25
OUTDOOR UNITS
LEGEND
INDOOR UNITS — STANDARD MOTORS
LEGEND
*Motors are designed for satisfactory operation within 10% of nominal voltages shown.
Voltages should not exceed the limits shown in the Voltage Limits column.
INDOOR UNITS — ALTERNATE MOTORS
LEGEND
*Motors are designed for satisfactory operation within 10% of nominal voltages shown.
Voltages should not exceed the limits shown in the Voltage Limits column.
UNIT
38AQS
V-PH-Hz
VOLTAGE RANGE
COMPR
FAN MOTORS
POWER SUPPLY
Min
Max
LRA
RLA
No. of
Fans
FLA
Min Ckt
Amps
MOCP
(Amps)
Fan No. 1
Fan No. 2
008
208/230-3-60
187
254
160
31.5
1
3.1
—
42.5
50
460-3-60
414
508
80
15.7
1
1.4
—
21.0
25
012
208/230-3-60
187
253
170
43.6
2
4.3
3.7
62.5
100
460-3-60
414
528
77
20.0
2
2.3
1.9
29.1
40
575-3-60
518
660
62
15.7
2
1.8
1.8
22.8
35
016
208/230-3-60
187
253
266
63.6
2
4.3
3.7
87.5
125
460-3-60
414
528
120
29.3
2
2.3
1.9
40.7
60
575-3-60
518
660
96
23.8
2
1.8
1.8
33.0
50
FLA
—
Full Load Amps
LRA
—
Locked Rotor Amps
MOCP—
Maximum Overcurrent Protection (Fuse Only)
RLA
—
Rated Load Amps
UNIT
40RMQ
V*-PH-Hz
VOLTAGE
LIMITS
FAN MOTOR
POWER SUPPLY
Hp
FLA
Minimum
Circuit
Amps
MOCP
(Amps)
008
208/230-1-60
187-253
2.4
11.0
13.8
20
208/230-3-60
187-253
2.4
5.2
6.5
15
460-3-60
414-506
2.4
2.6
3.3
15
575-3-60
518-632
2.0
2.3
2.9
15
012
208/230-3-60
187-253
2.4
5.2
6.5
15
460-3-60
414-506
2.4
2.6
3.3
15
575-3-60
518-632
2.0
2.3
2.9
15
016
208/230-3-60
187-253
3.7
10.2
12.8
20
460-3-60
414-506
3.7
4.8
6.0
15
575-3-60
518-632
3.0
3.8
4.8
15
FLA
—
Full Load Amps
Hp
—
Horsepower
MOCP—
Maximum Overcurrent Protection
UNIT
40RMQ
V*-PH-Hz
VOLTAGE
LIMITS
FAN MOTOR
POWER SUPPLY
Hp
FLA
Minimum
Circuit
Amps
MOCP
(Amps)
008
208/230-1-60
187-253
2.4
11.0
13.8
20
208/230-3-60
187-253
2.9
7.5
9.4
15
460-3-60
414-506
2.9
3.4
4.3
15
575-3-60
518-632
3.0
3.8
4.8
15
012
208/230-3-60
187-253
3.7
10.2
12.8
20
460-3-60
414-506
3.7
4.8
6.0
15
575-3-60
518-632
3.0
3.8
4.8
15
016
208/230-3-60
187-253
5.0
15.3/12.8
19.1/16.0
30/25
460-3-60
414-506
5.0
6.4
8.0
15
575-3-60
518-632
5.0
5.1
6.4
15
FLA
—
Full Load Amps
Hp
—
Horsepower
MOCP—
Maximum Overcurrent Protection
Electrical data