Table 9B — Field-Supplied Evaporator-Fan Pulley Data, 054-074 Units
IFM
Hp
IFM
RPM
MOTOR PULLEY
BLOWER PULLEY
BELTS
48 Series and 50 Series
Horizontal Discharge Units
50 Series
Vertical Discharge Units
No.
Grooves
Type
Size (in.)
No.
Grooves
Type
Size (in.)
Quantity
Type
Size (in.)
Quantity
Type
Size (in.)
15
450
2
B5V
4.3
2
B5V
18.5
2
5VX
118
2
5VX
132
470
16.1
115
125
485
15.5
123
575
4.5
13.7
112
650
5.1
725
5.7
20
405
3
B5V
4.3
3
B5V
18.5
3
5VX
123
3
5VX
132
470
16.1
118
125
485
15.5
575
2
4.5
2
13.7
2
115
2
123
660
5.1
725
5.7
25
405
3
B5V
4.3
3
B5V
18.5
3
5VX
123
3
5VX
132
470
16.1
115
125
485
15.5
123
575
2
4.5
2
13.7
2
B5V
2
700
5.5
725
5.7
30
470
4
B5V
4.3
4
B5V
16.1
4
5VX
118
4
5VX
123
485
15.5
530
3
4.7
3
15.5
3
3
600
2
5.5
2
15.5
2
2
660
5.9
730
6.5
IFM — Indoor (Evaporator) Fan Motor
Check rotation of wheel with arrow on the fan housing.
Check fan speed with a strobe-type tachometer, or use this
formula:
motor rpm x motor sheave pitch diameter (in.)
Fan
=
Rpm
fan sheave pitch diameter (in.)
(Obtain motor rpm from the fan motor nameplate and read
sheave pitch diameters marked on the fan and motor sheaves.)
Example:
Nameplate motor rpm .................................................. 1760
Motor sheave pitch diameter (in.) .................................. 6.4
Fan sheave pitch diameter (in.) .................................... 12.4
1760 x 6.4
Fan Rpm =
= 908 Rpm
12.4
The maximum allowable fan speed for the supply-air fan
is 900 rpm for 034 and 044 units and 750 rpm for 054-074
units. The maximum rpm for the power exhaust is 1300 rpm
for 034 and 044 units and 925 rpm for 054-074 units.
Excessive fan speed may result in condensate carryover from
the evaporator coil, fan motor overload, or wheel failure. See
Table 10 for Air Quantity Limits.
Table 10 — Air Quantity Limits (cfm)
UNIT SIZE
MINIMUM
MAXIMUM
034
6,000
15,000
044
8,000
20,000
054
10,000
25,000
064
12,000
30,000
074
14,000
30,000
Condenser Fans and Motors —
Each unit has mul-
tiple condenser fans and motors; these are positioned at the
factory. See Fig. 32 for correct location of fan in orifice. Check
that fan propeller rotation is correct; it should be counter-
clockwise when facing the fans. If fan propeller rotation is
incorrect, switch motor leads.
Return-Air Filters —
Check that the correct filters are
installed in the filter rack. See Tables 1A and 1B for quan-
tities and sizes. Access is through the door marked FILTER
SECTION. Do not operate the unit without return-air filters.
Economizer Inlet Screens —
Check that they are in
place before operating the unit.
Economizer Dampers —
With no power to the unit,
the economizer outdoor-air dampers should be fully closed.
Check by opening the access door marked FILTER SEC-
TION. On units with economizer, be sure economizer mini-
mum position is set at the desired setting. Be sure hood is
installed properly.
25% Outdoor-Air Damper —
On units without econo-
mizer, be sure 25% outdoor-air damper is set at the desired
position. Also, be sure hood is installed properly.
40
Содержание 48DJ
Страница 56: ...LEGEND CLO Compressor Lockout P Plug SC Safety Circuit Fig 65 Compressor Lockout Connections 56...
Страница 58: ...Fig 66 Gas Heat Sections 48DJ NP034 044 Units 58...
Страница 59: ...Fig 67 Gas Heat Sections 48DJ NP054 074 Units 59...
Страница 60: ...Fig 68 Gas Heat Section 48DK034 044 Units 60...
Страница 61: ...Fig 69 Gas Heat Section 48DK054 074 Units 61...
Страница 62: ...Fig 70 Typical Wiring Schematic 48 50DJ 50DW Units 054 074 Shown 62...
Страница 63: ...Fig 70 Typical Wiring Schematic 48 50DJ 50DW Units 054 074 Shown cont 63...
Страница 64: ...Fig 71 Typical Wiring Schematic 48 50DK 50DY Units 054 074 Shown 64...
Страница 65: ...Fig 71 Typical Wiring Schematic 48 50DK 50DY Units 054 074 Shown cont 65...
Страница 66: ...Fig 72 Typical Control Wiring Schematic 48 50NP 50NB Units 054 074 Shown 66...
Страница 67: ...Fig 72 Typical Control Wiring Schematic 48 50NP 50NB Units 054 074 Shown cont 67...
Страница 68: ...Fig 72 Typical Control Wiring Schematic 48 50NP 50NB Units 054 074 Shown cont 68...
Страница 69: ...Fig 73 Typical Power Wiring Schematic 48 50NP 50NB Units 054 074 208 230 and 460 v Shown 69...
Страница 71: ......