When the first-stage thermostat is satisfied, first-stage main

gas valve and the pilot valve close. Induced-draft motor shuts
off. Time-delay relay (built into constant volume control board)
opens and timer sequence begins. When sequence is com-
plete (after 110 ± 5 seconds) evaporator-fan motor shuts off.

48 Series High-Heat Units — Unit power on, thermostat sys-
tem switch set at HEAT or AUTO. position, and fan switch
set at AUTO. position.

First-stage thermostat (W1) calls for heat. Time-delay re-

lay (built into constant volume control board), controlling
evaporator fan, begins timer sequence (approximately 55 ±
10-second delay).

When time-delay sequence is complete, time-delay relay

closes and evaporator fan starts.

When evaporator fan starts, airflow switch closes, closing

induced draft contactor, and induced draft motor starts.

Centrifugal switch closes. Pilot valve opens, allowing gas

to flow to first-stage pilot. Spark ignitor ignites pilot flame.
Sensor detects flame, energizes main gas valve coil, and main
gas valve opens. Gas flows to main burners and first-stage
burners ignite. Spark ignitor shuts off and pilot remains on.

The spark ignitor will continue to spark for 90 seconds

until pilot flame is sensed. If the pilot fails to ignite or the
sensor fails to detect flame, the pilot valve closes and the
spark ignitor shuts off for 300 seconds (5 minutes). During
this time the induced draft motor remains on to purge any
unburnt gas from the combustion tubes. This ignition se-
quence will repeat indefinitely.

When additional heat is needed, W2 is energized. Pilot

valve no. 2 opens, allowing gas to flow to second-stage pi-
lot. Spark ignitor ignites pilot flame. Sensor detects flame,
energizes main gas valve coil, and main gas valve no. 2 opens.
Gas flows to main burners and second-stage burners ignite.
Second-stage spark ignitor shuts off. When the second-stage
thermostat is satisfied, W2 is deenergized and the second
induced-draft motor and gas valve are shut off.

When the first-stage thermostat is satisfied, first-stage main

gas valve and the pilot valve close. Induced draft motor shuts
off. Time-delay relay (built into constant volume control board)
opens and timer sequence begins. When sequence is com-
plete (after 110 ± 5 seconds) evaporator-fan motor shuts off.

50 Series Units — Unit power on, system selector switch
set at HEAT position, fan switch set at AUTO. position.

On a call for heating, W1 on the thermostat closes, and

evaporator fan and the first stage of electric heat are ener-
gized. On a further drop in room temperature, W2 on the
thermostat closes, energizing the second stage of electric heat.
NOTE: Units equipped with low electric heat option have
only one stage. Reset thermostat to a setting below room
temperature. Electric heat and evaporator fan shut off.

COOLING, UNITS WITH ECONOMIZER — With sub-
base switch set at COOL position and fan switch set at AUTO.
position, evaporator fan is energized when Y1 on thermostat
closes. If enthalpy is below setting on enthalpy switch, the
economizer outdoor-air dampers will modulate open to sat-
isfy the cooling requirement. If outdoor air alone will not
meet the cooling requirements, Y2 on the thermostat will
close energizing compressor no. 1 to work in conjunction
with the modulating economizer to meet the cooling require-
ment. While the unit is operating using outdoor air, com-
pressor no. 2 cannot be energized. If enthalpy is above set-
ting on enthalpy switch, the economizer outdoor-air dampers
move to the minimum (ventilation) position, and condenser
fan numbers 1 and 2 cycle on and off as described in Cool-
ing, Units Without Economizer section on page 41.
NOTE: If fan switch is ON position and the room thermostat
is satisfied, the outdoor-air dampers move to the minimum
position.

HEATING, UNITS WITH ECONOMIZER — Operation is
the same as described in Heating, Units Without Econo-
mizer sections on page 41, except that the outdoor-air damp-
ers move to the minimum position on a call for heat.

VENTILATION-AIR CIRCULATION (Continuous Fan) —
Turn unit power on. Set system selector switch at OFF, HEAT,
or COOL position, and set fan switch at ON position.

Evaporator-fan contactor is energized through the switch

on the thermostat and the evaporator fan runs continuously.
The damper moves to the minimum position.

AUTOMATIC CHANGEOVER USING AUTOMATIC
CHANGEOVER THERMOSTAT — Turn unit power on. Set
system selector switch at AUTO. position.

When the temperature of the conditioned space rises to

the cooling selector lever setting, unit automatically switches
from heating to cooling mode. When the temperature of the
conditioned space falls to the heating selector switch setting,
unit automatically changes from cooling to heating mode.
The thermostat is interlocked so that cooling and heating sys-
tems do not operate at the same time.

Head Pressure Control

— All units have a fan cy-

cling thermostat which cycles the no. 2 condenser fan. This
switch opens at 60 F ± 3° F and closes at 70 F ± 3° F. This
allows the unit to operate down to 45 F outdoor ambient
temperature.
NOTE: Accessory −20 F Low Ambient Kit is available, which
allows mechanical cooling to −20 F outdoor ambient. See
accessory installation instructions for mounting and opera-
tion details.

SERVICE

Service Access —

All unit components can be reached

through clearly labeled hinged access doors. These doors are
not equipped with tiebacks, so if heavy duty servicing is needed,
either remove them or prop them open to prevent accidental
closure.

Each door is held closed with 3 latches. The latches are

secured to the unit with a single 1/4-in.

2

20 x 1/2-in. long

bolt. See Fig. 33.

To open, loosen the latch bolt using a 7/16-in. wrench.

Pivot the latch so it is not in contact with the door. Open the
door. To shut, reverse the above procedure.
NOTE: Disassembly of the top cover may be required under
special service circumstances. It is very important that the
orientation and position of the top cover be marked on the
unit prior to disassembly. This will allow proper replace-
ment of the top cover onto the unit and prevent rainwater
from leaking into the unit.

IMPORTANT: After servicing is completed, make sure
door is closed and relatched properly, and that the latches
are tight. Failure to do this can result in water leakage
into the indoor-air section of the unit.

COMPRESSORS

Sizes 034 and 044 — Access to the compressors is through
the doors on the condenser end of the unit. This door also
provides access to the discharge and suction service valves,
the crankcase heaters, and the high- and low-pressure switches.
Compressor no. 1 is always the compressor on the left when
facing main control box.
Sizes 054-074 — The oil pump end (compressor access) of
each compressor is readily accessible from sides of unit as
shown in Fig. 17. Access the motor end of the compressor
through the condenser end of the unit or by removing
compressor.

42

Содержание 48DJ

Страница 1: ...ATIC CHANGEOVER THERMOSTAT Head Pressure Control 42 SERVICE 42 53 Service Access 42 COMPRESSORS LIQUID SERVICE VALVES FILTER DRIERS AND SIGHT GLASSES EVAPORATOR FAN MOTORS PULLEYS AND BELTS POWER EXHA...

Страница 2: ...shock could cause personal injury Do not try to light any appliance Do not touch any elec trical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone...

Страница 3: ...read with four 95 in 2413 mm and 2 8A 1 B 1 A8 long spreader bars 2 Center of gravity includes economizer 1 All panels must be in place when rigging 2 Unit is not designed for handling by forklift tru...

Страница 4: ...nal Cfm 10 500 14 000 Maximum Allowable Cfm 15 000 20 000 Maximum Allowable Rpm 900 900 Shaft Diameter at Pulley in 111 16 111 16 EVAPORATOR FAN MOTOR AND DRIVE Any motor available on any unit Motor H...

Страница 5: ...0 000 40 000 50 000 Motor Hp Rpm 1 0 1140 1 0 1140 1 0 1140 EVAPORATOR FAN Centrifugal 30 x 27 in Nominal Cfm 17 500 21 000 24 500 Maximum Allowable Cfm 25 000 30 000 30 000 Maximum Allowable Rpm 750...

Страница 6: ...n roof curb and ducts as required Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier Outlet grilles must not lie directly below unit discharge The return d...

Страница 7: ...7344 24 11 8 4141 13 71 16 UNIT LEVELING TOLERANCES DIMENSIONS degrees and inches A B Deg in Deg in 1 0 2 0 50 75 From edge of unit to horizontal NOTES 1 Roof curb is shipped unassembled 2 Roof curb 1...

Страница 8: ...24 51 16 5933 19 59 16 UNIT LEVELING TOLERANCES DIMENSIONS degrees and inches A B Deg in Deg in 1 0 2 0 50 75 From edge of unit to horizontal NOTES 1 Roof curb is shipped unassembled 2 Roof curb 14 g...

Страница 9: ...ANCES DIMENSIONS degrees and inches A B Deg in Deg in 1 0 2 0 50 75 From edge of unit to horizontal NOTE To prevent the hazard of stagnant water build up in the drain pan of the indoor air section uni...

Страница 10: ...outward There is a total of 4 hoods 5 Install 18 screws 5 each side 6 top and 2 bottom around the outside of each hood Screws are in the fastener pack age taped to the basepan inside the fan section 6...

Страница 11: ...50DW DY NB LEGEND CONN Connection DIM Dimension NOTES 1 Dimensions in are in millimeters 2 Center of Gravity includes economizer Unit weight does not include economizer 3 Unit clearances Top Do not re...

Страница 12: ...es economizer Unit weight does not include economizer 3 Unit clearances Top Do not restrict condenser fans Control Box End 68 09 Sides 68 09 Economizer End 68 09 except power exhaust units 108 09 For...

Страница 13: ...units On 50 series units dimension given is measured from economizer end of unit to drain connection closest to condenser fans NOTES 1 Dimensions in are in millimeters 2 Center of Gravity includes ec...

Страница 14: ...r Unit weight does not include economizer 3 Unit clearances Top Do not restrict condenser fans Control Box End 68 09 Sides 68 09 except power exhaust units 108 09 Economizer End 68 09 except power exh...

Страница 15: ...NITS 044 074 UNITS Fig 5 Drain Location Selection Fig 6 Condensate Drain Location Fig 7 Seal Plate Location ROOF MOUNT DRAIN SLAB MOUNT DRAIN Fig 8 Condensate Drain Piping Details Fig 9 Outdoor Air Ho...

Страница 16: ...Adjustments Inside of Hood Shown O ENTHALPY SENSOR Fig 11 Enthalpy Sensor Fig 12 Enthalpy Sensor Location CONTROL CURVE CONTROL POINT Approx Deg AT 50 RH A 73 B 68 C 63 D 58 Fig 13 Psychrometric Char...

Страница 17: ...Fig 17 A 4 5 32 in hole for field power wiring and a 7 8 in hole for 24 v control wiring are provided in the bottom of the control box Field supplied couplings must be used when rout ing wiring into...

Страница 18: ...formula to determine the percent voltage imbalance Voltage Imbalance max voltage deviation from average voltage 100 x average voltage Example Supply voltage is 460 3 60 AB 452 v BC 464 v AC 455 v 452...

Страница 19: ...393 8 400 400 6 0 21 2 20 0 29 36 78 9 91 0 197 9 192 5 250 250 6 0 21 2 20 0 59 72 157 7 182 0 254 9 280 0 300 350 6 0 21 2 20 0 88 108 236 6 273 0 353 5 393 8 400 400 10 0 33 4 30 0 29 36 78 9 91 0...

Страница 20: ...6 36 46 3 93 8 110 6 0 9 6 72 93 0 133 7 150 6 0 9 6 108 139 0 191 2 200 10 0 15 2 36 46 3 99 4 125 10 0 15 2 72 93 0 133 7 150 10 0 15 2 108 139 0 191 2 200 15 0 22 0 36 46 3 106 2 125 15 0 22 0 72 9...

Страница 21: ...72 72 0 111 2 125 10 0 12 2 108 108 0 156 2 175 15 0 18 0 36 36 0 91 8 110 15 0 18 0 72 72 0 111 2 125 15 0 18 0 108 108 0 156 2 175 20 0 22 0 78 8 100 6 0 7 8 86 6 100 10 0 12 2 91 0 110 15 0 18 0 9...

Страница 22: ...72 157 7 182 0 236 1 262 5 300 300 10 0 33 4 30 0 88 108 236 6 273 0 334 2 376 3 350 400 15 0 48 4 44 0 29 36 78 9 91 0 251 1 243 9 300 300 15 0 48 4 44 0 59 72 157 7 182 0 251 1 262 5 300 300 15 0 4...

Страница 23: ...0 10 0 15 2 72 93 0 142 5 175 10 0 15 2 108 139 0 200 0 200 15 0 22 0 36 46 3 128 9 150 15 0 22 0 72 93 0 142 5 175 15 0 22 0 108 139 0 200 0 200 20 0 27 0 112 9 125 6 0 9 6 122 5 150 10 0 15 2 128 1...

Страница 24: ...7 8 36 36 0 86 1 110 6 0 7 8 72 72 0 103 7 110 6 0 7 8 108 108 0 148 7 150 10 0 12 2 36 36 0 90 5 110 10 0 12 2 72 72 0 103 7 110 10 0 12 2 108 108 0 148 7 150 15 0 18 0 36 36 0 96 3 110 15 0 18 0 72...

Страница 25: ...3 426 3 500 500 10 0 33 4 30 4 29 36 78 9 91 0 338 8 329 0 400 400 10 0 33 4 30 4 59 72 157 7 182 0 338 8 329 0 450 450 10 0 33 4 30 4 88 108 236 6 273 0 389 3 426 3 500 500 15 0 48 4 44 0 29 36 78 9...

Страница 26: ...36 46 3 150 8 200 10 0 15 2 72 93 0 150 8 200 10 0 15 2 108 139 0 207 5 225 15 0 22 0 36 46 3 157 6 200 15 0 22 0 72 93 0 157 6 200 15 0 22 0 108 139 0 207 5 225 20 0 28 0 36 46 3 163 6 200 20 0 28 0...

Страница 27: ...0 132 3 150 15 0 18 0 72 72 0 132 3 175 15 0 18 0 108 108 0 168 7 200 20 0 22 0 36 36 0 136 3 175 20 0 22 0 72 72 0 136 3 175 20 0 22 0 108 108 0 168 7 200 30 0 32 0 119 3 150 10 0 12 2 131 5 150 15...

Страница 28: ...59 72 157 7 182 0 371 7 361 9 450 450 15 0 48 4 44 0 88 108 236 6 273 0 371 7 408 8 450 450 20 0 61 6 56 0 29 36 78 9 91 0 384 9 373 9 450 450 20 0 61 6 56 0 59 72 157 7 182 0 384 9 373 9 450 450 20 0...

Страница 29: ...3 180 6 225 15 0 22 0 72 93 0 180 6 225 15 0 22 0 108 139 0 216 3 250 20 0 28 0 36 46 3 186 6 225 20 0 28 0 72 93 0 186 6 225 20 0 28 0 108 139 0 216 3 250 30 0 40 0 164 6 200 10 0 15 2 179 8 225 15...

Страница 30: ...36 36 0 131 8 150 10 0 12 2 72 72 0 131 8 150 10 0 12 2 108 108 0 162 5 175 15 0 18 0 36 36 0 137 6 175 15 0 18 0 72 72 0 137 6 175 15 0 18 0 108 108 0 162 5 175 20 0 22 0 36 36 0 141 6 175 20 0 22 0...

Страница 31: ...3 426 3 500 500 10 0 33 4 30 4 29 36 78 9 91 0 420 8 411 0 500 500 10 0 33 4 30 4 59 72 157 7 182 0 420 8 411 0 500 500 10 0 33 4 30 4 88 108 236 6 273 0 420 8 426 3 500 500 15 0 48 4 44 0 29 36 78 9...

Страница 32: ...36 46 3 188 0 250 10 0 15 2 72 93 0 188 0 250 10 0 15 2 108 139 0 207 5 250 15 0 22 0 36 46 3 194 8 250 15 0 22 0 72 93 0 194 8 250 15 0 22 0 108 139 0 207 5 250 20 0 28 0 36 46 3 200 8 250 20 0 28 0...

Страница 33: ...0 161 8 200 15 0 18 0 72 72 0 161 8 200 15 0 18 0 108 108 0 168 7 200 20 0 22 0 36 36 0 165 8 200 20 0 22 0 72 72 0 165 8 200 20 0 22 0 108 108 0 168 7 200 30 0 32 0 148 8 200 10 0 12 2 161 0 200 15...

Страница 34: ...ressurization switch field supplied normally open switch 4 Wire a field supplied switch between TB2 and the C1 connection on the evaporator fan con tactor coil IFC on unit label diagram 5 Switch to is...

Страница 35: ...TIONAL MODULATING POWER EXHAUST OPTIONAL NON MODULATING EXHAUST 054 074 UNITS BASE UNIT BASE UNIT OPTIONAL MODULATING POWER EXHAUST OPTIONAL NON MODULATING EXHAUST Fig 20 Field Wiring for Building Pre...

Страница 36: ...g 24 to ac cess panel using screws provided Hoods go over each com bustion air outlet Sub assemble flue deflector baffle inside the flue deflector hood as shown in Fig 25 and 26 Flue deflector baffle...

Страница 37: ...CATION 48 SERIES HIGH HEAT ONLY FLUE HOOD AND FLUE DEFLECTOR HOOD FLUE AND FLUE DEFLECTOR HOOD LOCATION 48 SERIES HIGH HEAT ONLY FLUE AND FLUE DEFLECTOR HOOD LOCATION SMALL INLET HOOD REMOVED SMALL IN...

Страница 38: ...Check all electrical connections in the unit control box tighten as required Refrigerant Service Valves All units have a Schrader type service port on both suction lines Be sure that caps on the port...

Страница 39: ...s for field supplied drives See Tables 9A and 9B for a complete listing of field supplied pulleys and belt connections Check the lubrication of fan and motor bearings Bearings are shipped full of grea...

Страница 40: ...d 044 units and 750 rpm for 054 074 units The maximum rpm for the power exhaust is 1300 rpm for 034 and 044 units and 925 rpm for 054 074 units Excessive fan speed may result in condensate carryover f...

Страница 41: ...ressor no 1 as first stage of cooling Com pressor no 1 is always the larger of the 2 unit compressors If cooling load cannot be satisfied with only first stage cool ing Y2 on the thermostat will close...

Страница 42: ...ng outdoor air com pressor no 2 cannot be energized If enthalpy is above set ting on enthalpy switch the economizer outdoor air dampers move to the minimum ventilation position and condenser fan numbe...

Страница 43: ...tion MAIN AND PILOT BURNERS 48 Series Units Only At the beginning of each heating season inspect for dete rioration due to corrosion or other causes Observe the pilot and main burner flames and adjust...

Страница 44: ...se block heater contactors HC1 HC1A etc plug No 20 PL20 HEATER BOX 50 Series Units Only Access to the heater box is through the door on the left side sizes 034 and 044 or right side sizes 054 074 of t...

Страница 45: ...am Clean evaporator coil with a stiff bristle brush not wire vacuum cleaner or compressed air Check and clean condensate drain annually at the start of the cooling season Replace return air filters at...

Страница 46: ...for all belts Failure to do so may result in uneven belt stretching 4 Tighten belts using the motor plate adjusting bolts 5 Adjust until proper belt tension 1 2 in deflection with one finger is obtain...

Страница 47: ...ifice is unobstructed then check for spark ignitor mal functions as follows 1 Turn off the control circuit breaker CCB to shut off con trol supply power to ignitor control pack ICP 2 Check that spark...

Страница 48: ...em 1 One Condenser Fan Running Fig 51 Charging Chart 044 Units System 1 All Condenser Fans Running Fig 52 Charging Chart 044 Units System 2 One Condenser Fan Running Fig 53 Charging Chart 044 Units Sy...

Страница 49: ...small screwdriver turn adjustment screw until flame fully engulfs sensor 6 Replace cap on pilot gas valve Turn off power to unit Return valve s to original position 7 Check for proper burner operation...

Страница 50: ...t off power to unit 3 Unplug PL9 and PL10 on high heat and all sensor and ignitor wires 4 Disconnect gas connection s from between gas valve s and field supplied piping See Fig 37 and 38 5 Remove 2 sc...

Страница 51: ...rol power Crankcase Heater Each compressor has a crankcase heater to prevent absorption of liquid refrigerant by oil in the crank case when the compressor is idle Since 115 v power for the crankcase h...

Страница 52: ...adjustments and elec trical plugs accessible through the top of the cover The econo mizer control is factory wired to the terminals on the motor All potentiometers and adjustments are a part of the co...

Страница 53: ...TED RESULT AND RESPONSE A Outdoor Air Sensor 1 Connect the enthalpy sensor terminal 1 to terminal 1 on the motor 2 Connect the positive ter minal of a DC milliam meter to terminal S of the sensor 3 Co...

Страница 54: ...problem is external to the board Reconnect plug P1 if troubleshooting is com plete and plug P3 to the board Symptom Condenser fan no 2 5 will not operate 1 Check operation of condenser fan no 1 If fa...

Страница 55: ...r and con tactor closes the board is operating properly 8 To verify compressor lockout logic a Disconnect CLO sensor wires connected to CLO2 at the control board Check wires for continuity If there is...

Страница 56: ...LEGEND CLO Compressor Lockout P Plug SC Safety Circuit Fig 65 Compressor Lockout Connections 56...

Страница 57: ...r Evaporator Fan Contactor IFCB Indoor Evaporator Fan Circuit Breaker IFM Indoor Evaporator Fan Motor IGV Inlet Guide Vanes IGVM Inlet Guide Vanes Motor LPS Low Pressure Switch LS Limit Switch LSR Lim...

Страница 58: ...Fig 66 Gas Heat Sections 48DJ NP034 044 Units 58...

Страница 59: ...Fig 67 Gas Heat Sections 48DJ NP054 074 Units 59...

Страница 60: ...Fig 68 Gas Heat Section 48DK034 044 Units 60...

Страница 61: ...Fig 69 Gas Heat Section 48DK054 074 Units 61...

Страница 62: ...Fig 70 Typical Wiring Schematic 48 50DJ 50DW Units 054 074 Shown 62...

Страница 63: ...Fig 70 Typical Wiring Schematic 48 50DJ 50DW Units 054 074 Shown cont 63...

Страница 64: ...Fig 71 Typical Wiring Schematic 48 50DK 50DY Units 054 074 Shown 64...

Страница 65: ...Fig 71 Typical Wiring Schematic 48 50DK 50DY Units 054 074 Shown cont 65...

Страница 66: ...Fig 72 Typical Control Wiring Schematic 48 50NP 50NB Units 054 074 Shown 66...

Страница 67: ...Fig 72 Typical Control Wiring Schematic 48 50NP 50NB Units 054 074 Shown cont 67...

Страница 68: ...Fig 72 Typical Control Wiring Schematic 48 50NP 50NB Units 054 074 Shown cont 68...

Страница 69: ...Fig 73 Typical Power Wiring Schematic 48 50NP 50NB Units 054 074 208 230 and 460 v Shown 69...

Страница 70: ...assette and or slides and a companion booklet Use these for self teaching or to conduct full training sessions For a free Service Training Material Catalog STM call 1 800 962 9212 Ordering instruction...

Страница 71: ......

Страница 72: ...PRESSOR NO 2 L1 L2 L3 SUPPLY FAN AMPS EXHAUST FAN AMPS ELECTRIC HEAT AMPS L1 L2 L3 TEMPERATURES OUTDOOR AIR TEMPERATURE F DB Dry Bulb RETURN AIR TEMPERATURE F DB F WB Wet Bulb COOLING SUPPLY AIR F GAS...

Отзывы: