
–
50
–
FILE NO. SVM-12052
50 mm
or more
Do not rise the drain hose.
Do not form the drain hose
into the waved shape.
Do not put the
drain hose end
into water.
Do not put the drain
hose end in the
drainage ditch.
Shield pipe
Extension drain hose
Inside the room
Drain hose
10-3-8. Drainage
1. Run the drain hose sloped downwards.
NOTE :
on the outdoor side.
the water is drained out of doors.
•
The hole should be made at a slight downward slant
Fig. 10-3-24
2. Put water in the drain pan and make sure that
3. When connecting extension drain hose, insulate
the connection part of extension drain hose with
shield pipe.
Fig. 10-3-25
Screw
Screw
11
Information
The lower part of indoor unit may float, due to the
condition of piping and you cannot fix it to the
installation plate. In that case, use the
11
screws
trovided to fix the unit and the installation plate.
Fig. 10-3-
23
CAUTION
Arrange the drain pipe for proper drainage from
the unit.
Improper drainage can result in dew-dropping.
This air conditioner has the structure designed
to drain water collected from dew, which forms
on the back of the indoor unit, to the drain pan.
Therefore, do not store the power cord and other
parts at a height above the drain guide.
Space for
pipes
Wall
Drain
guide
11
Fig.
10-3-26
Содержание 39cvur018-703
Страница 94: ...TOSHIBA CARRIER THAILAND CO LTD ...