5
LEGEND
*Air Conditioning & Refrigeration Institute.
NOTES:
1. Standard ratings are net values, reflecting the effects of circulating fan heat.
Supplementary electric heat is not included. Ratings are based on:
Cooling Standard:
80 F db, 67 F wb indoor entering-air temperature and
95 F db entering-air outdoor unit.
Hi-Temp Heating Standard:
70 F db indoor entering-air temperature and
47 F db/43 F wb entering-air outdoor unit.
Lo-Temp Heating Standard:
70 F db indoor entering-air temperature and
17 F wb/15 F db entering-air outdoor unit.
38AQS008, 012 and 40RMQ008, 012 are rated in accordance with ARI
Standard 210/240-94. 38AQS016 and 40RMQ016 are rated in accordance
with ARI Standard 340/360-93.
2. Sound ratings are in accordance with ARI Standard 270-84.
OUTDOOR
UNIT
38AQS
INDOOR
UNIT
40RMQ
AIRFLOW
(Cfm)
COOLING
HEATING
SOUND
RATING
(Bels)
Hi-Temp
Low-Temp
Net Cap.
(Btuh)
EER
IPLV
Net Cap.
(Btuh)
COP
Net Cap
(Btuh)
COP
008
008
3000
86,000
9.8
N/A
83,000
3.0
46,000
2.0
9.2
012
012
4000
108,000
8.9
11.2
111,000
3.0
62,000
2.0
8.8
016
016
6000
172,000
8.8
9.9
164,000
3.0
94,000
2.2
8.8
Bels —
Sound Level (1 bel = 10 decibels)
COP —
Coefficient of performance =
Btuh output
or
Btuh input
Btuh output
(Based on ARI conditions)
Unit Power Input x 3.413
EER —
Energy Efficiency Ratio =
Btuh
(Based on ARI conditions)
Unit Power Input
IPLV —
Integrated Part-Load Value
ARI* capacities
Содержание 40RMQ
Страница 13: ...13 38AQS012 016 ...
Страница 30: ...30 Typical control wiring schematic cont 38AQS008 ...
Страница 31: ...31 38AQS012 016 208 230 3 60 ...
Страница 32: ...32 Typical control wiring schematic cont 38AQS012 016 460 3 60 575 3 60 COMPONENT ARRANGEMENT ...