27
–
Item
2. Indoor fan
motor control
Operation flow and applicable data, etc.
<In cooling operation>
The indoor fan motor is operated in 5 stages in MANUAL
mode (Fig.1) and 5 stages in AUTO mode (Fig. 2)
Table 1 shown the indoor fan speed and air flow rate of
each mode.
Description
* Symbols
UH
: Ultra High
H
: High
M+
:
M
: Medium
L+
: Low+
L
: Low
L-
: Low–
UL
: Ultra Low
SUL
: Super Ultra Low
* The fan speed broadly varies due
to position of the louver, etc.
The described value indicates one
under condition of inclining
downward blowing.
1) When setting the fan speed to L,
L+, M, M+ or H on the remote
controller, the operation is
performed with the constant
speed shown in Fig. 1.
2) When setting the fan speed to
AUTO on the remote controller,
revolution of the fan motor is
controlled to the fan speed level
shown in Fig. 2 and Table 1
according to the setup tempera-
ture, room temperature, and heat
exchanger temperature.
(Fig. 1)
(Fig. 2)
(Table 1) Indoor fan air flow rate
+2.5
Ta
[˚C]
+2.0
+1.5
+1.0
+0.5
Tsc
a
b
c
d
e
M+(WB)
*3
*4
*5
L(W6)
Air volume AUTO
L
L+
M
M+
H
W6
(L + M) / 2
W9
(M + H) / 2
WC
Indication
Fan speed
Fan speed setup
COOL ON
AUTO
MANUAL
*3 : Fan speed = (M + –L) x 3/4 + L
*4 : Fan speed = (M + –L) x 2/4 + L
*5 : Fan speed = (M + –L) x 1/4 + L
(Linear approximation
from M+ and L)
FILE NO. SVM-12052
Fan speed
level
Fan speed Air flow rate
(rpm) (m3/h)
WF 1000 888
WE 1000 888
WD UH UH 1000 888
WC H H 980 858
WB M+ M+ 920 795
WA M 870 738
W9 M 860 724
W8 800 658
W7 L+ L+ 750 603
W6 L L 740 591
W5 L- L- 700 547
W4 UL UL 700 547
W3 SUL SUL 650 492
W2 500 325
W1 500 325
DRY
COOL
42CVUR018-703