Code setting of wired controller
Note: ON indicates short circuit; OFF indicates disconnection.
Function Switches
Comparison
Items
Main wired
controller
Auxiliary wired controller
Functions
All functions It can only set shutdown, mode, air quantity, temperature and
swinging.
Code
Switch
status
Function description
Default setting
Remarks
SW1
ON
Auxiliary wired controller
OFF
OFF
Mas ter wired controller
SW2
ON
Common wired controller
ON
OFF
New fan-only has refrigerating,
heating, and air supplying mo-
des
SW3
ON
Display ambient temperature
OFF
OFF
Do not display ambient temperature
SW4
ON
26
o
C lock disabled
ON
OFF
26
o
C lock enabled
SW5
ON
Collect ambient temperature of wi-
red controller
ON
OFF
Collect ambient temperature of
PCB
SW6
ON
Power failure memory disabled
OFF
OFF
Power failure memory enabled
SW7
ON
Temperature sensor 4k7 enabled
ON
Between SW7 and SW8, one
and only one must be ON for any
given period
OFF
Temperature sensor 4k7 disabled
SW8
ON
Temperature sensor 5k1 enabled
OFF
OFF
Temperature sensor 5k1 disabled
21
Electrical Wiring
Difference between Main Wired Controller and Auxiliary Wired Controller
Содержание 40VU007-0182-7G-QEE
Страница 30: ...The manufacturer reserves the right to change any product specifications without notice...
Страница 57: ...Il produttore si riserva il diritto di modificare qualsiasi specifica del prodotto senza preavviso...
Страница 85: ...Le fabricant se r serve le droit de modifier les sp cifications du produit sans pr avis...
Страница 113: ...Der Hersteller beh lt sich das Recht vor Produktspezifikationen ohne Vorank ndigung zu ndern...
Страница 141: ...El fabricante se reserva el derecho de cambiar cualesquiera especificaciones de producto sin previo aviso...
Страница 169: ...O fabricante reserva se o direito de alterar as especifica es do produto sem aviso pr vio...