If roof curb is not used, support unit with steel beams along
its entire length and then support steel as required. As a mini-
mum, unit must be supported across its width at each lifting
lug location.
Positioning —
Provide clearance around and above unit
for airflow, safety, and service access. Do not restrict top (area
above condenser fans) in any way. Allow at least 6 ft on all
sides for rated performance, code compliance, and service.
Do not install unit in an indoor location. Do not locate air
inlets near exhaust vents or other sources of contaminated
air.
On units equipped with or power exhaust option, high ve-
locity air is exhausted out the hoods. Unit should be posi-
tioned with at least 10 ft clearance between the exhaust hoods
and any obstruction. Although unit is weatherproof, guard
against water from higher level runoff and overhangs.
NOTES:
1. Sizes 034,044: Rig with 4 cables and spread with two 95 in. (2413 mm) and
2
8
A
1
A
8
long spreader bars.
Sizes 054-074: Rig with 4 cables and spread with four 95 in. (2413 mm) and
2
8
A
1
B
1
A
8
long spreader bars.
2. Center of gravity includes economizer.
1. All panels must be in place when rigging.
2. Unit is not designed for handling by forklift truck.
RIGGING WEIGHTS AND DIMENSIONS
UNIT
UNIT WEIGHT*
A
B
Lb
Kg
in.
mm
in.
mm
48DJD,DKD,NPD034
5941
2694.8
86.0
2185
109.4
2780
48DJE,NPE034
6070
2753.4
110.4
2804
48DJD,DKD,NPD044
6841
3103.1
92.6
2353
127.6
3240
48DJE,NPE044
6970
3161.6
128.6
3267
48DJD,DKD,NPD054
9230
4186.7
121.5
3086
126.8
3221
48DJE,NPE054
9350
4241.2
48DJD,DKD,NPD064
9530
4322.8
48DJE,NPE064
9650
4377.2
48DJD,DKD,NPD074
9950
4513.3
134.7
3421
134.7
3421
48DJE,NPE074
10,080
4572.3
50DJ,DK,NP034
5700
2585.5
84.8
2153
120.8
3067
50DW,DY,NB034
6270
2844.1
76.4
1940
102.5
2604
50DJ,DK,NP044
6350
2880.4
92.6
2353
126.6
3216
50DW,DY,NB044
6920
3138.9
86.0
2185
108.4
2753
50DJ,DK,NP054
8230
3733.1
120.8
3066
126.8
3221
50DW,DY,NB054
8780
3982.6
109.0
2769
109.0
2769
50DJ,DK,NP064
8530
3869.2
120.9
3071
120.9
3071
50DW,DY,NB064
9080
4119.7
120.8
3066
126.8
3221
50DJ,DK,NP074
8960
4064.3
131.7
3345
137.6
3495
50DW,DY,NB074
9500
4309.2
109.0
2769
109.0
2769
*Includes optional economizer.
Fig. 1 — Rigging Label
3
Содержание 48DJ
Страница 56: ...LEGEND CLO Compressor Lockout P Plug SC Safety Circuit Fig 65 Compressor Lockout Connections 56...
Страница 58: ...Fig 66 Gas Heat Sections 48DJ NP034 044 Units 58...
Страница 59: ...Fig 67 Gas Heat Sections 48DJ NP054 074 Units 59...
Страница 60: ...Fig 68 Gas Heat Section 48DK034 044 Units 60...
Страница 61: ...Fig 69 Gas Heat Section 48DK054 074 Units 61...
Страница 62: ...Fig 70 Typical Wiring Schematic 48 50DJ 50DW Units 054 074 Shown 62...
Страница 63: ...Fig 70 Typical Wiring Schematic 48 50DJ 50DW Units 054 074 Shown cont 63...
Страница 64: ...Fig 71 Typical Wiring Schematic 48 50DK 50DY Units 054 074 Shown 64...
Страница 65: ...Fig 71 Typical Wiring Schematic 48 50DK 50DY Units 054 074 Shown cont 65...
Страница 66: ...Fig 72 Typical Control Wiring Schematic 48 50NP 50NB Units 054 074 Shown 66...
Страница 67: ...Fig 72 Typical Control Wiring Schematic 48 50NP 50NB Units 054 074 Shown cont 67...
Страница 68: ...Fig 72 Typical Control Wiring Schematic 48 50NP 50NB Units 054 074 Shown cont 68...
Страница 69: ...Fig 73 Typical Power Wiring Schematic 48 50NP 50NB Units 054 074 208 230 and 460 v Shown 69...
Страница 71: ......