Please refer to the attached manual for outdoor units.
Please refer to the attached manual for outdoor units.
Add the refrigerant according to the installation instruction for outdoor units. The addition of the R410A refrigerant
must be performed with a measure gage to ensure the specified amount is added. Compressor failure can be
caused by filling too much or too little refrigerant.
Proceed with the flare tube connecting operation to connect all the refrigerant tubes.
• Dual wrenches must be used for connecting the indoor unit tubing.
• For mounting torque, refer to the table on the right.
1. Connecting circular terminals:
The connecting method of the circular terminal is
shown in the Fig. Remove the screw, connect it to the
terminal tier after inserting it through the ring at the end
of the lead and then tighten it.
2. Connecting straight terminals:
The connection method for circular
terminals is shown in the Fig.
Loosen the screw before inserting
the line terminal into the terminal tier, tighten the screw
and confirm that it has been clamped by pulling the line
gently.
3. Pressing connecting line:
After line connection is completed, press the
connecting line with clips that should be pressed on the
protective sleeve of the connecting line.
Tubing permissible length and height difference
Tubing materials and specifications
Refrigerant filling amount
Connecting procedures of refrigerant tubing
Connecting
Model
40VU007~0092 -7G-QEE
40VU012~-0182 -7G-QEE
Tubing Size (mm)
Gas pipe
Ø9.52
Ø12.7
Liquid pipe
Ø6.35
Ø6.35
Tubing Material
Phosphor deoxy bronze seamless pipe (TP2) for air conditioner
Outer Diameter of
Tubing (mm)
Mounting Torque
(N-m)
Increase Mounting
Torque (N-m)
Ø6.35
11.8(1.2kgf-m)
13.7(1.4kgf-m)
Ø9.52
24.5(2.5kgf-m)
29.4(3.0kgf-m)
Ø12.70
49.0(5.0kgf-m)
53.9(5.5kgf-m)
Ø15.88
78.4(8.0kgf-m)
98.0(10.0kgf-m)
Connecting
circular
terminals:
terminal tier
correct
pressing
wrong
pressing
Installation Procedures
pressing
clip
Cutting or enlarging pipes should be carried out by
installation personnel according to the operating
criterion, if the tube is too long or the flare opening
is broken.
Cutting and Enlarging
Vacuumize from the stop valve of outdoor units with
vaccum pump. Refrigerant sealed in indoor machine
is not allowed to use for vaccumization.
Vacuumizing
Open all the valves of outdoor units. [NB: oil balancing
stop valve must be shut up completely when only
connected one main Unit].
Open All Valves
Check if there is any leakage at the connecting part
and bonnet with hydrophone or soapsuds.
Check for Air Leakage
Содержание 40VU007-0182-7G-QEE
Страница 30: ...The manufacturer reserves the right to change any product specifications without notice...
Страница 57: ...Il produttore si riserva il diritto di modificare qualsiasi specifica del prodotto senza preavviso...
Страница 85: ...Le fabricant se r serve le droit de modifier les sp cifications du produit sans pr avis...
Страница 113: ...Der Hersteller beh lt sich das Recht vor Produktspezifikationen ohne Vorank ndigung zu ndern...
Страница 141: ...El fabricante se reserva el derecho de cambiar cualesquiera especificaciones de producto sin previo aviso...
Страница 169: ...O fabricante reserva se o direito de alterar as especifica es do produto sem aviso pr vio...