The recording of these parameters whilst 

the unit is running allows controlling the installation performance and 

it is the best possible way to avoid breakdowns since the analysis 

of these data makes early detection of anomalies possible or the 

provision of the necessary means available to ensure that they do 

not take place.

Possible problems at commissioning

All indications given in this brochure must be respected and 

complied with to guarantee a correct operation of the units.

Next, several possible operation problems are stated which could 

happen if the conditions of the commissioning are not appropriate.

- Air 

fl ow lack: very high differences between inlet and outlet, originated 

by a high pressure drop in the ducts, or by other causes that impede 

the correct air circulation.

-  Air recirculation in the unit, originated by some obstacle in the air 

aspiration or outlet.

-  Noise problems because of excessive air fl ow in the grille.

- Water overfl owing to the pan problems, originated by an excessive 

fl ow, an incorrect siphon installation or because a defective unit level.

-  Refrigerant circuit humidity problem, because of an incorrect vacuum 

realization.

Checks prior to commissioning

-  It is advisable to make a complete sketch of the installation including 

the location of the unit and all the components used. This will be very 

helpful for maintenance and repairs to the installation.

-  Check that the electrical power supply matches the unit voltage and 

that its value lies within acceptable limits.

-  It must also be verifi ed that the electric installation has been carried 

out according to the electric wiring diagram provided with the unit 

(consult the chapter on “Checking before commissioning”).

-  Once the above verifi cations have been carried out, the control 

circuit is supplied with voltage by the automatic control switch. It is 

necessary to leave with voltage the compressor crankcase heater 

for 24 hours before starting the compressor.

WICHTIG: WIEDERBEHEIZUNG DER

OLWANNE

IMPORTANT: CRANKCASE HEATING

IMPORTANT: SURCHAUFFE CARTER D’HUILE

IMPORTANTE: RISCALDARE IL CARTER

DELL’OLIO

IMPORTANTE: RECALENTAMIENTO DE

ACEITE DEL CÁRTER

KOENNEN.

TO ALLOW THE COMPRESSOR(S) STARTING

AU PREMIER DÉMARRAGE OU APRÈS UNE ABSCENCE

T E N S I O N   2 4   H E U R E S   A V A N T   D ’ A U T O R I S E R   L E
DÉMARRAGE DU(DES) COMPRESSEUR(S).

AL PRIMO AVVIAMENTO U DOPO UNA INTERRUZIONE
PROLUNGATA DELLA ALIMENTAZIONE ELETTRICA,
LASCIARE LA MACCINA SOTTO TENSIONE PER 24 ORE
PRIMA DI AUTORIZZARE L’AVVIAMENTO DEL(DEI)
COMPRESSORE(I).

ANTES DEL PRIMER ARRANQUE O DESPUÉS DE UNA
AUSENCIA DE CORRIENTE POR UN LARGO PERIODO DE
TIEMPO, CONVIENE QUE LA UNIDAD ESTÉ CONECTADA
UN MÍNIMO DE 24 HORAS.

BEIDER ERSTEN INBETRIEBSETRUNZ ORDER NACH EINER
LANGEN STROMUNTER-BRECHUNG BRINGEN SIE DIE
M A S C H I N E   U N T E R   S P A N N U N G   2 4   S T R U N D E R L A N G
BEVOR SIE DEN(DIE) KOMPRESSOR(EN) EINSCHALTEN

FOR THE FIRSTSTART OR AFTER ALONG TIME OUT OF
VOLTAGE PUT THE MACHINE ON LIVE 24 HOURS BEFORE

DE COURANT PROLONGÉE, METTRE LA MACHINE SOUS

COMPRESOR SCROLL.

COMPROBAR SENTIDO DE GIRO

COMPRESSEUR SCROLL.

VÉRIFIER LE SENS DE ROTATION

SCROLL COMPRESSOR.

CHECK SENSE OF ROTATION

COOLING mode

HEATING mode

Compressor

Suction pressure

bar

Compressor

Suction pressure

bar

Suction temp. (1)

ºC

Suction temp. (1)

ºC

Condens. pressure

bar

Condens. pressure

bar

Condens. temp. (2)

ºC

Condens. temp. (2)

ºC

Air 
condenser

Gas inlet temperature ºC

Air 
evaporator

Gas inlet temperature ºC

Gas outlet temp. (3)

ºC

Gas outlet temp. (4)

ºC

Air inlet temperature

ºC

Air inlet temperature

ºC

Outdoor temperature ºC

Outdoor temperature ºC

Air outlet temperature ºC

Air outlet temperature ºC

Air 
evaporator

Air inlet temperature

ºC

Air 
condenser

Air inlet temperature

ºC

Air outlet temperature ºC

Air outlet temperature ºC

Gas inlet temperature ºC

Gas inlet temperature ºC

Evap. outlet temp. (4) ºC

Gas outlet temp. (3)

ºC

Subcooling (2) - (3)

ºC

Subcooling (2) - (3)

ºC

Overheating (4) - (1)

ºC

Overheating (4) - (1)

ºC

Содержание 48EH

Страница 1: ...ERATION AND MAINTENANCE INSTRUCTIONS 48EN EH Nominal cooling capacity 58 9 135 5 kW Nominal heating capacity 62 2 143 4 kW 50 Hz Packaged rooftop cooling only heat pumps with integrated gas burner Ori...

Страница 2: ...ommissioning and maintenance operations 8 7 Gas Burner 9 Operating principle 9 Control of the gas burner 10 8 Safety elements 11 Safety devices in the gas burner 11 Safety devices in the 48EN EH unit...

Страница 3: ...lation and reliable operation Space 48EN Series Autonomous air air cooling units with a compact horizontal rooftop design with a built in gas burner Space 48EH Series Autonomous reversible air air hea...

Страница 4: ...5 900 18 000 18 200 20 400 24 000 Available static pressure mm w c 12 12 12 12 12 12 12 12 15 15 Type Centrifugal Number no turbines 2 2 Motor output kW 2 x 1 5 2 x 2 2 2 x 3 2 x 1 1 2 x 2 2 2 x 2 2 2...

Страница 5: ...ents during installation commissioning or maintenance it is required to take into consideration the units specifications refrigerated circuits under pressure refrigerant presence voltage presence and...

Страница 6: ...said vapours Although the R 410A is not flammable when in contact with a flame or hot spot it can decompose thus producing fluorhydric acid HF and fluophosgene COF2 which are highly toxic and corrosiv...

Страница 7: ...re can withstand the weight of the unit Since the unit is designed to work outdoors some specific installation norms must be followed The unit will be located on the roof of the premises If it is fore...

Страница 8: ...02 450 404 66 414 368 1805 MA MC0 1845 2095 137 498 438 63 424 364 1925 322 MO 1845 2095 72 432 397 74 433 398 1806 MS 1845 2095 107 471 423 69 434 385 1888 MA MC0 1845 2095 143 520 457 66 443 380 200...

Страница 9: ...lectrode nozzle Control device On off signal Burner fan EVP pilot light flame EV1 1st electromagnetic valve gas EV2 2nd electromagnetic valve gas A B C D E F Operation of the air gas premix The air an...

Страница 10: ...imit the power supplied by the burner This avoids the stratification of the hot air masses and that the outlet air temperature exceeds a maximum safety level 55 C by default which will cause the burne...

Страница 11: ...or the modulation are outside the range Failure in the fan motor F4 F5 F6 Unused F7 No serial communication The remote control is disconnected F8 The flame control device does not work The flame contr...

Страница 12: ...utomatic reactivation It is installed in the auxiliary electric panel Anti fire safety device This safety device integrated in the control shuts down the unit if the probe located in the return detect...

Страница 13: ...ces etc refer to The information supplied in this document table of technical characteristics Data plate The wiring diagram and the legend supplied with the unit The CARRIERrtc electronic control broc...

Страница 14: ...burns Note The gas burner chimney is not supplied with the unit Its design and installation is the responsibility of the engineer and must comply with all the directives and regulations in force in t...

Страница 15: ...ibration transmission Air ducts connections Checks in the axial fans Before commissioning check the blade rotation direction and that the axis turns without strokes nor vibrations Once running check t...

Страница 16: ...Condensates outlet Before commissioning check the blade rotation direction and that the axis turns without strokes nor vibrations Once running check the operation conditions pressures flows and consum...

Страница 17: ...unit and all the components used This will be very helpful for maintenance and repairs to the installation Check that the electrical power supply matches the unit voltage and that its value lies with...

Страница 18: ...means this has to be taken into account in the selection of higher pressure fans optional or in the substitution of the standard pulley set with a new set that generates a higher turn speed to the pa...

Страница 19: ...ually Depending on the installation conditions the filter aspect must be examined to define the cleaning periodicity Gravimetric filters Cleaning the filtering mesh can be done with a household vacuum...

Страница 20: ...f the charge Note Both the oil type as well as the volume needed for each model are stated in the Technical characteristic tables in chapter 3 Caution Before starting any maintenance operations ensure...

Страница 21: ...n Burner Safety Devices Open the valve unblock the control and check that the burner is operating correctly 8 The safety thermostat and the air differential pressostat With the burner in operation ope...

Страница 22: ...rature of air or water in condenser very low air or water flow very high adjust flow f Repair Compressor does not start does not make noise humming a No power b The contacts of a control element are o...

Страница 23: ......

Страница 24: ...Order No 10051 03 2015 Supersedes order No New Manufactured for CARRIER in Spain The manufacturer reserves the right to change the specification without prior notice Printed in the European Union...

Отзывы: