30
–
Item
6. Release protective
control by tempera-
ture of indoor heat
exchanger
Operation flow and applicable data, etc.
<In cooling/dry operation>
(Prevent-freezing control for indoor heat exchanger)
In cooling/dry operation, the sensor of indoor heat
exchanger detects evaporation temperature and
controls the compressor speed so that temperature of
the heat exchanger does not exceed the specified
value.
Description
1) When temperature of the indoor
heat exchanger drops below 5°C,
the compressor speed is
reduced. (P zone)
2) When temperature of the indoor
heat exchanger rises in the
range from 6°C to under 7°C, the
compressor speed is kept.
(Q zone)
3) When temperature of the indoor
heat exchanger rises to 7°C or
higher, the capacity control
operation returns to the usual
control in cooling operation.
(R zone)
7˚C
6˚C
5˚C
R
Q
P
Usual cooling capacity control
Reduction of compressor speed
Indoor heat e
xchanger temper
ature
When the value is
in Q zone, the
compressor speed
is kept.
FILE NO. SVM-12052
Horizontal
blowing
Inclined
blowing
Blowing
downward
Air direction
Inclined
blowing
Horizontal
blowing
Initial setting of "Storage position"
Louver : (Directs downward 37.4°)
7. Louver control
This function controls the air direction of the indoor unit.
•
Swing operation is performed in width 35°
with the stop position as the center.
•
If the stop position exceeds either upper or lower limit
position, swing operation is performed in width 35° from
the limit which the stop position exceeded.
3) Swing
2) Air direction
•
The position is automatically controlled initial setting of
•
The set louver position is stored in memory by the
The angle of the louver is indicated as the louver closes
"storage position" Louver : (Directs downward 37.4°).
microcomputer, and the louver returns to the stored
position when the next operation is performed.
•
Swing
When pressing
[SWING] button during
operation, the louver
starts swinging.
•
The louver position can
be arbitrarily set up by
pressing [FIX] button.
fully is 0°.
adjustment
1) Louver position
Cooling operation / AUTO (COOL)