Cool Mode

:

 

If the room temperature is higher than the setting, the compressor will automatically turn on provide a 

cooling effect. On the hand, if the room temperature is lower than the setting, the compressor will automatically turn 

off to stop cooling operation. If indoor fan is programed to be turned off with comp signal, it will turn off once comp 

is cut off 

 

Heat Mode:

 

If the room temperature is lower than the setting, the Electric heater will automatically turn on to 

provide a heating effect. If the room temperature is higher than the setting, the heater will automatically turn off to 

stop heating operation.

 

If indoor fan is programed to be turned off with heater signal, it will turn off once heater is 

cut off but subject to 30 sec dispersing remaining heat timing. 

 

Dry Mode: 

The fan speed runs automatically at low speed and compressor stopping and running is controlled by 

the difference between room and setting temperatures and by continuous running time. If indoor fan is programed 

to be turned off with comp signal, it will turn off once comp is cut off 

- In Dry mode, the humidity is reduced in the space to be air-conditioned. 

 

Fan Mode: 

There will be no cooling or heating effects; only the fans of indoor unit will run for ventilation at the 

selected speed (High, Med, and Low). 

-

  In COOL or HEAT mode and if AUTO fan speed is selected; Fan speed is automatically selected by controller 

according to the difference between setting temperature and room temperature, fan will be continuously 

running at low speed after setting temperature is achieved. 

 

Notes: 

a)  Temperature setting range is 16ºC to 30ºC or 60ºF to 85ºF. 

b)  Hold down at the same time for about 5 seconds, Temp down and fan keys will toggle the temperature 

setting from degree C to degree F and vice versa. 

c)  Press any temperature key will flash the current setting temperature for 4 seconds, Should there be no 

further key press, it will revert to room temperature display. Temperature display range is 0 C to 50 C or 32 F 

to 99 F. 

d)  Temp keys are invalid in Fan mode. 

 

6) Sleep Key:

 

Press this key to set the SLEEP timer and then the sleep led will light on, to cancel the sleep timer 

press this key again. 

- Sleep function for healthy sleep to control automatically the room temperature and stop automatically the 

operation of the air conditioner after certain set off time. 

- Sleep mode is valid in cool or heat mode and invalid in Fan mode. 

 

7) Timer Key: 

Upon count down of the set hours, the system will switch from OFF to ON or vice-versa. 

  -  OFF Timer Function to stop automatically, the air conditioner after certain set OFF time. 

  -  ON Timer Function to start automatically, the air conditioner after certain set ON time. 

    * Timer setting is 1 Hour to 24 Hour. The timer led will light on when operating the Timer Function 

    First key press will flash the digital display and Timer Led for 3 seconds. 

 

 

Notes: 

a)  The digital displays show the number of hours previously set, only the Timer Led flashes. 

b)  Subsequent 3 seconds will show the number of hours previously set; only the timer led flashes. 

c)  Should there be no further key press, it will revert to normal mode. 

d)  Should Timer key is not released timer setting will increase automatically every 0.5-second. 

 

8) Sensor:

 

Receives the remote controller’s signal 

9) Display Screen:

 

Displays the set temperature and displays also the TIMER settings when adjusting it.

 

10) Key Lock Mode:

 

 

To activate key lock mode, hold down for 3 seconds, temp. Down Key (5) and Mode Key (2). 

In key lock mode, all keys are not valid except ON/OFF Key (1) to turn ON/OFF the system. 

 

 

Notes: 

a)  Hold down Temp Down and Sleep button for one second to enter into coil temperature display mode. 

Press Temp Up key to display indoor coil temperature, High Fan LED flashes. With the same sequence to 

exit coil temperature display mode. Temperature display range is -9C to 78 ºC. 

b)  Hold down 

 and 

FAN

 buttons for only 1 second ( 5 sec to toggle between ºC and ºF temperature ) 

to activate temperature display setting and auto fan LED flashes. Repeat the same sequence to cancel 
this function. Press 

 or 

 button to change the setting from 1 to 2. “1” means disable room 

temperature display and “2” means enable room temperature display. 

 

Menu 

Parameter 

Set Range  Default value 

Remarks 

Temperature display, Auto fan 

LED flashing 

1~2 

1: Disable room temp display 

2: Enable room temp display 

Cool mode fan control function, 

Auto & High fan LED flashing 

1~2 

1: Comp OFF, Fan ON 

2: Comp OFF, Fan OFF 

Heat mode fan control function, 

Auto & Medium fan LED flashing 

1~2 

1: Heater OFF, Fan ON 

2: Heater OFF, Fan OFF 

 

Содержание 42TD Series

Страница 1: ...rvicing air conditioning equipment can be hazardous due to system pressure and electrical components Only trained and qualified service personnel should install repair or service air conditioning equi...

Страница 2: ...hould be checked before the installation is started The installer should be familiar with each of the following requirements before the actual installation Space requirement and clearance See Fig 3 Ce...

Страница 3: ...outlet High speed 0 Static Table 3 Physical Data 42TW4 42TD4 4 Pipe System Model 42TW4 Model 42TD4 Size 03 04 05 06 08 10 11 14 CFM 313 533 623 702 795 1065 1247 1416 Cooling Capacity kw 3 4 5 3 6 9 8...

Страница 4: ...0 38 0 29 0 44 0 34 0 24 Watts 109 91 73 93 75 56 86 67 48 10 Amps 0 84 0 75 0 65 0 72 0 62 0 53 0 64 0 54 0 44 Watts 164 145 127 140 121 103 124 105 86 11 Amps 1 03 0 84 0 65 0 86 0 70 0 53 0 78 0 61...

Страница 5: ...7 1055 1091 16 2062 1575 1268 1770 1295 1530 H At High Fan Speed M At Medium Fan Speed L At Low Fan Speed Table 6 b Fan Performance 42TW 4 SI 42TW4 Air Flow m 3 hr Ex Static Pres Pa 0 12 5 25 37 5 Uni...

Страница 6: ......

Страница 7: ...age against available power supply For special installation consult local building and electrical codes INSTALLATION PLACING UNIT IN POSITION 1 Select the unit location Allow adequate space for free a...

Страница 8: ...unit to operate within duct external static pressure limits as shown on job submittals Units designed to operate with ductwork may be damaged if operated without intended ductwork attached Units provi...

Страница 9: ...inutes to prevent overloading 2 Operation Mode Selection Key Toggles the operation mode Cool Dry Heat or Fan only 3 Fan Speed Selection Key Toggles the fan speed Auto High Medium or Low Note Fan key i...

Страница 10: ...n Sleep function for healthy sleep to control automatically the room temperature and stop automatically the operation of the air conditioner after certain set off time Sleep mode is valid in cool or h...

Страница 11: ...WIRING SCHEMATIC 42TW TD COOL HEAT...

Страница 12: ...WIRING SCHEMATIC 42TW TD COOL HEAT WITHOUT CONTROL...

Страница 13: ...fan assembly remove front or bottom panel Fan assembly may be removed from its tracks if unit has a long conduit lead Use a stiff brush or vacuum to remove dirt and debris from scroll Wipe all fan sur...

Страница 14: ...t protected from direct foreign matter Cooling Heating Connections 13 Connect field piping to unit 14 Pressure test all piping for leaks 15 Install drain line traps as required 16 Insulate all piping...

Страница 15: ...NOTES...

Страница 16: ...Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations...

Отзывы: