WIRING DIAGRAM NOTES:

1. CARRIER THERMOSTAT WIRING DIAGRAMS ARE ONLY ACCU-

RATE FOR MODEL NUMBERS BEGINNING WITH TSTAT _ _ _ _ _
_ _.

2. WIRING MUST CONFORM TO NEC OR LOCAL CODES.

3. SOME UNITS ARE EQUIPPED WITH PRESSURE SWITCH(ES), TEM-

PERATURE SWITCH, OR 5-MINUTE COMPRESSOR CYCLE PRO-
TECTION.

CONNECT

24-V

FIELD

WIRING

TO

FACTORY-

PROVIDED STRIPPED LEADS.

4. A LIQUID-LINE SOLENOID VALVE IS REQUIRED ON SOME

UNITS.

5. THERMOSTATS ARE FACTORY CONFIGURED WITH 5-MINUTE

COMPRESSOR CYCLE PROTECTION AND 4 CYCLES PER HR
LIMIT. SEE THERMOSTAT INSTALLATION INSTRUCTIONS FOR
DETAILS.

6. TO STAGE ELECTRIC RESISTANCE HEAT, CONSULT OUTDOOR

THERMOSTAT INSTALLATION INSTRUCTIONS.

7. FOR DUAL FUEL THERMOSTATS, UNDERLINED LETTER ON

DUAL TERMINAL INDICATES ITS USAGE.

FOR EXAMPLE: O/W2 MEANS O

O/W2 MEANS W2

OUTDOOR TEMPERATURE SENSOR MUST BE ATTACHED IN ALL
DUAL FUEL INSTALLATIONS.

JUMPER WIRE BETWEEN O/W2 AND L THERMOSTAT TERMI-
NALS MUST BE PRESENT.

8. Y1 AND O CONNECTIONS TO 2-STAGE FURNACES MAY NOT

EXIST OR MAY ONLY BE A WIRE RATHER THAN A SCREW
TERMINAL.

LEGEND

24-V FACTORY WIRING

24-V FIELD WIRING

FIELD SPLICE CONNECTION

OUTDOOR THERMOSTAT

EMERGENCY HEAT RELAY

SUPPLEMENTAL HEAT RELAY

  

SHR

  

EHR

  

ODT

A97413

Fig. 13—Typical 24-v Circuit Connections using Carrier Model DF Thermostat with Single- or 2-Stage Furnace

A97538

G

R

Y/Y2

O/W2

CARRIER

DUAL FUEL

THERMOSTAT

MODEL DF

SINGLE-STAGE

FURNACE

HEAT PUMP

G

Y

W

C

Y

R

O

W2

Y1/W2

C

B

L

S1

S2

R

C

FURNACE

COMPRESSOR

 FAN

24 VAC HOT

24 VAC COM

N/A

RVS HEATING

RVS SENSING

OUTDOOR
SENSOR
CONNECTION

OUTDOOR
TEMPERATURE
SENSOR

W/W1

See note 7

RVS COOLING

A97539

G

R

Y/Y2

O/W2

CARRIER

DUAL FUEL

THERMOSTAT

MODEL DF

TWO-STAGE OR

VARIABLE SPEED

FURNACE

HEAT PUMP

G

C

Y

R

O

W2

Y1/W2

C

B

L

S1

S2

R

C

O

W2

Y1

FURNACE LO

COMPRESSOR

 FAN

24 VAC HOT

24 VAC COM

FURNACE HI

RVS HEATING

RVS SENSING

OUTDOOR
SENSOR
CONNECTION

OUTDOOR
TEMPERATURE
SENSOR

W/W1

W/W1

Y/Y2

See notes 7 and 8

RVS COOLING

10

Содержание 38YSA

Страница 1: ...nal injury or death INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from windows p...

Страница 2: ...irflow a 6 in clearance on 1 side of unit and 12 in on all remaining sides must be maintained Maintain a distance of 24 in between units Position so water snow or ice from roof or eaves cannot fall di...

Страница 3: ...it Step 8 Make Piping Connections Relieve pressure and recover all refrigerant before system repair or final unit disposal to avoid personal injury or death Use all service ports and open all flow con...

Страница 4: ...oltage See unit rating plate for recommended circuit protection device NOTE Operation of unit on improper line voltage constitutes abuse and could affect unit reliability See unit rating plate Do not...

Страница 5: ...asses protective clothing and gloves when handling refrigerant and observe the following Back seating service valves are not equipped with Schrader valves Fully back seat counter clockwise valve stem...

Страница 6: ...A FB FC FD FF FH FAN COIL HEAT PUMP G Y1 W2 L R O INDOOR FAN HEAT STAGE 2 COOL HEAT STAGE 1 NOT USED 24 VAC COM NOT USED TROUBLE OPTIONAL OUTDOOR SENSOR CONNECTION Y C C IF AVAILABLE A98629 24 VAC HOT...

Страница 7: ...W2 Y G R C RVS COOLING C W2 OTHER HP THERMOSTAT FA FB FC FD FF FH FAN COIL HEAT PUMP G O E W2 E W3 R Y 24 VAC COM HEAT STAGE 2 COOL HEAT STAGE 1 INDOOR FAN EMERGENCY HEAT O IF AVAILABLE A98630 24 VAC...

Страница 8: ...VAC COM NOT USED TROUBLE OPTIONAL OUTDOOR SENSOR CONNECTION JW1 A98631 24 VAC HOT R G W W1 Y Y2 Y Y2 Y1 W2 R DH RVS COOLING C B L S1 S2 Y W2 CARRIER PROGRAMMABLE THERMOSTAT MODEL 2S 40FKA FK4C FAN COI...

Страница 9: ...VAC COM HEAT STAGE 2 CUT JW1 SHR SHR FA FB FC FH FAN COIL SMART HEAT ODT A97410 24 VAC HOT R C Y G O RVS COOLING W2 OTHER HP THERMOSTAT FA FB FC FH FAN COIL SMART HEAT HEAT PUMP E R C Y G O W2T W3 W2...

Страница 10: ...UMPER WIRE BETWEEN O W2 AND L THERMOSTAT TERMI NALS MUST BE PRESENT 8 Y1 AND O CONNECTIONS TO 2 STAGE FURNACES MAY NOT EXIST OR MAY ONLY BE A WIRE RATHER THAN A SCREW TERMINAL LEGEND 24 V FACTORY WIRI...

Страница 11: ...observe a complete defrost in warmer weather the thermostat must be closed as follows 1 Turn off power to outdoor unit 2 Disconnect outdoor fan motor lead from OF2 on control board See Fig 15 Tape to...

Страница 12: ...ature F LIQUID PRESSURE AT SERVICE VALVE PSIG REQUIRED SUBCOOLING TEMPERATURE F 5 10 15 20 134 71 66 61 56 141 74 69 64 59 148 77 72 67 62 156 80 75 70 65 163 83 78 73 68 171 86 81 76 71 179 89 84 79...

Отзывы: